LC-KIT Plenum Rating: SC NSC CL2P/CMP C(UL) CL3P/CMP C(UL) California State Fire Marshall approved Shear Strength: SC/NSC SC-C >180 lbs (>81.65 kg) 160 lb (72.6 kg) Cut Through Resistance: SC/NSC SC-C >40 lbs (>18.2 kg) w/0.005” (0.13 mm) blade >50 lbs (>27.7 kg) w/0.005” (0.13 mm) blade Abrasion Resistance: SC/NSC SC-C 60 cycles per UL 719 >65 cycles per UL719 Connector: SC/NSC SC-C 4 pin, 1” (25.4 mm) dia., circular, locking, 4 pin, 0.5” (13 mm) diameter Input Power5 Vdc ±10% Storage Environment-20 to 70 °C (-4 to 158 °F) Weight3 oz. (85 g) INPUTS Water Leak Detection Cable Requires 15 ft. (4.5 m) leader cable (kit included) Maximum Cable Length300 ft. (91 m) Detection Response Time <20 sec (10 sec typical) Relay Output2 Form C relays (leak and fault); 1 A@24 Vdc, 0.5 A resistive@120 Vac OPERATING ENVIRONMENT Temperature0 to 50 °C (32 to 122 °F) Humidity5 to 95% RH non-condensing Altitude15,000 ft. (4,572 m) max *Prolonged exposure to concentrated ketones may cause temporary reduction of sensitivity; call for details. Single zone leak detection controller kits are pre-configured in popular lengths for monitoring single areas or rooms. Kits come with everything needed for a complete system, including an LD310 single zone control panel, a leader cable kit with end-of-line terminator, sensing cable, and a WA-DC-05 power supply. LD310 control panels continuously monitor up to 300 ft. of leak detection cable. If the cable detects compatible fluid at any point along its length, the detection panel LED illuminates and an alarm signals the presence of a leak. Additionally, if the cable loses continuity, the panel will activate a cable fault LED pattern. SPECIFICATIONS Cables SPECIFICATIONS LD310 Controller OPERATING ENVIRONMENT Temperature: SC/NSC SC-C 0 to 75 °C (32 to 167 °F) 90 °C (194 °F) max. Humidity: SC/NSC: 5 to 95% RH non-condensing Altitude: SC/NSC: 15,000 ft. (4,572 m) max. Storage Environment: SC NSC -30 to 85 °C (-22 to 185 °F) 0 to 75 °C (32 to 167 °F) Chemical Resistance: SC-C* In accordance with ASTM D543, cable functions normally after seven days exposure to the following: fresh deionized water, tap water, sulfuric acid (98%), sulfuric acid (50%), hydro- chloric acid (37%), sodium hydroxide (10%), aqua regia, ethylene glycol (60% in DI water) Agency Approvals: LD300 SC NSC CE; RoHS compliant CE; UL; RoHS compliant UL E118871; UL 13, power limited circuit cable; UL 444, communication cables; NFPA 262; plenum flame test (UL 910); NEC Articles 725 and 800; RoHS compliant WARRANTY Limited Warranty2 years AGENCY APPROVALS APPLICATIONS • Monitoring data centers, computer room under-floor areas, mechanical rooms, and electrical control centers • Protecting records storage rooms • Monitoring plumbing in facilities • Monitoring chilled beams • Monitoring chemical and fuel storage areas Application flexibility Monitor up to 3’*, 10’, 17’, 25’, 50’, or 100’ of leak detection cable Pushbutton Pushbutton switch allows users to silence the audible alarm and to test and reset the system LED indicator Bi-color LED indicator for alarm status and cable fault...easy indication of leaks or equipment problems Max accuracy Sensitivity settings for each zone help reduce false alarms... maximum detection accuracy Audible alert Selectable on/off audible alert Fast response Summary alarm relay output 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com LC-KIT & LC-KIT-M Single Zone Leak Detection Controller Kits Leak Detection | Leak Detection Kits HQ0001800.G 0720SINGLE ZONE KIT WITH SC-C SENSING CABLE Wiring Diagram W B GR 15 foot Leader Cable (included with LC-KIT) SC Sensing Cable (10, 17, 25, 50, or 100) End Terminator (EOL) (included with LC-KIT) Power supply (WA-DC-05 ) LD310 W B GR 15 foot Leader Cable (included with LC-KIT-M) SC-C Sensing Cable (3, 10, 17, 25, 50, or 100) End Terminator (EOL) (included with LC-KIT-M) Power supply (WA-DC-05 ) LD310 LED INDICATIONDEVICE STATUS Solid green (on or off)Normal operation Flashing green (0.5 sec on/2.5 sec off)Cable fault Flashing green (0.5 sec on/0.5 sec off)Leak detected Cables, EOL, and power supply only. MODELDESCRIPTIONKIT INCLUDES THESE MANUF. PART #S U006-0062Kit, LeakDet, LD310, 10’ Conductive FluidLD310, LC-Kit, SC-10 & WA-DC-05 U006-0063Kit, LeakDet, LD310, 17’ Conductive FluidLD310, LC-Kit, SC-17 & WA-DC-05 U006-0064Kit, LeakDet, LD310, 25’ Conductive FluidLD310, LC-Kit, SC-25 & WA-DC-05 U006-0065Kit, LeakDet, LD310, 50’ Conductive FluidLD310, LC-Kit, SC-50 & WA-DC-05 U006-0066Kit, LeakDet, LD310, 100’ Conductive FluidLD310, LC-Kit, SC-100 & WA-DC-05 U006-0067Kit, LeakDet, LD310, 3’ ChemicalLD310, LC-Kit-M, SC-C-3 & WA-DC-05 U006-0068Kit, LeakDet, LD310, 10’ ChemicalLD310, LC-Kit-M, SC-C-10 & WA-DC-05 U006-0069Kit, LeakDet, LD310, 17’ ChemicalLD310, LC-Kit-M, SC-C-17 & WA-DC-05 U006-0070Kit, LeakDet, LD310, 25’ ChemicalLD310, LC-Kit-M, SC-C-25 & WA-DC-05 U006-0071Kit, LeakDet, LD310, 50’ ChemicalLD310, LC-Kit-M, SC-C-50 & WA-DC-05 U006-0072Kit, LeakDet, LD310, 100’ ChemicalLD310, LC-Kit-M, SC-C-100 & WA-DC-05 www.veris.com | Leak Detection | LC-KIT & LC-KIT-M SINGLE ZONE KIT WITH SC SENSING CABLE Wiring Diagram BLINK CODE KEY ORDERING INFORMATION 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com Leak Detection | LC-KIT & LC-KIT-M HQ0001800.G 0720Next >