TM CURRENT MONITORING INSTALLATION GUIDE Z202763-0D PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. Fractional HP Motor Status Sensor/ Command Relay HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. • This equipment must only be installed and serviced by qualified electrical personnel. • Read, understand and follow the instructions before installing this product. • Turn off all power supplying equipment before working on or inside the equipment. • Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION • Only install this product on insulated conductors. Failure to follow these instructions will result in death or serious injury. A qualied person is one who has skills and knowledge related to the construction and operation of this electrical equipment and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2009 Article 100 No responsibility is assumed by Veris Industries for any consequences arising out of the use of this material. DANGER H540NS/548NS TM 540NS/548NS NOTICE • This product is not intended for life or safety applications. • Do not install this product in hazardous or classified locations. • The installer is responsible for conformance to all applicable codes. • Mount this product inside a suitable fire and electrical enclosure. Installer’s Specifications Amperage Range H540NS: 0.25 to 15 A; H548NS: 0.5 to 15 A Frequency Range 50-60 Hz Operating Temperature Range -15°C to 50°C (5° to 122°F) Operating Humidity Range 0-95% non-condensing Wire to Relay Contacts Use 12 AWG (3.3 mm 2 ) or larger wire* Terminal Block Torque Relay control terminals: 3.5 in-lb (0.4 N-m) All other terminals: 12 in-lb (1.35 N-m) Relay: Switching Capacity at 120 VAC 1 HP Relay Output SPST F.S. N.O. or N.C. Relay Coil 24 VAC/DC; 36 mA nom Current Sensor: Sensor Supply Voltage Induced Status Output Rating N.O. 1.0 A at 30 VAC/DC Trip Point H540NS: Fixed (on/off status); H548NS: Adjustable (belt loss detection) Agency Approvals UL508, Installation Category III * For current loads up to 10A, use 75°C rated wire insulation. For loads greater than 10A, use 90°C rated wire insulation. Specification Note: For CE compliance, insulate conductor according to IEC 61010‑1:2001. The product design provides for basic insulation only. Dimensions 2.13" (55 mm) 1.16" (30 mm) 4.25" (108 mm) 1.53" (39 mm) C L C L C L Wire Opening Wire Opening Wire Opening 1.16" (30 mm) 4.25" (108 mm) quick install 1. Disconnect power sources prior to installation. 2. Remove the sensor lid and wire the command relay connections and relay controls to the base. 3. Set the relay contact jumper. 4. This device has four wiring options, detailed on page 2-3 of this installation guide. Choose the option appropriate to the application and follow instructions. operation The H540NS and H548NS devices combine a switching relay and a current status sensor into a single housing. The device is connected in series between the power source and the motor device, and the relay controls the on/off functioning of the motor. The current switch trip point is fixed at 0.25 A on the H540NS and adjustable from 0.5 to 15 A in the H548NS. The maximum load is 15 A for both devices. The H540NS and H548NS require no additional power source for operation. VERIS INDUSTRIES, IN C. PORTLAND, ORE GON USA TOLL FREE U SA 1.800.354 .8556 TEL USA 1.503.598. 4564 FAX USA 1.503.598.466 4 540NS HAND OFF AUTO CAUTION: Consult instructions prior to installation ! STATUS OUTPUT: 1A@30VAC/DC RELAY COIL: 24VAC/DC; 16mA nom. RELAY OUTPUT: 16(8)A@250VAC; 3/4 HP RS OC SO SP SC VERIS INDUSTRIES, I NC. PORTLAND, OREGON USA TOLL FREE USA 1.800.354.8556 TEL USA 1.503.598.4564 FAX USA 1.503.598.4664 548NS HAND OFF AUTO CAUTION: Con sult instructions prior to insta llation ! STATUS OUTPUT: 1A@30VAC/DC RELAY COIL: 24VAC/DC; 16mA nom. RELAY OUTPUT: 16(8)A@250VAC; 3/4 HP RS OC SO SP SCZ202763-0D PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. TM INSTALLATION GUIDE H540NS/548NS Wiring boarD 1 2 1. Line current terminals: Common Normally Open Normally Closed 2. 24 VAC/DC Relay installation Prior to installation, disconnect and lock out all power sources. 1. Open the device. Set aside the lid and the bag of hardware enclosed. VERIS INDUSTRIES, INC. PORTLAND, OREGON USA TOLL FREE USA 1.800.354.8556 TEL USA 1.503.598.4564 FAX USA 1.503.598.4664 540NS CAUTION: Consult instructio ns prior to installation STATUS OUTPUT: 1A@30VAC/DC RELAY COIL: 24VAC/DC; 16mA nom. RELAY OUTPUT: 16(8)A@250VAC ; 3/4 HP RS OC SO SP SC 2. Wire the 24 AC/DC relay control through the top hole of the device. Use only copper conductors for command relay inputs. Tighten terminal blocks to 3.5 in-lb (0.4 N-m) torque. Keep wires away from the N. O. and N. C. jumper blocks. 