Flowrite™ 599 Series Technical Instructions Document No. 155-163P25 September 25, 2018 SKB/C Electronic Valve Actuator Proportional Control Siemens Industry, Inc. Description The Flowrite 599 Series SKB/C Electronic Valve Actuator requires a 24 Vac supply and receives a 0 to 10 Vdc or a 4 to 20 mA control signal to proportionally control a valve. This actuator is designed to work with Flowrite 599 Series valves with a 3/4-inch (20 mm) or 1-1/2-inch (40 mm) stroke. Features • Direct-coupled installation requires no special tools or adjustments • Visual and electronic stroke indication • Die-cast aluminum housing • Manual override • Spring return to fail-safe position • Automatic stroke calibration • Maintenance-free Application These electronic actuators are designed to be used with Flowrite 599 Series valves with 3/4-inch (20 mm) stroke (SKB) and 1-1/2 inch (40 mm) stroke (SKC) in liquid and steam service applications. Product Numbers Actuator Stroke Order Number Actuator Prefix Code 3/4-inch (20 mm) SKB62U 291 1-1/2 inch (40 mm) SKC62U 294 Technical Instructions Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Document Number 155-163P25 September 25, 2018 Page 2 Siemens Industry, Inc. Warning/Caution Notations WARNING: Personal injury/loss of life may occur if you do not perform a procedure as specified. CAUTION: Equipment damage or loss of data may occur if you do not follow a procedure as specified. Specifications Power Supply Operating voltage SKB/C62U 24 Vac 20% Frequency SKB/C62U 50/60 Hz Power consumption SKB62U 18 VA/12W SKC62U 28 VA/20W Control signal Control input (Y) SKB/C62 Voltage 0 to 10 Vdc or 4 to 20 mA Maximum Impedance 0 to 10 Vdc, 100K ohms 4 to 20 mA, 250 ohms Control input (Z) SKB/C62U Resistance 0 to 1000 ohms Voltage 0 to 1.6 Vdc Feedback signal Control output (U) SKB/C62U Voltage 0 to 10 Vdc Load impedance >500 ohms Current 4 to 20 mA Load impedance <500 ohms Equipment rating Rating SKB/C62U Class 2 according to UL, CSA Function Nominal stroke SKB62U 3/4-inch (20 mm) SKC62U 1-1/2 inches (40 mm) Run time with control operation (full stroke) Open/Close Spring Return SKB62U 120 seconds 15 seconds SKC62U 120 seconds 20 seconds Nominal Force SKB/C62U Stroke Force NC and 3-way upper 0% 640 lbs (2800 N) NO and 3-way by-pass 100% 1000 lbs (4400 N) Housing Mounting location NEMA 1 (interior only) NEMA TYPE 3R rated when installed with 599-10065 weather shield. See Accessories. Ambient conditions Ambient temperature (Operation) 5°F to 130°F (-15°C to 55°C) Media temperature 20°F to 337°F (-7°C to 170°C) Agency certification UL UL873 cUL Certified to Canadian standard C22.2 No. 24-93 CE Conformity as per the EMC directive 89/336/EEC Low voltage directive 78/23/EEC Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Technical Instructions Document Number 155-163P25 September 25, 2018 Siemens Industry, Inc. Page 3 Specifications, continued Miscellaneous Conduit opening 1/2-inch NPSM Dimensions See Figure 18 Weight SKB62U 18.9 lbs (8,6 kg) SKC62U 22 lbs (10,0 kg) Accessories Installation instructions are included with each accessory. Figure 1. Auxiliary Switch. ASC1.6 Auxiliary switch sends a signal to indicate the valve is in the 0% stroke position. Switching point is fixed at the 0% stroke position. Switching capacity 24 Vac 4A resistive, 2A inductive Lowest recommended current 10 mA Figure 2. Stem Heating Element. ASZ6.6 The stem heating element prevents the formation of ice on the stem when the medium temperature drops below 32°F (0°C). It is suited for universal use with valves having a stem or spindle diameter of 10 or 14 mm. Operating voltage 24 Vac/dc ± 20% Power consumption ≤ 40 VA/30W Figure 3. Weather Shield. 599-10065 The SKB/C actuator is UL listed to meet NEMA Type 3R requirements (a degree of protection against rain, sleet, and damage from external ice formation) when installed with Weather Shield and outdoor-rated conduit fittings in the vertical position. See Service Kits for replacement ultraviolet resistant cable ties. Technical Instructions Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Document Number 155-163P25 September 25, 2018 Page 4 Siemens Industry, Inc. Service Kits Circuit board replacement 4 668 5748 8 Manual override kit 4268 5510 8 Plastic wiring compartment cover 4 104 5582 8 Stem retainer kit Contains one stem nut (Figure 7, Item 6) and one stem retainer clip. 2-1/2 and 3-inch valves 599-10048 4, 5, and 6-inch valves 599-10049 Retainer clamp kit 599-10200 Ultraviolet (UV) resistant cable ties (pkg. of 8) 538-994 WARNING: This product contains a spring under high compression. Do not attempt to disassemble the actuator. Operation A 0 to 10 Vdc or a 4 to 20 mA control signal controls the actuator. The actuator, mounted on a valve, produces a stroke proportional to the input signal. When power is turned off or in the event of a power failure, the actuator spring returns the valve to its normal position. Figure 4. Input Signal. Figure 5. Spring Return. SKB/C Details Figure 6. Actuator Design. Legend 1. Pressure cylinder 2. Piston 3. Oscillating pump 4. Return springs 5. Bypass valve 6. Coupling piece (stem nut) 7. Manual setting knob 8. Position indicator Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Technical Instructions Document Number 155-163P25 September 25, 2018 Siemens Industry, Inc. Page 5 Mounting and Installation The vertical position is the required position for mounting and the only position for NEMA Type 3R rating with the Weather Shield. Acceptable mounting positions are shown in Figure 