Wattstopper ® Passive Infrared Wall Switch Occupancy Sensor (version 3) Détecteur de présence interrupteur mural infrarouge passif (v3) Sensor de ocupación con interruptor a la pared y tecnología de infrarrojo pasivo (v3) Installation Instructions • Instructions d’Installation • Instrucciones de Instalación No: 23950 – 10/18 rev. 3 Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: PW-100/PW-100-347/PW-200/PW-200-347 Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China DESCRIPTION AND OPERATION The PW Passive Infrared Wall Switch sensors use advanced passive infrared (PIR) technology. The PW sensor can turn a load on, and hold it on as long as the sensor detects occupancy. After no movement is detected for the selected time delay, the lights switch off. A “walk-through” mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an occupancy detection. The PW-100 has one relay and one ON/OFF button. The PW-200 contains two relays and two ON/OFF buttons to allow control of one or two loads independently. Pressing a button toggles the state of the corresponding relay. PW sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even if the area is occupied. In the PW-200, light level only affects the load on Relay 2. Users can overrule the hold OFF function by pressing the ON/OFF button. See Light Level Adjustment. Turning Load(s) ON (ON Mode) The relays are programmed independently for either Auto ON or Manual ON. In either mode, the load can be turned ON or OFF using the ON/OFF button. Manual ON DIP 8 ON for Relay 1 DIP 9** ON for Relay 2 With an ON Mode DIP switch in the ON position, the occupant must press the ON/OFF button to turn ON the load. The sensor keeps the load ON until no motion is detected for the selected time delay. There is a 30 second re-trigger delay. If occupancy is detected during the delay, the sensor turns the load back ON. After the re-trigger delay elapses the ON/OFF button must be pressed to turn ON the load. Auto ON DIP 8 OFF for Relay 1 DIP 9** OFF for Relay 2 With an ON Mode DIP switch in the OFF position, the load turns ON and OFF automatically based on occupancy. If the load is turned OFF manually, Presentation Mode operation applies. This prevents the load from turning ON automatically after it was deliberately turned OFF. Pressing the button to turn lights ON returns the sensor to Auto ON mode. ** PW-100: Switch 9 is not used. PW-200: Switch 9 default is ON to comply with CA Energy Commission Title 24 bi-level switching requirements. SPECIFICATIONS Voltages: PW-100 & PW-200 .......................................120/277VAC, 50/60Hz Load Limits for each relay: @120VAC ...............................0-800W tungsten or ballast, 1/6 HP @277VAC .............................................................0-1200W ballast Load Type Compatibility: Incandescent, fluorescent, magnetic or electronic ballast Horsepower Rating (each relay) ........................1/6 HP @120VAC Time Delay Adjustment ..................................................5 to 30 minutes Walk-Through Mode ................3 minutes if no activity after 30 sec. Test Mode ...................... 5 sec. for 10 min. with DIP switch setting PIR Adjustment ................................................High or Low (DIP switch) Light Level Adjustment .......................................................8fc to 180+fc Alerts ...........................................................Selectable Audible & Visual US Patents: 5640113, 6617560 PW-100PW-2002 MODELRELAYDEFAULT ON MODEDIP SWITCHSETTING PW-1001MANUAL ON8ON PW-2001 2 AUTO ON MANUAL ON 8 9 OFF ON Gray shaded cells in the following tables indicate the default operation and switch settings. Presentation Mode This mode is a feature of the Auto ON mode. When both relays are manually turned OFF the PW holds the lights OFF until no motion has been detected for the duration of the Time Delay. With subsequent occupancy, the PW turns the load ON. If both relays are ON and one relay is manually turned OFF this relay remains OFF until both the Time Delay and re-trigger delay expires for the relay that is ON, after that time the ON Mode control settings again apply. Time Delays The PW sensor holds the load ON until no motion is detected for the selected time