24VAC/DC Relay Control / Status Control Status Output & Relay Coil (Low Voltage Wires Only) 3. Wire the line current from the controller to the Common terminal. Wire the second line to either the N. O. terminal or the N. C. terminal. The device is shown here as wired to the N.O. block. Tighten line current terminal blocks to 12 in-lb (1.35 N-m) torque. Common N.O. block N.C. block 4. Select one of the following mounting configurations (a, b, c, or d) to match your installation. a.) duplex box: Mounting slot Mounting hole Line Voltage Wires Connect line voltage wires to line current terminals Wire the 12 AWG lines from the controller through the back of the device, to the line current terminals. Tighten line current terminal blocks to 12 in-lb (1.35 N-m) torque. Use the base as a template for mounting to the wall using the mounting hole and slot shown. b.) 4S junction box: Line Voltage Wires Connect line voltage wires to line current terminals Mounting hole Mounting hole Wire the 12 AWG lines from the controller through the back of the device, to the line current terminals. Tighten line current terminal blocks to 12 in-lb (1.35 N-m) torque. Use the base as a template for mounting to the wall using the mounting holes shown.Z202763-0D PAGE 3 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. TM INSTALLATION GUIDE H540NS/548NS calibration (H548ns only) Note: Testing the solid-state status output of this sensor with a digital ohmmeter may yield inaccurate, but relative readings of switching (e.g. 6 MΩ) Use an analog V-O-M for readings similar to loop values. Calibration to be done while motor is running normally. 1. For under-current status indication: (Belt loss, fan & pump status) • Turn the set point screw clockwise until the status closed LED goes out and the status open LED comes on. • Turn the set point screw counter-clockwise until the status open LED goes out and the status closed LED comes on. • Turn the set point screw 1/2 turn counter-clockwise. • The sensor is now calibrated to provide indication of current flow below normal full load amps. Output Status: Normal: Output closed Alarm: Output open 2. For over-current status indication: (Locked rotor) • Turn the set point screw counter-clockwise until the status open LED goes out and the status closed LED comes on. • Turn the set point screw clockwise until the status closed LED goes out and the status open LED comes on. • Turn the set point screw clockwise 1/2 turn • The sensor is now calibrated to provide indication of current flows above normal full load amps Output Status: Normal: Output open Alarm: Output closed c.) surface mounting: Line Voltage Wires Connect line voltage wires to line current terminals Wire the 12 AWG lines from the controller through the side of the device, onto the line current terminals. Tighten line current terminal blocks to 12 in-lb (1.35 N-m) torque. d.) nipple mount to another enclosure: Insert the conduit nuts (provided) into the slots in the side hole of the device for additional weight support. Connect line voltage wires to line current terminals ENCLOSURE Nipple to existing enclosure (conduit nipple fitting not provided) Line voltage wires Wire the 12 AWG lines from the controller through the side of the device, from the enclosure to the line current terminals. Tighten line current terminal blocks to 12 in-lb (1.35 N-m) torque. 5. Use the knockout seal to cover any unused holes in the housing. Attach the cover, securing with the screws provided. NOTE: If a conduit is used, connect the conduit to the mounting hub before connecting it to the device. Be sure to support the H540NS/548NS housing when nipple‑mounted to another enclosure, or the unit may shift on opening, potentially causing undue stress on the wiring and the terminals.Z202763-0D PAGE 4 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com 07122 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries. TM INSTALLATION GUIDE H540NS/548NS Wiring example C N.C. N.O. 2 1 3 45 6 7 8 9 1. Power Terminal Block: Wire the H540NS/548NS in series with the motor using these terminals. Choose N.O. or N.C. 2. Current Sensor: In-series current sensor for motor status. 3. Relay: Enables actuation of circuit by a control system. 4. Relay Coil Terminal Blocks: Wire the output signal from the control panel to actuate the relay. 24 VAC/DC; 36 mA nominal. 5. Status Terminal Blocks: Wire the status input back to the control panel. 6. Relay Status LED: For positive indication of energized coil. 7. Status Open LED: Indicates that the current is below the trip point and the status contact is open (used to calibrate the current switch in H548NS models only). 8. Current Switch Set-Point Screw: Used to adjust the point in the current range at which the current switch will change states (used to calibrate the current switch in H548NS models only). 9. Status Closed LED: Indicates that the current is above the trip point and the status contact is closed (used to calibrate the current switch in H548NS models only). CAUTION! Do not rely on status indicators to determine whether or not the relay contacts are connected to a power source. Doing so may result in injury or death from electrical shock. If the connections to the unit are made through more than one metallic conduit, bond the conduits to prevent the hazard of electric shock. A bonding plate is available (Veris part AH10).Next >