7. Figure 7. Acceptable Mounting Positions. Allow four inches (100 mm) around the sides and back of the actuator and eight inches (200 mm) above and to the front of the actuator. See dimensions in Figure 17 and Figure 18. Detailed installation instructions for field mounting are shipped with the actuator. CAUTION: Use care when removing the knockout. Do not damage the circuit board. Use the top knockout position, if possible. Start up Check the wiring for proper connections. NOTE: The valve body assembly determines the complete assembly action. Override Control The override control input (Z) has three modes of operation: NOTE: The Z-modes have a direct acting factory setting. Technical Instructions Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Document Number 155-163P25 September 25, 2018 Page 6 Siemens Industry, Inc. Start-up, continued Stroke Calibration To determine the stroke positions 0% and 100% in the valve, calibration is required when the valve/actuator are commissioned for the first time. The actuator must be mechanically connected to a valve and must have a supply voltage of 24 Vac. Repeat the calibration procedure as often as necessary CAUTION: Before starting calibration, be sure that the manual adjuster is set to Automatic for the actual values to register. There is a slot on the printed circuit boards for the actuators. To initiate the calibration procedure, the contacts inside this slot must be short-circuited (possibly with a screwdriver). See Figure 8. Automatic calibration proceeds as follows (see Figure 9): • Actuator runs to the 0% stroke position (1), green LED flashes. • Actuator then runs to the 100% stroke position (2), green LED flashes. • Measured values are stored in the EPROM. • The actuator now moves to the position defined by control signal Y or Z (3), and the green LED now glows steady (normal operation). • Throughout this procedure, output U is inactive, meaning the values only represent actual positions when the green LED stops flashing and remains on continuously. Figure 8. Figure 9. Automatic Calibration Table 1. LED Status. LED Display Function Action Green ON Normal Operation Automatic operation Flashing Stroke calibration In Progress Wait for calibration to be completed (LED stops flashing) Red ON Faulty stroke calibration Internal Error - Check mounting - Restart stroke calibration (by short-circuiting calibration slot) - Replace electronics Flashing Inner valve jammed Check the valve OFF • No power supply • Faulty electronics -Check mains -Replace electronics Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Technical Instructions Document Number 155-163P25 September 25, 2018 Siemens Industry, Inc. Page 7 Start-up, Continued Standard Features 1 2 Figure 10. DIP Switches. DIP Switches (From Left to Right) 1 Selection of Control Signal 2 Selection of Flow Characteristic ON 4 to 20 mA Modified* OFF (Factory Settings) 0 to 10 Vdc Default * Changing the default setting will modify an equal percentage valve to a linear flow characteristic. When set to default, the flow characteristic is determined by the valve body. Normally Closed Valve Actuator pressure cylinder moves: • Outward (0 to 1): Valve opens. • Inward (1 to 0): Valve closes. Normally Open Valve Actuator pressure cylinder moves: • Outward (0 to 1): Valve closes. • Inward (1 to 0): Valve opens. Technical Instructions Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Document Number 155-163P25 September 25, 2018 Page 8 Siemens Industry, Inc. Start-up, continued Three-way Valve Actuator pressure cylinder moves: • Outward (0 to 1): Valve opens between ports NC and C. • Inward (1 to 0): Valve opens between ports NO and C. Figure 11. Valve Stem Travel Indication. Manual operation Release the crank arm of the manual setting knob located on the top of the actuator. See Figure 12. A red scale appears in a window in the manual setting knob as you turn the crank clockwise, (see Figure 12). This scale indicates the effective valve stroke in millimeters. Each complete revolution (360°) is equal to 2 mm of stroke. The numbers 2 to 20 or 2 to 40 are visible depending on the stroke of the actuator. If a signal is sent to the actuator while it is in manual operation, the actuator will move but the control will not be accurate. The valve cannot be commanded to its 0% position while in manual operation. Figure 12. Manual Operation. CAUTION: Do not attempt automatic operation of the actuator when the red scale is visible. Flowrite 599 Series SKB/C Electronic Valve Actuator Proportional Control Technical Instructions Document Number 155-163P25 September 25, 2018 Siemens Industry, Inc. Page 9 Automatic operation When returning to automatic control, turn the crank arm of the manual setting knob counterclockwise until the red numbers disappear. It is essential that the window is clear and the crank arm is snapped into position. See Figure 13. NOTE: It is possible to secure the manual override handle in place by inserting a # 8 ×1-1/4-inch or M5 × 30 mm thread-forming screw through the handle. Figure 13. Automatic Operation. Wiring Do not use autotransformers. Use earth ground isolating step-down Class 2 transformers. Determine supply transformer rating by summing total VA of all actuators used. The maximum rating for Class 2 step-down transformer is 100 VA. Actuator Power Consumption Actuators per Class 2 Supply Circuit * (80% of transformer VA) SKB62U 17 VA 4 SKC62U 28 VA 2 * Operating more actuators requires additional transformers or separate 100 VA power supplies. Next >