VTR8300 Series Installation Guide Room Controller with Optional PIR sensor Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Location 2 Installation 2 Terminal, Identification and Function 3 Communication wiring to VC3xxxE Relay Pack 3 BACnet ® Communication Wiring (if applicable) 3 Network wiring topology 3 How to Enter Setup Screen 4 Setup Screen Display 4 Specifications 5 Drawing and Dimensions 6VTR8300 Series 2 Installation Guide Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0414-02 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconics Technologies Inc. All rights reserved. DISCLAIMERS • The VTR8300 series Room Controller is only to be used in conjunction with the VC3000 line voltage switching relay pack. Together they are used as operating controls for high voltage fan coil units. • If replacing an existing Line Voltage FCU Controller, label the wires before removal of the Room Controller. • Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing the Room Controller. A short circuit or wrong wiring may permanently damage the Room Controller or equipment. • All VTR8300 series Room Controllers are designed for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user/installer/electrical system designer to incorporate safety devices such as relays, flow switches, thermal protections, and/or an alarm system to protect the entire system against any catastrophic failures. Tampering with the devices or unintended application of the devices results in a void of warranty. • If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. • These devices are not serviceable and must be returned to the supplier for any repair. • A switch or circuit breaker must be installed. It must be suitably located, easily reached, and marked as the disconnecting device • Never apply more than 9VDC to Room Controller. • This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. VTR8300 Room ControllerVC3000 Relay Pack IMPORTANT SYMBOLS Products marked with this symbol state that the manuals must be consulted in all cases to any hazards. This product has been tested to the requirements of CAN/CAS-C22.2 No. 61010-1, second edition, including Amendment 1, or a later version of the same standard incorporating the same level of testing requirements. Alternating Current Direct Current Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION VTR8300 Series3Installation Guide Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0414-02 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconics Technologies Inc. All rights reserved. INSTALLATION Location • Do not install on outside wall. • Do not install in areas with direct heat source. • Do no install near any air discharge grill. • Do not install in areas exposed to direct sunlight. • Ensure Room Controller has sufficient air circulation. • Ensure wall surface is flat and clean. Installation 1. Open unit by pulling on bottom side of Room Controller (Figure 1). 2. Read FCC ID and IC label installed in cover before installing any wireless product. 3. Ensure correct side of base faces up. 4. Pull cables 6in (15cm) out from wall. 5. Align base and mark location of two mounting holes on wall (Figure 2). 6. Install anchors in wall. 7. Insert cable in central hole of base. 8. Insert screws in mounting holes on each side of base. 9. Strip each wire 1/4in ( 0.6cm) from end. 10. Insert each wire according to wiring chart (next page). 11. Gently push excess wiring back into hole. 12. Gently align cover to top of base and snap in place from bottom (Figure 3). 13. Install security screw. • IfreplacinganexistingLineVoltageFCUController,labelthe wires before removal of the controller. • Electroniccontrolsarestaticsensitivedevices.Discharge yourself properly before manipulating and installing the Room Controller. • Ashortcircuitorwrongwiringmaypermanentlydamagethe Room Controller or the equipment. • AllVTR8300seriesRoomControllersaredesignedforuseas operating controls only and are not safety devices. Tampering with the devices or unintended application of the devices will result in a void of warranty. This transmitter must be installed to provide a separation distance of at least 4in (10cm) from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter. Figure-1 Open the cover Figure-2 Install the base Figure-3 Reinstall coverVTR8300 Series 4 Installation Guide Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0414-02 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconics Technologies Inc. All rights reserved. To other VC3xxxE Relay Pack Terminal ControllerRelay Pack VTR83xxA VC3504E 4 - Tx / Rx 5 - 7 Vdc Power Hot 6 - Power Common 1 - Tx / Rx 2 - 7 Vdc Power Hot 3 - Power Common Relay Pack VC3300E 1 - Tx / Rx 2 - 7 Vdc Power Hot 3 - Power Common Terminal ControllerTerminal Controller To others To others 13 - COM + 14 - COM - VTR83xxAVTR83xxA 13 - COM + 14 - COM - Terminal Identification All VTR83xxA Terminal Equipment Controller Terminal 4Tx – Rx Communication Terminal 5Power Hot 7.0 VDC Terminal 6Power Common Terminal 13BACnet + Terminal 14BACnet - Terminal 15BACnet REF Terminal 16BI 1 ( Configurable ) Terminal 17BI 2 ( Configurable ) Terminal 18Scom TERMINAL, IDENTIFICATION AND FUNCTION Only ONE VC3xxxE Relay Pack with remote monitoring inputs can be used under a single VTR83xxA Controller. All other slave units must be VC3xxxE Relay Pack(s) WITHOUT remote inputs. A maximum of 10 VC3xxxE Relay Packs can be used for a single VTR83xxA Room Controller. From VTR83xxA to first VC3xxxE Relay Pack • Usesexistingornewfieldwires • Aminimumof3wiresarerequired14-22Ga, Solid or Stranded, shield not necessary From first VC3xxxE to all other slave VC3xxxE Relay Pack(s) •Usesexistingornewfieldwires •Aminimumof2wiresarerequired14-22Ga,Solid or Stranded •Shieldnotnecessary •Connectonlytwowires:Tx/Rx(1)andPower Common (3). Daisy Chained TopologyStar Topology Mixed Daisy Chained & Star Topology COMMUNICATION WIRING TO VC3XXXE RELAY PACK Network Wiring Topology BACnet ® Communication Shielded Wiring (if required) NOTE: See VTR8300 BACnet ® integration manual for more details NOTE: never use any terminal not mentioned in above table.VTR8300 Series5Installation Guide Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0414-02 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconics Technologies Inc. All rights reserved. HOME SCREEN DISPLAY Note: User HMI is configurable and allows display functions such as Date, Time, Humidity, Outdoor Temperature, Setpoint, and others to be enabled or disabled by setting various parameters. Time System Status Fan Status Up Arrow Increase Temperature Setpoint Actual Setpoint Down Arrow Decrease Temperature Setpoint Help Language Selection Temperature Units Fan Mode Date Occupancy Status Indoor Temperature Indoor Humidity Outdoor Temperature System Mode Short Network Message Hospitality User Interface ShownVTR8300 Series 6 Installation Guide Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150 028-0414-02 www.viconics.com | sales@viconics.com April 2015 © 2015 Viconics Technologies Inc. All rights reserved. HOW TO ENTER SETUP SCREEN SETUP SCREEN DISPLAY Return to home screen General Note: 1/2 Setup Network Configuration Setpoints - Display Setpoints view Test outputs Language Selection Adjustable parameter Non-adjustable parameter Touch and hold this point for 3 seconds to enter setup mode Note: If a configuration / installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt will appear to prevent access to the device configuration components. Discover Mode The Controller will become discoverable on the wireless ZigBee® network for 1 minute (this button is hidden if ZigBee® settings are not configured) Enter BACnet ® & ZigBee ® network settings Enter parameter configuration menu Enter setpoint & display settings Enter output testing mode Enter status and service view Enter setpoint & display settings Enter language selection settingsNext >