delay. Select the time delay using DIP switch settings. In the PW-200, both relays use the same delay. Test/20 min (DIP 1, 2, 3, OFF) A Test Mode with a short time delay of 5 seconds is set when DIP switches 1, 2, & 3 are OFF. It cancels automatically after ten minutes, or when you set a fixed time delay. When the Test Mode times out, the sensor assumes a 20 minute time delay. To restart Test Mode, change the time delay setting to any fixed amount and then return it to the Test setting. Fixed Time Delay (DIP 1 ON, 2 & 3 OFF) Time delays are 5, 10, 15, 20 (default), 25, or 30 minutes. Walk Through The Walk-Through mode shortens the time delay to reduce the amount of time the load is ON after a brief moment of occupancy, such as returning to an office to pick up a forgotten item then immediately exiting. Walk-Through Mode (DIP #4 ON) The PW sensor turns the load OFF three minutes after the area is initially occupied, if no motion is detected after the first 30 seconds. If motion continues beyond the first 30 seconds, the set time delay applies. No Walk-Through (DIP #4 OFF) Walk-Through mode disabled. PIR Sensitivity Adjustment The PW sensor constantly monitors the controlled environment and automatically adjusts the PIR to avoid common ambient conditions that can cause false detections, while providing maximum coverage. High (DIP #5 OFF) Default setting. Suitable for most applications. Low, 50% (DIP #5 ON) Reduces sensitivity by approximately 50%. Useful in cases where the PIR is detecting movement outside of the desired area (also consider masking the lens) and where heat sources cause unnecessary activation. Alerts The PW can provide audible and/or visible alerts as a warning before the load turns OFF. Visible Alert (DIP #6 ON) When only one minute is left in the time delay, the load connected to the relay turns OFF for one second. This provides a one minute warning before the load(s) are turned OFF by the sensor. No Visible Alerts (DIP #6 OFF) No visible warnings provided. Audible Alerts (DIP #7 ON) Unit will beep at one minute*, at 30 seconds and at 10 seconds before turning OFF load. When Walk- Through is active, the unit beeps three times at 10 seconds before the load goes OFF. *If Visible Alert is also ON, the one-minute time-out warning beep is replaced by the visible alert. No Audible Alerts (DIP #7 OFF) No audible warnings provided.3 COVERAGE PATTERNS Coverage testing has been performed according to the NEMA WD 7 guideline. For best performance, use in spaces not larger than 15’ x 12’. PIR Sensor The sensor has a two-tiered, multi-cell viewing Fresnel lens with 180 degree field of view. The red LED on the sensor flashes when the PIR detects motion. Masking the Lens Opaque adhesive tape is supplied so that sections of the PIR sensor’s view can be masked. This allows you to eliminate coverage in unwanted areas. Since masking removes bands of coverage, remember to take this into account when troubleshooting coverage problems. PIR Coverage 7.5’ (2.2m) 15’ (4.5m) 20’ (6.1m) 35’ (10.6m) Major motion Minor motion Top View 4’ (1.2m) 20’ (6.1m) 35’ (10.6m) 0 Side View INSTALLATION 1. \Make sure that the power has been turned OFF at the circuit breaker. 2. Connect wires to the PW flying leads as shown in the wiring diagram that is appropriate to the PW model and electrical supply. The 2 ground wires (green and green/yellow) must be fastened to ground for the sensor to work properly. 3. Attach the sensor to the wall box by inserting screws into the two wide holes on the top and bottom of the attached metal bracket. Match them up with the holes in the wall box and tighten. 4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF switch for each load and the lights will turn ON. There is a delay due to initial power-up of the sensor that only occurs during installation. 5. Test and adjust the sensor if necessary. 