Z204201-0J Page 1 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0819 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners. NOTICE • This product is not intended for life or safety applications. • Do not install this product in hazardous or classied locations. • Read and understand the instructions before installing this product. • Turn o all power supplying equipment before working on it. • The installer is responsible for conformance to all applicable codes. If this product is used in a manner not specied by the manufacturer, the protection provided by the product may be impaired. No responsibility is assumed by the manufacturer for any consequences arising out of the use of this material. Installation Guide Pressure TM Product Identification Specifications Product Overview The PW2 Series sensor is designed to accept high differential pressure. Install the sensor on a duct or pipe across a pump, filter, heat exchanger, compressor, or other non-corrosive wet media. The dual sensor design eliminates the need for a bypass valve, and the bi-directional capability reduces installation errors. A pushbutton allows easy zero adjustment. PW2 Series Wet Media Differential Pressure Transducer Local Display L = LCD Display X = No Display NIST N = NIST X = None Options S = Standard BP = With mounted bypass assembly Operational Range* 03 = 0 to 50 psig 04 = 0 to 100 psig 05 = 0 to 250 psig PW2 * IMPORTANT! Select operational range according to maximum gauge pressure, NOT differential pressure. Example: High gauge pressure=90 psig, select 100 psig model (04). Media Compatibility17-4 PH stainless steel Input PowerClass 2; 12 to 24 Vdc, loop powered (polarity insensitive) Output 2-wire transmitter; 4 to 20 mA (clipped and capped) Proof Pressure2x max. F.S. range Burst Pressure5x max. F.S. range Accuracy at 25 °C*Ranges A, B, C: ±1% F.S.** Range D: ±2% F.S.** Surge DampingElectronic; 5-second averaging Temperature Compensated Range 0 to 50 °C (32 to 122 °F); TC Zero <1.5% of product F.S. per sensor TC Span <1.5% of product F.S. per sensor Sensor Operating Range -20 to 85 °C (-4 to 185 °F) Long Term Stability±0.25% per year Zero AdjustPushbutton auto-zero Operating Environment-10 to 55 °C (14 to 131 °F); 10 to 90% RH non-condensing Fittings 1/8” NPT female thread, stainless steel 17-4 PH PhysicalWhite powder-coated aluminum PRESSURE RANGES 0 to 50 psi (0 to 3.45 bar)5/10/25/50 psid (0 to 0.34/0.69/1.72/3.45 bar) 0 to 100 psi (0 to 6.89 bar)10/20/50/100 psid (0 to 0.69/1.38/3.45/6.89 bar) 0 to 250 (0 to 17.24 bar)25/50/125/250 psid (0 to 1.72/3.45/8.62/17.24 bar) Note: To conform to EMC standards, use shielded cabling. Technical information is available from the factory on request. * Accuracy combines linearity, hysteresis, and repeatability. ** F.S. is defined as full span of selected range in bidirectional mode. PW2xxxS PW2xxxBPZ204201-0J Page 2 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0819 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners. TM PW2 Series Installation Guide 2.2" (57 mm) 4" (102 mm) 5.8" (147 mm) LOW HIGH WET DIFFERENTIAL PRESSURE Dimensions 6.75” (172 mm) 8.7” (221 mm) 8.7” (221 mm) 7.75” (191 mm) 1.8” (46 mm) 3.5” (89 mm) 3.5” (89 mm) 0.4” (11 mm) 1.0” (25 mm) 12.0” (305 mm) 0.5” (13 mm) 1.5” (38 mm) 0.3” (8 mm) PW2xxxS PW2xxxBPZ204201-0J Page 3 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0819 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners. TM PW2 Series Installation Guide Operation JumperNotes Port Swap/NormReverses polarity of the pressure ports (i.e. makes the LO port operate as the HI port and vice versa); used when the sensor is incorrectly plumbed. Bi-Dr/NormalNormal: 0 to F.S. pressure Bidirectional: -F.S. pressure to +F.S. pressure; output reads 1/2 when pressure is zero. Slow Avg/Fast NormSlow mode provides 5-second averaging for surge damping. Analog Rev/NormNormal: Output increases as pressure increases; Reverse: Output is maximum when pressure differential is zero and decreases as pressure increases. Bar/PSISelect output units. Auto-Zero: Press and hold the Zero button for two seconds or provide contact closure on the auxiliary ‘Remote Zero’ terminal to reset the output to zero pressure. To protect the device from accidental zeroing, this feature is only enabled when the detected pressure is within 5% of factory calibration. Installation Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty. 1. Mount sensor on a duct or pipe, across the pump, filter, or other pressure differential. 2. Wire as shown below. DIGITAL CONTROL Digital Output 4-20mA IN POWER SOURCE 12 to 24 VDC Port Swap/Norm Bi-Dr/Normal Slow Avg/Fast Norm Analog Rev/Norm Bar/PSI ZERO A-High B-Mid High C-Mid Low D-Low REMOTE ZERO 4-20mA Pressure Range Settings Polarity Insensitive Default Settings in bold. Insert jumper to activate other features. Model PW2-03 PW2-04 PW2-05 A 50 100 250 B 25 50 125 C 10 20 50 D 5 10 25 Model PW2-03 PW2-04 PW2-05 A 3.45 6.89 17.24 B 1.72 3.45 8.62 C 0.69 1.38 3.45 D 0.34 0.69 1.72 Range (PSI) Range (bar) HI PORT 100 psi 100 psi 50 psi 50 psi 0 psi LO PORT 0 psi 50 psi 50 psi 100 psi 100 psi 4-20mA +100 psi +50 psi 0 psi -50 psi -100 psi Bidirectional Operation Input ConditionsResultOutputs Read DP 20mA 16mA 12mA 8mA 4mA Output is mA only. Example: PW2-04 Optional: Connect Zero terminals to digital output (contact closure) of control system. Caution: Zero input is for dry-contact only. Do not apply voltage to the Zero terminals. Range: Use the Range switch to select F.S. differential pressure. Note: Use of a housing grounding screw is required for CE applications 3. Configure the jumpers as described below.Z204201-0J Page 4 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 0819 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Other companies’ trademarks are hereby acknowledged to belong to their respective owners. TM PW2 Series Installation Guide Commissioning (PW2xxxBP only) 1. Close C and D. 2. Open B (null). 3. Open D (bleed or purge). 4. Slowly open A to bleed air from line. 5. Close B, then fully open A. 6. Slowly open C to bleed air from line. 7. Close D, then fully open C. 1. Bleed or purge: see Commissioning step. 2. Equalize pressure: open B. 3. Isolate sensors: close A and C. Maintenance (PW2xxxBP only) B A C D B A C D B A CD Valve positions: All closed Valve positions: All open Valve positions: Normal operationNext >