Submittal Sheet Document No. 154-095 June 7, 2021 Pressure Independent Control Series 2-Way Flanged Valves and Electromotoric Valve Actuators Siemens Industry, Inc. Description The 2-1/2-inch and 3-inch Pressure Independent Control Valves have a 3/4-inch (20 mm) stroke, and work with the SAX and SQV Series Electromotoric Actuators. The 4-, 5-, and 6-inch valves have a 1-1/2-inch (40 mm) stroke, and work with the SAV and SQV Series Electromotoric Actuators. The actuators require a 24 Vac/dc operating voltage and accept floating, 0 to 10 Vdc, or 4 to 20 mA control signals. Typical applications include control of hot or chilled water or water-glycol solutions up to 50% in closed loop systems. Product Numbers Use the product numbers in the tables to order the valve and the actuator assembled together. The product number consists of a 3-digit prefix code, a hyphen, and a 5-digit code. The prefix specifies an actuator. The 5-digit code specifies the valve body. See Table 2. 238-07310 3-Digit Actuator Prefix Code 5-Digit Valve Body Code Table 1. Reference: Valve Body Maximum Flow Range. Valve Body Line Size Inch (mm) Maximum GPM Flow Range 599-07310 2-1/2 (65) Low Flow 19 to 110 599-07320 599-07330 2-1/2 (65) New 21 to 132 599-07335 599-07315 2-1/2 (65) High Flow 26 to 154 599-07325 599-07311 3 (80) Low Flow 24 to 150 599-07321 599-07331 3 (80) New 31 to 195 599-07336 599-07316 3 (80) High Flow 31 to 190 599-07326 599-07312 4 (100) Low Flow 55 to 300 599-07322 599-07332 4 (100) New 54 to 307 599-07337 599-07317 4 (100) High Flow 65 to 395 599-07327 599-07313 5 (125) Low Flow 85 to 485 599-07323 599-07318 5 (125) High Flow 105 to 595 599-07328 599-07314 6 (150) Low Flow 115 to 650 599-07324 599-07319 6 (150) High Flow 140 to 860 599-07329 Features The Pressure Independent Control Valves include a pressure regulator, a flow limiter, and a control valve in a single device. SAX, SAV, and SQV Actuators have a direct-coupled installation, manual override and visual position indication. Technical Data Valve Specifications Body material: Cast iron Stem: Stainless steel Line size: 2-1/2-inch (65 mm) to 6-inch (150 mm) Action: 2-way Valve body rating: ANSI 125/ANSI 250 Close-off: 100 psi (700 kPa) Δp Leakage rate: < ANSI Class IV (0.01%) Media temperature range: 34°F to 250°F (1°C to 121°C) Flow characteristic: Linear Connection: ANSI flanged Actuator Specifications Operating voltage: SAX, SAV, SQV 24 Vac/dc Frequency: 50/60 Hz Power consumption (normal operation): SAX81.03U/SAV81.00U 5 VA (3.75W)/7 VA (4.5W) SAX61.03U/SAV61.00U 8 VA (3.75W)/9.5 VA (4.5W) SQV 20 VA/7.5W Control Signal: SAX81.03U/SAV81.00U Floating SAX61.03U/SAV61.00U 0 to 10 Vdc, 4 to 20 mA SQV Selectable (Floating, 0 to 10 Vdc, 4 to 20 mA) Run time: SAX 30 seconds SAV 120 seconds SQV 40 to 240 seconds (adjustable) Force: SAX 180 lb (800 N) SAV 360 lb (1600 N) SQV 250 lb (1100 N) Weight: SAX 4.1 lbs (1.85 kg) SAV 4.23 lbs (1.92 kg) SQV 14 lbs (6.2 kg) Additional References: Agency Certifications: UL UL 873 cUL Canadian Standard C22.2 No. 24 Technical Instructions PICV Valves 155-522 SAX Actuators 155-506, 155-507 SAV Actuators 155-547, 155-548 SQV Actuators 155-521 Submittal Sheet Pressure Independent Control 2-Way Flanged Valves Document No. 154-095 and Electromotoric Valve Actuators June 7, 2021 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Products or company names mentioned herein may be the trademarks of their respective owners. © 2021 Siemens Industry, Inc. Siemens Industry, Inc. Smart Infrastructure 1000 Deerfield Parkway Buffalo Grove, IL 60089 USA + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com Document No. 154-095 Printed in the USA Page 2 of 2 Typical Specifications Flow shall be varied by actuator position. At any given position, flow through the valve shall not vary more than ±5% due to system pressure fluctuations across the valve in the selected operating range. Table 2. 2-1/2-Inch to 6-Inch 2-Way Valve and Actuator Assemblies. Valve Body ANSI Class Line Size, Inch (mm) Maximum Flow Non-Spring Return Spring Return SAX61.03U 0 to 10V SAX81.03U Floating SAV61.00U 0 to 10V SAV81.00U Floating SQV91P30U Normally Open SQV91P40U Normally Closed Floating, 0 to 10V, 4 to 20 mA Actuator Prefix Code 371 373 378 379 238 239 599-07310 125 2.5 (65) 110 371-07310 373-07310 - - 238-07310 239-07310 599-07320 250 371-07320 373-07320 - - 238-07320 239-07320 599-07330 125 132 371-07330 373-07330 - - 238-07330 239-07330 599-07335 250 371-07335 373-07335 - - 238-07335 239-07335 599-07315 125 154 371-07315 373-07315 - - 238-07315 239-07315 599-07325 250 371-07325 373-07325 - - 238-07325 239-07325 599-07311 125 3 (80) 150 371-07311 373-07311 - - 238-07311 239-07311 599-07321 250 371-07321 373-07321 - - 238-07321 239-07321 599-07316 125 190 371-07316 373-07316 - - 238-07316 239-07316 599-07326 250 371-07326 373-07326 - - 238-07326 239-07326 599-07331 125 195 371-07331 373-07331 - - 238-07331 239-07331 599-07336 250 371-07336 373-07336 - - 238-07336 239-07336 599-07312 125 4 (100) 300 - - 378-07312 379-07312 238-07312 239-07312 599-07322 250 - - 378-07322 379-07322 238-07322 239-07322 599-07332 125 307 - - 378-07332 379-07332 238-07332 239-07332 599-07337 250 - - 378-07337 379-07337 238-07337 239-07337 599-07317 125 395 - - 378-07317 379-07317 238-07317 239-07317 599-07327 250 - - 378-07327 379-07327 238-07327 239-07327 599-07313 125 5 (125) 485 - - 378-07313 379-07313 238-07313 239-07313 599-07323 250 - - 378-07323 379-07323 238-07323 239-07323 599-07318 125 595 - - 378-07318 379-07318 238-07318 239-07318 599-07328 250 - - 378-07328 379-07328 238-07328 239-07328 599-07314 125 6 (150) 650 - - 378-07314 379-07314 238-07314 239-07314 599-07324 250 - - 378-07324 379-07324 238-07324 239-07324 599-07319 125 860 - - 378-07319 379-07319 238-07319 239-07319 599-07329 250 - - 378-07329 379-07329 238-07329 239-07329 Valves shall be pressure independent between a differential pressure of ≤5 to 90 psi for low-flow valves and new 599-0733X valves, or ≤10 to 90 psi for high-flow valves. Length of stroke shall be consistent and independent of flow setting. Next >