6. Install industry standard decorator. #12 – #14 AWG Cu Wire Only Strip Gage 1/2" 12.7mm WARNING: TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING. Load Red Line Black Neutral Ground Green Ground Green/Yellow PW-100 Wiring Blue Primary Load Secondary Load Neutral Red Brown Line 2 Line 1 Black Neutral Ground Ground Green/Yellow Green PW-200 Bi-Level Wiring Neutral Blue LineBlack Secondary Load Brown Primary Load Red Ground GroundGreen/Yellow Green PW-200 Dual Circuit Wiring4 ADJUSTMENTS Sensor Adjustment Remove the wall plate. Remove the button cap by firmly squeezing together the top sides of the button assembly. Gently pull it away from the unit. When the adjustments are completed, replace the button cap by inserting its hinges into the tabs on the main unit and then squeezing the top of the button while pressing it into the unit. Reinstall the cover plate. Light Level Adjustment The light level can be set with loads ON or OFF. To enable light level control and set the threshold: 1) Make sure the room is lit appropriately. 2) Put the sensor into TEST mode (see Time Delay switches). You have 5 minutes to complete the procedure. 3) Press and hold the ON/OFF button (Relay 1 button on the PW-200) for 3 seconds, until you hear a beep. 4) Step away from the sensor. After 25 seconds a beep sounds, indicating that the threshold level is set. This threshold is retained, even if power is lost, until it is re-set or disabled. In the PW-200, light level control only affects Relay 2. To disable light level control, press and hold the Relay 1 button for 7 seconds, until a double beep tone sounds. Reset to Default Use the DIP Switch Settings tables to return features to factory settings. To reset the PW, press and hold the Relay 1 button for 10 seconds, until a triple beep sounds. This resets the sensor and disables light level control (the brightest ambient light will not hold the light OFF). =ON =OFF 8 Auto On Manual On Relay 1 Mode 5 High Low, 50% PIR Sensitivity 7 Disabled Enabled Audible Alert 4 Disabled Enabled Walk-Through 912345678 Time Delay Walk-Through ON Relay 1 Mode Relay 2 Mode Audible Alerts PIR Sensitivity Visible Alerts Test/20 min 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes Service 5 minutes 123 Time Delay Service bypasses occupancy & light level functions. Control the load manually using ON/OFF button. 6 Disabled Enabled Visible Alert PW-200 ONLY 9 Auto On Manual On Relay 2 Mode 1 2 Factory Settings: All models PW-100 series PW-200 series 1 2 DIP SWITCH SETTINGS PW-200 shown. PW-100 has a single button. DELA Y PIR 50% WA LK A UD. ALER T RL Y 1 MA N RL Y 2 MA N VIS. ALER T ON/OFF Buttons Relay 1 Relay 2 DIP Switches PIR Lens Button Hinges Detection LED Tabs5 TROUBLESHOOTING Lights do not turn ON with motion (LED does flash). 1. Press and release each button to make sure that the correct lights come ON for each relay. If the lights do NOT turn ON, check wire connections, especially the Load connection. If the lights turn ON, verify that the correct On Mode is selected in DIP switches 8 and 9. 2. Check to see if light level control is enabled: cover the sensor lens with your hand. If the lights come ON, adjust the light level setting. 3. If lights still do not turn ON, call 800.879.8585 for technical support. Lights do not turn ON with motion (LED does not flash). 1. Press and release each button to make sure that the correct lights come ON for each relay. If the lights turn ON, verify that Sensitivity is on High. 2. Check the wire connections, particularly the Line connection. Verify that connections are tightly secured. 3. If lights still do not turn ON, call 800.879.8585 for technical support. Lights do not turn OFF. 1. There can be up to a 30 minute time delay after the last motion is detected. To verify proper operation, set DIP switch 1 to ON, then reset switches 1, 2, and 3 to OFF to start Test Mode. Move out of view of the sensor. The lights should turn OFF in approximately 5 seconds. 2. Verify that the sensor is mounted at least six feet (2 meters) away from any heating/ventilating/air conditioning device that may cause false detection. Verify that there is no significant heat source (for example, a high wattage light bulb) mounted near the sensor. 3. If the lights still do not turn OFF, call 800.879.8585 for technical support. Sensing motion outside desired areas. 1. Select PIR Sensitivity – Low (DIP switch 5 = ON) if necessary. 2. Mask the PIR sensor’s lens to eliminate unwanted coverage area. Red LED is lit all the time and the sensor features don’t work. 1. Check DIP switches 1,2,3. If they are all ON the unit is in Service Mode. Set the DIP switches to a valid Time Delay setting. 