INPUTS Input PowerE3xA/B/C: 90 to 277 Vac line-to-neutral, 50/60 Hz, 8 VA E3xE: 100 to 277 Vac line-to-neutral, 50/60 Hz, 15 VA ACCURACY Power/EnergyIEC 62053-21 Class 1, ANSI C12.1-2008. 1% system accuracy (includes main board and 50 A or 100 A branch CTs) Voltage±0.5% of reading 90 to 277 Vac line-to-neutral Current±0.5% of reading Minimum ON Current50 mA OPERATION Sampling Frequency2560 Hz Update Rate 2 seconds (both panels) Overload Capability 22 kAIC OUTPUTS Serial ProtocolsAll: Modbus RTU E3xE models: BACnet MSTP Serial ConnectionAll: 2-wire, RS-485 E3xA/B/C models: 4-wire RS-485 AddressE3xA/B/C models: Selectable address 1 to 247 (uses 2 addresses for Modbus RTU) E3xE models: Selectable at address 1 to 247 for Modbus RTU; 0 to 127 for BACnet MS/TP Baud RateAll: 9600, 19200, 38400 (selectable on A/B/C models) Integrated Ethernet with SNMP, BACnet, & Modbus E3xA/B/C E3xE E30 & E31 SERIES Monitor Entire Panelboards with One Device SPECIFICATIONS * Indoor use only. **The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformity for additional details. ***E30xxx (solid-core) models only. ® T E S T I N G L ABO R A T O R I E S · B A Cn e t · (E31E only) ** The E30 & E31 Series Panelboard Monitoring System provides a cost effective solution for electrical load management, making it ideally suited for applications where loads are dynamic, such as the data storage industry, lighting panels, etc. The E30 & E31 Series monitors the current, voltage, instantaneous power, demand, and energy consumption of each circuit in a panelboard including the main feed.* As a circuit approaches the user- configured thresholds, alarm indicators are triggered, preventing costly downtime from overloaded circuits or failed loads. (See graph, facing page). * E3xB/C models have less capability. ParityAll: Modbus RTU: NONE, ODD, EVEN (selectable on A/B/C models) E3xE models: BACnet MS/TP: NONE (fixed) Terminal Block Torque 4.4 to 5.3 in-lb (0.5 to 0.6 N-m) Ethernet Protocols All: Modbus TCP E3xE models: BACnet IP, SNMP V2c Ethernet ConnectionE3xE models only: RJ-45 10/100 Mbit ENVIRONMENTAL Operating Range0 to 60 °C (32 to 140 °F) (<95% RH non-condensing)* Storage Temp Range-40 to 70 °C (-40 to 158 °F) Altitude of Operation3000 m WARRANTY Limited Warranty5 years AGENCY APPROVALS Agency ApprovalsUL508, EN61010-1, Cat. III, pollution degree 2 Type Approval***California Code of Regulations, Title 4, Division 9, Article 1. National Uniformity Exceptions and Additions, 2016 edition APPLICATIONS • Load-based cost allocation • Overload protection • Data center PDUs • Sub-tenant billing • Lighting control panels • Load management • Load balancing • Energy management Revenue grade ANSI and IEC Class 1 metering system accuracy including branch CTs Retrofit or new construction New construction and retrofit applications with solid-core and split-core CT models 50 mA to 100 A Widest dynamic range in the industry, 50 mA to 100 A monitoring Up to 92 Channels Monitor up to 92 circuits per unit providing unlimited possibilities for monitoring Versatility Flexible installation with 3/4”, 1”, or 18 mm spaced solid-core branch CT strips Configure the meters you want Choose 4, 8, 14 or 28 3-phase meters. User-configurable to any combination of 1-, 2-, 3-phase meters. Reconfigure channels as needed to monitor neutral current. 