EP2 GENERAL Input Power Class 2; 24 Vac/dc nominal, 30 Vac max.; 150 mA max. Control Input Class 2; 4 to 20mA/0-5 V/0-10 Vdc; jumper-selectable Input Impedance4 to 20 mA, 250 Ω; 0-5 V/0-10 Vdc, 10 kΩ Manual OverrideJumper-selectable mode, digital pushbutton adjust Alarm Contact100 mA@30 Vac/dc (pressure loss, manual mode, jumper selectable) Accuracy1% FS; combined linearity, hysteresis, repeatability Compensated Temp Range-4 to 65 °C (25 to 140 °F) Temperature Coefficient±0.05%/°C EP Series transducers are sold as an open device. Observe handling precautions for static sensitive devices to avoid damage to the circuitry which would not be covered under the factory warranty. **The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details. *For shorter tubing runs use AA45 Pneumatic Capacitor EMC Conformance - CE option: Low voltage directive 2014/35/EU; EMC directive 2014/30/EU. EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1 specification requirements). The EP2 Series electropneumatic pressure transducer uses micro- controlled poppet valve technology for highly accurate pressure sensing in multiple applications. The poppet valves consume no air, eliminating unnecessary air losses in the system and allowing for stable and reliable operation. The EP2 comes installed on standard SnapTrack, and an optional dust cover is available to protect from the environment. An LCD display and LED indicators make it easy to read system status at a glance. APPLICATIONS • Hospitals • Schools • Pneumatic dampers/actuators Operating Environment10 to 90% RH non-condensing Air Capacity523 in3/min @ 45 psi (8570 cm3/min @ 310.3 kPa); 333 in3/min @ 20 psi (5456 cm3/min @ 137.9 kPa) Supply Pressure45 psig max. Control Range0 to 20 psig or 3 to 15 psig, jumper-selectable Pressure Differential0.1 psig (supply to branch) Pressure IndicationElectronic, 3-1/2 digit LCD Minimum Tubing Length15 feet* Port Connection1/8” I.D. poly tubing Media ConnectionClean, dry air, or inert gas. Do not use with oxygen service WARRANTY Limited Warranty5 years AGENCY APPROVALS Field selectable Field-selectable 4 to 20 mA/ 0-5 V/0-10 Vdc input for application flexibility Multi-point calibration Multi-point calibration; 3 to 15 psi (5-point calibration) and 0 to 20 psi (6-point calibration) Quiet operation Poppet valve technology for quiet operation Pressure loss alarm Pressure loss alarm provides a contact closure if the EP3 is unable to achieve the desired output within a fixed length of time Manual override Manual override with set and hold feature…great for commissioning leaky systems Fail-safe vent Fail-safe vent solenoids bleed branch pressure on power failure for added safety SPECIFICATIONS Available ** 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com TM EP2 SERIES Micro-Controlled with High-Performance, Low-Power Coil Poppet Valve Technology Pressure Monitoring | Electropneumatic Transducers HQ0001828.F 01173.3" (84 mm) 1.8" (46 mm) 3.5" (89 mm) 4.9" (125 mm) 2.1" (53 mm) If the dust cover is ordered, the EP2 is mounted to a longer Snaptrack. FROM CONTROL SYSTEM GND/COMMON INPUT SIGNAL POWER TO DIGITAL INPUT - OPTIONAL PRESSURE LOSS ALARM ALARM MODE MANUAL ADJUST ON OFF Auto Manual 0-20psi3-15psi 0-5V 0-10V Current Voltage GND/COM INPUT SIGNAL POWER PRESSURE RANGE PRESSURE LOSS ALARM (OPTIONAL) OPERATION MODE INPUT MODE VOLTAGE MODE Slide Switch Option Available Output = Selectable 3-15/0-20 psi US or EU S = Standard C = CE, includes cover plate Feedback 0 = None 1 = Pressure Loss Alarm 2 = Manual Mode Alarm EP2 Failsafe 0 = None 1 = Vent on Power Fail Option Blank = none 1 = Slide Switch/Auto/Manual 2 = EP Cover Plate 3 = Slide Switch/Auto/Manual plus EP cover plate 1 WIRING DIAGRAM CONFIGURATION DIMENSIONAL DRAWINGS ORDERING INFORMATION EP2100S1 Option = Slide Switch Auto Manual Mode Example: DUST COVER Dimensional Drawings (Front View)Side View Pressure Monitoring | EP2 Series HQ0001828.F 0117Next >