2. If re-setting the Time Delay switches does not clear the LED, call technical support. COVER PLATES Wattstopper PW series wall switches fit behind industry standard decorator-style switch cover plates. Cover plates are not included. Units come in the following colors, which are indicated by the final suffix of the catalog number (shown here in parentheses): White (-W), Light Almond (-LA), Ivory (-I), Grey (-G), Black (-B), Red (-R).6 INSTRUCTIONS EN FRANÇAIS CARACTÉRISTIQUES TECHNIQUES Courant électrique : PW-100 et PW-200 .................................120/277 V c.a., 50/60 Hz Limites de charge pour chaque relais : à 120 V c.a. .........................tungstène ou ballast 0-800 W, 1/6 HP à 277 V c.a. ..........................................................ballast 0-1200 W Type de charge compatible : Ballast incandescent, fluorescent, magnétique ou électronique Puissance nominale (chaque relais) ................1/6 HP à 120 V c.a. Réglage de la temporisation............................................5 à 30 minutes Mode passage ......3 minutes si aucune activité au bout de 30 sec. Mode test ........................ 5 sec. pour 10 min. avec le réglage des interrupteurs DIP Réglage de l’IRP .............................Élevée ou Faible (interrupteur DIP) Réglage du niveau de luminosité ..............................86,1 à 1936,8+ lux (8 à 180+ pied-bougies) Alarmes ......................................................Sonores et visuelle au choix Brevets américains : 5640113, 6617560 DESCRIPTION ET FONCTIONNEMENT DE L’UNITÉ Le détecteur interrupteur mural infrarouge passif PW utilise la technologie avancée de l’infrarouge passif (IRP). Le détecteur PW est capable d’activer une charge et de la maintenir ainsi aussi longtemps qu’il détecte une présence. Après une absence de détection de mouvements durant la temporisation sélectionnée, les lumières s’éteignent. Le mode « passage » permet d’éteindre les lumières au bout de 3 minutes seulement, si aucun mouvement n’est détecté 30 secondes après la détection d’une présence. Le PW-100 dispose d’un relais et d’un bouton MARCHE/ARRÊT. Le PW-200 contient deux relais et deux boutons MARCHE/ ARRÊT pour permettre une régulation indépendante d’une ou de deux charges. La pression sur un bouton fait basculer l’état du relais correspondant. Les détecteurs PW contiennent un détecteur du niveau de luminosité. Si la lumière naturelle est suffisamment forte, le détecteur maintient la charge COUPÉE jusqu’à ce que le niveau de luminosité baisse, même lorsqu’il y a une présence dans la zone. Dans le PW-200, le niveau de luminosité ne concerne que la charge du relais 2. Les utilisateurs peuvent contourner la fonction de maintien de l’état ARRÊT en appuyant sur le bouton MARCHE/ ARRÊT. Voir Réglage du niveau de luminosité. ACTIVATION de la ou des charges (mode MARCHE) Les relais sont programmés indépendamment soit sur MARCHE automatique, soit sur automatique, soit sur MARCHE manuelle. Dans ces deux modes, la charge peut être ACTIVÉE ou COUPÉE à l’aide du bouton MARCHE/ARRÊT. Marche manuelle DIP 8 sur MARCHE pour relais 1 DIP 9** sur MARCHE pour relais 2 Lorsque l’interrupteur DIP du mode MARCHE est en position MARCHE, l’occupant doit appuyer sur le bouton de MARCHE/ARRÊT pour ACTIVER charge. Le détecteur maintient la charge ACTIVE jusqu’à ce que plus aucun mouvement ne soit détecté pendant la temporisation sélectionnée. Il existe un délai de re-déclenchement de 30 secondes. Si une présence est détectée pendant ce délai, le détecteur ACTIVE de nouveau la charge. À la fin du délai de re-déclenchement, il est nécessaire d’appuyer sur le bouton MARCHE/ARRÊT pour ACTIVER la charge. Marche automatique DIP 8 sur ARRÊT pour relais 1 DIP 9** sur ARRÊT pour relais 2 Lorsqu’un interrupteur DIP du mode MARCHE est en position ARRÊT, la charge s’ACTIVE et se COUPE automatiquement en fonction de la présence. Si la charge est COUPÉE manuellement, le fonctionnement en mode présentation est activé. Cette opération empêche l’ACTIVATION automatique de la charge après une COUPURE volontaire. Si vous appuyez sur le bouton pour ALLUMER les lumières, le détecteur revient en mode MARCHE automatique. ** PW-100 : l’interrupteur 9 est inutilisé. PW-200 :le réglage par