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM Power Monitoring Multi-Circuit | Panelboard Monitoring System HQ0001714.L 04177.3” (184 mm) 8.9” (226 mm) 5.8” (146 mm) 4.8” (122 mm) 3.9” (100 mm) 7.9” (200 mm) 8.3” (211 mm) 1.75” (45 mm) Ø = 0.2” (5 mm) 0A Ch. 2 Ch. 1 TIME High High High Alarm Latched Low Alarm Latched No Alarm Latched Low Low Alarm Latched High Low Low Low AMPS 13.9” (353 mm) 2x: 5.9” (150 mm) 12.8” (325 mm) 8.9” (225 mm) 10.0” (253 mm) 12.1” (307 mm) 8.2” (210 mm) 2.8” (71 mm) E3xAE3xBE3xCE3xE MONITORING AT MAINS Current per phase•••• Max. current per phase•••• Current demand per phase•••• Max. current demand per phase•••• Current phase angle••• Energy (kWh) per phase••• Real Power (kW) per phase••• Apparent Power (kVA)••• Power factor total*••• Power factor per phase••• Voltage, L-L and average••• Voltage, L-N and average••• Voltage, L-N and per phase••• Frequency (phase A)••• MONITORING AT BRANCH CIRCUIT Current•••• Max. current•••• Current demand•••• Max. current demand•••• Current phase angle•• Real power (kW)•• Real power (kW) demand•• Real power (kW) demand max.•• Energy (kWh) per circuit•• Power factor•• Apparent Power (kVA)•• MODBUS ALARMS Voltage over/under••• Current over/under•••• PROTOCOLS SUPPORTED Modbus RTU•••• Modbus TCP******• BACnet MS/TP†††• BACnet IP with BBMD support†††• SNMP V2‡‡‡• * Based on a 3-phase breaker rotation. ** With UO13-0012 or E8951 added. † With E8951 added. ‡ With E8951 added; requires one E8951 for each meter. PRODUCT CAPABILITIES OPERATION EXAMPLE E30A/B/C & E31A/B/C MAIN BOARD Dimensional Drawing E30E & E31E Dimensional Drawing 800.354.8556 | +1 503.598.4564 | sales@veris.com | intl@veris.com | www.veris.com TM Power Monitoring Multi-Circuit | E30 & E31 Series HQ0001714.L 04170.4” (10 mm) opening 1.0” (26 mm) on center 25.0” (635 mm) 1.2” (31 mm) 20.3” (516 mm) 1.1” (28 mm) 0.8” (20 mm) 0.8” (20 mm) 1.3” (33 mm) 2.0” (50 mm) slot: 0.25” x 0.5” (7 x 13mm) 2.0” (50 mm) 1.7” (43 mm) 1.3” (32 mm) slot: 0.25” x 0.5” (7 x 13mm) 1.2” (30 mm) 0.4” (10 mm) opening 0.75” (19 mm) on center 16.4” (417 mm) 1.7” (43 mm) 0.4” (10 mm) opening 0.7” (18 mm) on center 2.0” (50 mm) 0.9” (21.2 mm) 0.9” (21.2 mm) 0.9” (21.2 mm) 1.3” (32 mm) 15.7” (399 mm) 0.4” (10 mm) opening 0.7” (18 mm) on center 1.3” (32 mm) 12.3” (312 mm) 0.4” (10 mm) opening 0.7” (18 mm) on center E30 Branch CT Spacing 0 = 100 A, ¾" spacing 1 = 100 A, 1" spacing 2 = 100 A, 18 mm spacing Description A = Advanced B = Intermediate C = Basic E = Advanced w/Ethernet # of Branch CTs & Ribbon Cables 24 = 2 strips of 12 branch CTs (18 mm only) and two 4-ft. round ribbon cables 36 = 2 strips of 18 branch CTs (18 mm only) and two 4-ft. round ribbon cables 42 = 2 strips of 21 branch CTs (¾”, 1”, or 18 mm) and two 4-ft. round ribbon cables 48 = 4 strips of 12 branch CTs (18 mm only) and four 4-ft. round ribbon cables 72 = 4 strips of 18 branch CTs (18 mm only) and four 4-ft. round ribbon cables 84 = 4 strips of 21 branch CTs (¾”, 1”, or 18 mm) and four 4-ft. round ribbon cables Example: E30A042 Free configuration tool available from www.veris.com. Consult factory for additional mounting options. NOTE: CTs for mains (not used on E3xC models) must be ordered separately. Use 0 to 0.333V CTs rated for use with Class 1 voltage inputs. SOLID-CORE BRANCH CT s 100 A SOLID-CORE BRANCH CT Voltage Rating300 Vac Temperature0 to 60 °C AgencyEN61010-1 Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty. PANELBOARD Wiring Diagram BRANCH CT STRIPS