H709 H909 H609 H809 1. The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details. Note: Do not use the LED status indicators as evidence of applied voltage. If using this switch in an application that includes an electronically commutated motor (ECM), see Veris Application Note VN61, at www.veris.com. SPECIFICATIONS Sensor PowerInduced from monitored conductor Insulation Class600 Vac RMS (UL), 300 Vac RMS (CE 1 ) Frequency Range50/60 Hz Temperature Range-15 to 60 °C (5 to 140 °F) Humidity Range10 to 90% RH non-condensing Hysteresis10% (typical) Terminal Block Wire Size24 to 14 AWG (0.2 to 2.1 mm 2 ) Terminal Block Torque3.5 to 4.4 in-lbs (0.4 to 0.5 N-m) WARRANTY Limited Warranty5 years AGENCY APPROVALS Agency ApprovalsUL 508 open device listing; CE: EN61010-1, CAT III, Pollution Degree 2, basic insulation E150462 DETECTS BELT LOSS/COUPLING SHEAR! DETECTS BELT LOSS/COUPLING SHEAR! Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That’s why our sensors are the industry standard for status. Calibrated Trip Point OO Fan/pump On Loss of Belt/Coupling Shear Electrical Failure Hawkeye x09 Series are high performance current switches, ideal for line voltage loads. The devices are powered by the current being monitored. They are ideal for monitoring performance on unit vents, exhaust fans, recirculation pumps, and other fixed loads. APPLICATIONS • Detecting belt loss, coupling shear, mechanical failure, and interlocking loads • Verifying lighting circuit and other electrical service run times • Monitoring status of industrial process equipment • Monitoring status of critical motors (compressor, fuel, etc.) • VFD output On/Off status • Fan/pump status monitoring Maximize Reliability Minimize Installed Cost Low setpoint The H809 has a low (0.75 A) minimum setpoint…no need for multiple wraps of the conductor through the sensor, even on loads as small as 1/5 HP Adjustable trip point Precise current trip point setting Small in size H609 and H809 are small in size to fit easily inside small starter enclosures Status LEDs For easy setup and local indication Versatility Removable mounting bracket optimizes field versatility Flexibility Bracket on H909 can be installed in three different configurations 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM HX09 SERIES Detect Belt Loss, Coupling Shear, and Mechanical Failure Current Monitoring | Adjustable Trip Point, High Voltage Output HQ0001755.G 0117MODEL AMPERAGE RANGE @ 50/60 HZ ONLY STATUS OUTPUT (MAX.) MIN. TRIP POINT STATUS LED HOUSINGULCE LEAD FREE H6091.25 to 50 AN.O. 0.2 A @ 120 Vac/dc1.25 A or less•Split-core • 1 • H7091 to 135 AN.O. 0.2 A @ 120 Vac/dc1.0 A or less•Solid-core• H709HV1 to 135 AN.O. 1.0 A @ 250 Vac1.0 A or lessSolid-core• H8090.75 to 50 AN.O. 0.2A @ 120 Vac/dc0.75 A or less•Solid-core • 1• H9092.5 to 135 AN.O. 0.2 A @ 120 Vac/dc2.5 A or less•Split-core• H909HV2.5 to 135 AN.O. 1.0A @ 250 Vac2.5 A or lessSplit-core• 1. Listed for use on 75°C insulated conductors. ORDERING INFORMATION 2.5" * (64 mm) 2.1" (54 mm) 3.5" (89 mm) 2.9" (74 mm) 0.4” x 0.2” (10 mm x 5 mm) Slot (2x) 1.2" (31 mm) Removable Mounting Bracket 0.7" (18 mm) 0.5" (13 mm) 2.1" (54 mm) 1.0" (26 mm) 0.6" (16 mm) Self-gripping Iris 0.7" (18 mm) 0.4” x 0.2” Slot (x2) 2.8" * (71 mm) 1.7 (43 mm) 2.3" (58 mm) 1.1" * (27 mm) 0.9" (23 mm) Removable/Adjustable Mounting Bracket 0.2” x 0.15” slot (2x) 1.1" * (27 mm) 2.8" (68 mm) 0.7" (19 mm) 0.9" (23 mm) 3.0" ** (75 mm) Removable/Adjustable Mounting Bracket 3.8" (95 mm) 4.2" (106 mm) * Terminal block may extend up to 1/8” over the height dimensions shown. ** Slide switch may extend up to 1/4” over the height dimensions shown. Removable Mounting Bracket Self-gripping Iris 1.0” (25 mm) 0.8” (21 mm) 1.1” (26 mm) 3.1”** (79 mm) 2.8” (70 mm) Ø 0.3” (8 mm) 1.4”* (36 mm) 2.5” (64 mm) 3.0” (76 mm) Bracket can be mounted on three sides for added installation flexibility. H609 Dimensional Drawing H709/H709HV Dimensional Drawing H809 Dimensional Drawing H909/H909HV Dimensional Drawing MONITORING FAN /PUMP MOTORS FOR POSITIVE PROOF OF FLOW Wiring Diagram Motor Fan or Pump CONTROLLER Digital Input CONTACTOR 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM Current Monitoring | Hx09 Series HQ0001755.G 0117Next >