défaut de l’interrupteur 9 est sur MARCHE pour se conformer aux exigences en matière de commutation à deux niveaux du Titre 24 de la CA Energy Commission. N° de modèleRelaisMode MARCHE par défautN° interrupteur DIPRéglage PW-1001MARCHE manuelle8MARCHE PW-2001 2 MARCHE automatique MARCHE manuelle 8 9 ARRÊT MARCHE Gris cellules ombrée dans les tableaux suivants indique le fonctionnement et le réglage d’interrupteurs par défaut. Le mode présentation est une fonctionnalité du mode MARCHE automatique. Lorsque les deux relais sont manuellement COUPÉS, le PW maintient les lumières ÉTEINTES jusqu’à ce que plus aucun mouvement ne soit détecté pendant la temporisation. Si une présence est ensuite détectée, le PW ACTIVE la charge. Si les deux relais sont ACTIVÉS et qu’un relais est manuellement COUPÉ, ce relais reste COUPÉ jusqu’à la fin de la temporisation et du délai de re-déclenchement pour le relais qui est ACTIVÉ. Après cette période, les réglages de régulation du mode MARCHE s’appliquent de nouveau. Temporisations Le détecteur PW maintient la charge ACTIVE jusqu’à ce que plus aucun mouvement ne soit détecté pendant la temporisation sélectionnée. Sélectionnez la temporisation à l’aide des paramètres des interrupteurs DIP. Dans le PW-200, les deux relais utilisent la même temporisation.7 Test/20 min (DIP 1, 2, 3 sur ARRÊT) Le mode test, avec une temporisation courte de 5 secondes, est lancé lorsque les interrupteurs DIP 1, 2 et 3 sont sur ARRÊT. Il s’annule automatiquement au bout de dix minutes ou lorsque vous paramétrez une temporisation fixe. À la fin du mode test, le détecteur adopte une temporisation de 20 minutes. Pour redémarrer le mode test, modifiez le réglage de la temporisation en choisissant une quantité fixe, puis revenez au réglage du mode test. Temporisation fixe (DIP 1 sur MARCHE, 2 et 3 sur ARRÊT) Les temporisations sont de 5, 10, 15, 20 (par défaut), 25 ou 30 minutes. Mode passage Le mode passage raccourcit la temporisation pour réduire la durée d’ACTIVATION de la charge après une brève présence, telle que le retour au bureau pour récupérer un objet oublié suivi par une sortie immédiate. Mode passage (DIP 4 sur MARCHE) Le détecteur PW COUPE la charge trois minutes après la première détection de présence, si aucun mouvement n’est détecté au bout des 30 premières secondes. Si du mouvement est encore détecté au- delà des 30 premières secondes, la temporisation paramétrée est activée. Pas de mode passage (DIP 4 sur ARRÊT) Mode passage désactivé. Réglage de la sensibilité de l’IRP Le détecteur PW surveille en permanence l’environnement contrôlé et règle automatiquement l’IRP pour éviter des conditions ambiantes courantes susceptibles de provoquer de fausses détections, tout en fournissant une portée optimale. Élevée (DIP 5 sur ARRÊT) Réglage par défaut. Convient à la plupart des applications. Faible, 50 % (DIP 5 sur MARCHE) Réduit la sensibilité d’environ 50 %. Utile lorsque l’IRP détecte des mouvements en dehors de la zone souhaitée (pensez également à obstruer la lentille) et lorsque des sources de chaleur peuvent provoquer des activations inutiles. Alarmes Le PW est doté d’alarmes sonores et/ou visuelles qui avertissent de la COUPURE imminente de la charge. Alarme visuelle (DIP 6 sur MARCHE) Lorsqu’il ne reste qu’une minute de temporisation, la charge connectée au relais se COUPE pendant une seconde. Cette action constitue un avertissement une minute avant la COUPURE de la/des charge(s) par le détecteur. Aucune alarme visuelle (DIP 6 sur ARRÊT) Aucune alarme visuelle fournie. Alarmes sonores (DIP 7 sur MARCHE) L’unité émettra un bip une minute*, 30 secondes et 10 secondes avant la COUPURE de la charge. Lorsque le mode passage est activé, l’unité émet trois bips 10 secondes avant la COUPURE de la charge. *Si l’alarme visuelle est également ACTIVÉE, le bip d’avertissement une minute avant la fin du délai est remplacé par l’alarme visuelle. Aucune alarme sonore (DIP 7 sur ARRÊT) Aucune alarme sonore fournie.8 Vue du haut IRP Portée 7.5’ (2,2 m) 15’ (4,5 m) 20’ (6,1 m) 35’ (10,6 m) Mouvement important Mouvement faible Vue latérale 4’ (1,2 m) 20’ (6,1 m) 35’ (10,6 m) 0 INSTALLATION 1. Assurez-vous que le courant a bien été COUPÉ au niveau du disjoncteur du circuit. 