Dimensional Drawing E30 (SOLID-CORE) ORDERING INFORMATION E30 Solid-Core CT Strips Solid-Core CT Strips Monitor Mains Using 0.333 V CTs E30 Main Board Power Monitoring Multi-Circuit | Panelboard Monitoring System Solid-Core HQ0001714.L 0417WIRING DIAGRAM E31E31xY63 4.6” (117 mm) 2.75” (70 mm) 1.00” (26 mm) 1.00” (26 mm) 9.75” (248 mm) 8.75” (222 mm) E31 E31CT CBL0 Description Description Description # of CTs Ordering Examples: Option A: For monitoring 42 or 84 circuits, order a pre-made kit from Group 1 only (see Application/Wiring Diagram above). Example: E31x42 or E31x84 Option B: For monitoring other configurations, build your own kit by selecting from Groups 1, 2, and 3. Example kit for an 18-circuit panel retrofit: 1 E31A002 - Advanced board, 2 adapter boards (1 unit) 2 E31CT0 - 50A Branch CT six-pack (3 units) 3 CBL023 - 10 ft. round ribbon cable (2 units) NOTE: CTs for mains (not used on E3xC models) must be ordered separately. Use 0 to 0.333 V CTs rated for use with Class 1 voltage inputs. 1 2 Boards Branch CTs (up to 21 CTs per adapter board) Ribbon Cable (order 1 cable per adapter board) A = Advanced board B = Intermediate board C = Basic board E = Advanced with Ethernet 0 = 6-pack, 50A Branch CT, 6 ft. (1.8 m) lead 0R20 = 6-pack, 50A Branch CT, 20 ft. (6 m) lead 1 = 6-pack, 100A Branch CT, 6 ft. (1.8 m) lead 1R20 = 6-pack, 100A Branch CT, 20 ft. (6 m) lead 34 = Round Ribbon Cable, 1 ft. (0.3 m) 31 = Round Ribbon Cable, 18 in. (0.5 m) 32 = Round Ribbon Cable, 30 in. (0.8 m) 22 = Round Ribbon Cable, 4 ft. (1.2 m) 33 = Round Ribbon Cable, 8 ft. (2.4 m) 23 = Round Ribbon Cable, 10 ft. (3 m) 24 = Round Ribbon Cable, 20 ft. (6 m) 08 = Flat Ribbon Cable, 18 in. (0.5 m) 16 = Flat Ribbon Cable, 4 ft. (1.2 m) 17 = Flat Ribbon Cable, 5 ft. (1.5 m) 18 = Flat Ribbon Cable, 6 ft. (1.8 m) 19 = Flat Ribbon Cable, 8 ft. (2.4 m) 20 = Flat Ribbon Cable, 10 ft. (3 m) 21 = Flat Ribbon Cable, 20 ft. (6 m) 3 = Single CT, 200A Branch CT, 6 ft. (1.8 m) lead 3R20 = Single CT, 200A Branch CT, 20 ft. (6 m) lead 002 = 2 adapter boards, no CTs, no cables 004 = 4 adapter boards, no CTs, no cables 42 = 2 adapter boards, 42 50A CTs, 2 4 ft. round ribbon cables 84 = 4 adapter boards, 84 50A CTs, 4 4 ft. round ribbon cables Y63 = 2 adapter boards, flat ribbon cables, pre-assembled on one bracket, CTs not included (not available with E31E models) SPLIT-CORE BRANCH CT s 50 A SPLIT-CORE BRANCH CT 100 A SPLIT-CORE BRANCH CT 200 A SPLIT-CORE BRANCH CT Voltage Rating300 Vac 300 Vac (CE), 600 Vac (UL) 300 Vac (CE), 600 Vac (UL) Measurement Range 0 to 60 A0 to 120 A0 to 240 A Temperature0 to 60 °C0 to 60 °C0 to 60 °C Agency UL 61010-1 Recognized, EN61010-1 UL 61010-1 Recognized, EN61010-1 UL 61010-1 Recognized, EN61010-1 Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty. D E C B A D E B A C E31CT0 50 Amp (0 to 60 Amp Range) A = 1.0” (26 mm) B = 0.5” (11 mm) C = 0.4” (10 mm) D = 0.9” (23 mm) E = 1.6” (40 mm) E31CT1 100 Amp (0 to120 Amp Range) A = 1.5” (39 mm) B = 0.8” (20 mm) C = 0.7” (16 mm) D = 1.6” (40 mm) E = 2.1” (53 mm) E31CT3 200 Amp (0 to 240 Amp Range) A = 1.5” (39 mm) B = 1.25” (32 mm) C = 1.25” (32 mm) D = 2.5” (64 mm) E = 2.8” (71 mm) B E A C D 3 E31 ADAPTER BOARD Dimensional Drawing BRANCH CT s Dimensional Drawing E31XY63 BOARDS WITH BRACKET Dimensional Drawing E31 (SPLIT-CORE) ORDERING INFORMATION Power Monitoring Multi-Circuit | E30 & E31 Series HQ0001714.L 0417Next >