Installation Guide Temperature Z205464-0F Page 1 of 2 ©2013 Veris Industries 09134 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners. TM NOTICE • This product is not intended for life or safety applications. • Do not install this product in hazardous or classified locations. • Read and understand the instructions before installing this product. • Turn off all power supplying equipment before working on it. • The installer is responsible for conformance to all applicable codes. No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material. Product Identification Product Overview The TB Series temperature sensor is designed to strap onto a pipe. The copper sensing plate provides a secondary measurement of the temperature inside the pipe. The TRA Series temperature sensor is designed for remote sensing applications. Both devices have output options compatible with building control systems and both are warranted to meet accuracy specifications for a period of five years. TB/TRA Series Speciality Temperature Sensors TB TRA Bracket Diameter Sensor Type TB A = 2 ½" (6.4 cm) max. D = 8" (20 cm) max. E = 12” (31 cm) max. B = 100R platinum, RTD C = 1k platinum, RTD D = 10k T2, Thermistor E = 2.2k, Thermistor F = 3k, Thermistor G = 10k CPC, Thermistor H = 10k T3, Thermistor I = 1k Balco (Nickel-iron) RTD J = 10k Dale, Thermistor K = 10k w/11k shunt, Thermistor Cal Certificate TRA 0 = None 1 = 1 point Cal validation 2 = 2 point Cal validation Sensor Type B = 100R platinum, RTD C = 1k platinum, RTD D = 10k T2, Thermistor E = 2.2k, Thermistor F = 3k, Thermistor G = 10k CPC, Thermistor H = 10k T3, Thermistor I = 1k Balco (Nickel-iron) RTD J = 10k Dale, Thermistor K = 10k w/11k shunt, Thermistor Cal Certificate 0 = None 1 = 1 point Cal validation 2 = 2 point Cal validation Cable Length None = 3 ft (0.9 m) A = 6 ft (1.8 m)* B = 10 ft (3.1 m)* C = 20 ft (6.1 m)** D = 25 ft (7.6 m)** E = 50 ft (15 m)** F = 100 ft (30 m)** * Not available for sensor types B, C, & I. ** Not available for sensor types B, C, E, F, I, & N. M = 20k NTC, Thermistor N = 1800 ohm, Thermistor R = 10k US, Thermistor S = 10k 3A 221, Thermistor T = 100k, Thermistor U = 20k “D”, Thermistor W = 10k T2 high accuracy, Thermistor Y = 10k T3 high accuracy, Thermistor Z = 10k E1, Thermistor CC = 15k, Thermistor M = 20k NTC, Thermistor N = 1800 ohm, Thermistor R = 10k US, Thermistor S = 10k 3A 221, Thermistor T = 100k, Thermistor U = 20k “D”, Thermistor W = 10k T2 high accuracy, Thermistor Y = 10k T3 high accuracy, Thermistor Z = 10k E1, Thermistor CC = 15k, Thermistor Specifications Wiring22 AWG; 2-wire RTD/ThermistorZ205464-0F Page 2 of 2 ©2013 Veris Industries 09134 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners. Installation Guide Temperature TB/TRA Series TM 2.9" (74 mm) 4" (102 mm) strap fits pipe diameters up to 12” 2" (51 mm) 0.3" (6 mm) TRA ModelTB ModelDimensions Installation TB: 1. Clamp the sensor around the pipe to be monitored. Make sure the copper sensing plate is in contact with the pipe surface. 2. Wire the sensor to the controller as shown. Red Black Thermistor RTD Thermistor RTD Orange Orange TRA: 1. Set the stainless steel sensing probe in contact with the area to be monitored. No mounting necessary. 2. Wire the sensor to the controller as shown.Next >