2. Raccordez les fils aux câbles volants du PW comme illustré dans le schéma de câblage correspondant à votre modèle de PW et à votre alimentation électrique. Les 2 fils de terre (vert et vert/jaune) doivent être reliés à la terre pour que le détecteur fonctionne correctement. 3. Fixez le détecteur sur le boîtier mural en insérant des vis dans les deux grands orifices en haut et en bas du support métallique attaché. Placez-les en face des orifices du boîtier mural puis serrez. 4. ENCLENCHEZ le disjoncteur de circuit. Attendez une minute, puis appuyez sur l’interrupteur MARCHE/ARRÊT automatique de chaque charge et les lumières s’ALLUMERONT. La mise sous tension initiale du détecteur implique un certain délai qui n’apparaît que lors de l’installation. 5. Testez et réglez le détecteur si nécessaire. 6. Montez plaque d’interrupteur mural Decorator aux normes du secteur (non fourni). AVERTISSEMENT : COUPER LE COURANT AU DISJONCTEUR PRINCIPAL AVANT D’INSTALLER LE CÂBLAGE. AWG 12 –14 Câble cuivre uniquement Gabarit de dénudage 1/2" 12,7 mm Câblage des PW-100 Câblage à double circuit des PW-200 Câblage à deux niveaux des PW-200 Charge Rouge Ligne Noir Neutre Terre Vert Terre Vert/jaune Bleu Charge principale Charge secondaire Neutre Rouge Marron Ligne 2 Ligne 1 Noir Neutre Terre Terre Vert/jaune Vert Neutre Bleu LigneNoir Charge secondaire Marron Charge principale Rouge Terre TerreVert/jaune Vert PORTÉES Le test de portée a été réalisé conformément à la norme NEMA WD 7. Pour des performances optimales, n’utilisez pas le détecteur dans des espaces plus grands que 4,5 m x 3,6 m (15 pi x 12 pi). Détecteur IRP Le détecteur dispose d’une lentille Fresnel de visualisation à multiples cellules et deux niveaux avec un champ de vision à 180 degrés. La DEL rouge du détecteur clignote lorsque l’IRP détecte un mouvement. Obstruction de la lentille Du ruban adhésif opaque est fourni de manière à permettre l’obstruction de parties du champ de vision du détecteur IRP. Cette opération vous permet d’éliminer la portée dans des zones non souhaitées. Étant donné que cette obstruction diminue la portée, n’oubliez pas d’en tenir compte en cas de dépannage des problèmes de portée.9 RÉGLAGES Réglage du détecteur Retirez la plaque murale. Retirez le cache du bouton en serrant fermement et simultanément les parties supérieures de l’ensemble bouton. Sortez-le doucement de l’unité. Lorsque les réglages sont terminés, reposez le cache du bouton en insérant ses charnières dans les ergots de l’unité principale, puis serrez les parties supérieures du bouton tout en le poussant dans l’unité. Reposez la plaque murale. Réglage du niveau de luminosité Le niveau de luminosité peut être réglé avec les charges ACTIVÉES ou COUPÉES. Pour activer le contrôle du niveau de luminosité et régler le seuil : 1) Assurez-vous que la pièce est correctement éclairée. 2) Mettez le détecteur en mode test (avec les interrupteurs de temporisation). Vous avez 5 minutes pour accomplir la procédure. 3) Maintenez enfoncé le bouton MARCHE/ARRÊT (bouton du relais 1 sur le PW-200) pendant 3 secondes, jusqu’à l’émission d’un bip sonore. 4) Éloignez-vous du détecteur. Au bout de 25 secondes, un bip se fait entendre, indiquant que le niveau de seuil est réglé. Ce seuil est enregistré, même lors de coupures d’alimentation, jusqu’à ce qu’il soit à nouveau réglé ou désactivé. Dans le PW-200, le contrôle du niveau de luminosité ne concerne que le relais 2. Pour désactiver le contrôle du niveau de luminosité, maintenez enfoncé le bouton du relais 1 pendant 7 secondes, jusqu’à l’émission d’un double bip sonore. Rétablir les paramètres par défaut Utilisez les tableaux des réglages des interrupteurs DIP de la page précédente pour revenir aux réglages d’usine. Pour réinitialiser le PW, maintenez enfoncé le bouton du relais 1 pendant 10 secondes, jusqu’à l’émission d’un triple bip sonore. Cette opération réinitialise le détecteur et désactive le contrôle du niveau de luminosité (la luminosité ambiante la plus intense ne maintiendra pas les lumières ÉTEINTES). DELA Y PIR 50% WA LK A UD. ALER T RL Y 1 MA N RL Y 2 MA N VIS. ALER T Boutons MARCHE/ARRÊT Relais 1 Relais 2 Interrupteurs DIP DEL de détection Lentille IRP Ergots Charnières de bouton Illustration du PW-200. Le PW-100 dispose d’un seul bouton.Next >