Input Power24 Vac@600 mA max., 50/60 Hz INPUTS Water Leak Detection CableRequires 15 ft. (4.5 m) leader cable kit (LC-KIT or LC-KIT-M) Maximum LengthLD1500: 1500 ft. (457 m); LD2100: 2000 ft. (609 m) Detection Accuracy±2 ft (0.6 m) + 0.5% of the cable length Detection Repeatability±2 ft (0.6 m) + 0.25% of the cable length Detection Response Time5 to 995 sec ± 2 sec, configure in 5 steps OUTPUTS Relay (LD2100 only) 1 A@24 Vdc, 0.5 A resistive@120 Vac COMMUNICATIONS PORTS RS-2329600 baud, No parity, 8 data bits, 1 stop bit RS-4851200, 2400, 9600, or 19200 baud (selectable); No parity, 8 data bits, 1 stop bit PROTOCOLS Terminal Emulation: RS-232VT100 compatible Modbus RS-485 Slave; RTU Mode; Supports function codes 03, 04, 06, and 16; Johnson N2 (LD2100 only) EXPANDED PROTOCOLS TCP/IP, HTML, TFTPIPv4.0 SNMPV1: V2C MIB-2 compliant; NMS Manageable with Get, Set, Traps SMTP email, LD2100 only Supports client authentication (plain and login); compatible with ESMTP servers Modbus TCP/IPModbus slave; TCP/IP transmission protocol BACnet/IPASHRAE Std 135-2004 Annex J ALARM NOTIFICATION Audible Alarm: LD2100 70 dBA@2 ft. (0.6 m); re-sound configurable (disabled, 0 to 24 hours, integer values only) *The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details. Visual Alarm: LD1500 LD2100 Red, 4-digit; 7 segment LED display; bi-color status LED Bi-color status LED Email LD1500/LD2100 4 email recipients; email sent on Alarm and Return to Normal SNMP Traps LD1500, LD21004 community strings LOGGING CAPABILITIES Event Log LD1500 LD2100 Last 10 events Last 500 events Trend Log LD2100 Cable current level every day, for the last 288 days LOGIN SECURITY Display Access1 Administrator (password for configuration, no password required to view panel status) FRONT PANEL INTERFACE Display LD2100Green alphanumeric dot matrix Push Buttons LD2100 Test/Reset LED Indicator LD1500 LD2100 1 tri-color Power/Status (green = power on; red = alarm; yellow = cable fault 1 bi-color Power/Status (green=power on, red=alarm) OPERATING ENVIRONMENT Temperature0 to 50 °C (32 to 122 °F) Humidity5 to 95% RH non-condensing Altitude15000 ft. (4572 m) max. MountingVertical wall mount (DIN rail mounting option available on LD2100 only) WARRANTY Limited Warranty2 years AGENCY APPROVALS Agency ApprovalsCE*; ETL listed: conforms to UL 61010-1, EN 61010-1; CSA C22.2; RoHS compliant Together with the SC or SC-C sensing cable, the LD1500 and LD2100 panels detect and report the presence and location of the cable-specific fluid. When the fluid comes in contact with the patented cable, the monitoring panel quickly pinpoints the location of the leak, triggering an alarm and displaying the location. SPECIFICATIONS LD1500 LD2100 I N T E RT E K CUS L ISTE D CM LISTED 3037024 * High detection accuracy Adjustable leak and contamination alarm thresholds reduce false alarms due to high humidity… high detection accuracy PC configuration Summary alarm relay output… fast response 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM LD1500 & LD2100 Helps Eliminate High Humidity False Alarms Leak Detection | Distance Read Panel HQ0001796.F 01177.0” (176 mm) 3.7” (94 mm) 8.0” (203 mm) 4.25” (108 mm) W B GR Cable Leader Cable (LC-KIT) (included with LD1500 and LD2100) Sensing Cable (SC) End Terminator (EOL) (included with LC-KIT) Power supply (PS24-15W ) W B GR Cable Leader Cable (LC-KIT-M) (not included with LD1500 and LD2100) End Terminator (EOL) (included with LC-KIT-M) Power supply (PS24-15W ) Sensing Cable (SC-C) MODELMANUF. PART #DESCRIPTION U006-0038*LD1500*Leak Panel, 1500’ Distance Read, Modbus, BACnet, SNMP, SMTP, and relay outputs U006-0047*LD2100*Leak Panel, 2000’ Distance Read, Modbus, BACnet, SNMP, SMTP, and relay outputs U006-0035**LC-KIT**Leader cable kit for SC cables (connects from leak panel to SC or NSC cable) U006-0061***LC-KIT-M***Leader cable kit for SC-C cables (connects from leak panel to SC-C cable) U006-0004FM1114Reference map, framed (11” x 14”) * Power supply not included. Use LD-ENC (U006-0045) wall mount enclosure with built-in power supply or Veris PS24-15W power supply or equivalent. ** Included with LD1500 and LD2100. *** Not included with LD1500 or LD2100. Required for installation of SC-C cables. LD1500/LD2100 BASIC SC INSTALLATION Wiring Diagram LD1500 Dimensional Drawing LD1500/LD2100 BASIC SC-C INSTALLATION Wiring Diagram LD2100 Dimensional Drawing ORDERING INFORMATION 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM Leak Detection | LD1500 & LD2100 HQ0001796.F 0117Next >