CE1N1992en 2018-03-06 Building Technologies 1 992 Setpoint Adjuster, activeBSG61 Active, infinitely adjustable setpoint adjuster for setting or limiting a setpoint or positioning signal. Functions There are 4 functions to choose from: Maximum limitation: The BSG61 operates as a priority selector. It com- pares the setpoint with the Uin signal received and selects the lower of the 2 signals. U out 0 10 [V] 010050 % 1 9 9 2 D 0 2 U in Minimum limitation: The BSG61 operates as a priority selector. It com- pares the setpoint with the Uin signal received and selects the higher of the 2 signals. U out 0 10 [V] 0100 % 1 9 9 2 D 0 3 U in 50 Positioning transmitter: The BSG61 transmits the set value directly to the controlling element. Setpoint adjuster: The BSG61 transmits the set value directly to the connected controller. U out 0 10 5 [V] 010050 % 1 9 9 2 D 0 12/4 SiemensSetpoint Adjuster, active BSG61CE1N1992en Building Technologies2018-03-06 Ordering When ordering, please give quantity, name and type reference. Example:2 setpoint adjusters BSG61 Mechanical design Multisectional plastic housing with: - Printed circuit board carrying the potentiometer and the 4 connection terminals - Mounting plate with 3 adjustable end-stop pins for mechanical limitation of the setting range - Setting knob - Scale (exchangeable) - Transparent cover plate Accessories The BSG61 can be used with a number of different scales. An additional set of printed scales can be ordered using type referenceBSG-Z. Each of the printed scales listed below is contained in this set twice. This means that the BSG61 can be used with the following types of printed scales: Setting rangeMeasured value 0…50 °CTemperature 0…30 °CTemperature 0…100 °CTemperature 30…130 °CTemperature 0…130 °CTemperature 0…250 °CTemperature 100…200 °CTemperature -5…+5 KTemperature shift -10…+10 KTemperature shift 0…20 g/kgAir humidity 0…100 %Position 0…0.1 barDifferential pressure, liquids 0…0.2 barDifferential pressure, liquids 0…0.5 barDifferential pressure, liquids 0…1 barDifferential pressure, liquids 0…2 barDifferential pressure, liquids 0…4 barDifferential pressure, liquids 0…5 barDifferential pressure, liquids -1…+9 barDifferential pressure, liquids 0…10 barDifferential pressure, liquids 0…16 barDifferential pressure, liquids 0…20 barDifferential pressure, liquids -1…24 barDifferential pressure, liquids 0…25 barDifferential pressure, liquids 0…40 barDifferential pressure, liquids 0…20 PaDifferential pressure, gases -50…50 PaDifferential pressure, gases 0…100 PaDifferential pressure, gases 0…200 PaDifferential pressure, gases3/4 SiemensSetpoint Adjuster, active BSG61CE1N1992en Building Technologies2018-03-06 Setting rangeMeasured variable 0…250 PaDifferential pressure, gases 0…300 PaDifferential pressure, gases 0…500 PaDifferential pressure, gases 0…1000 PaDifferential pressure, gases 0…1500 PaDifferential pressure, gases 0…2500 PaDifferential pressure, gases 0…3000 PaDifferential pressure, gases Blank scale Installation notes The BSG61 setpoint adjusters are suited for mounting in a control panel front, control desk or on a concealed conduit box (on the cover plate). Commissioning notes FunctionDip Switch (1-2-3) * Maximum limitationOFF-OFF-ON Minimum limitationON-OFF-OFF Position transmitter / setpoint adjuster (factory setting) OFF-ON-OFF *) The positioning of DIP switch in right picture presents OFF-OFF-OFF. Do not refer to the silk printing on PCB. Disposal The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage. ∑ Dispose of the device through channels provided for this purpose. ∑ Comply with all local and currently applicable laws and regulations. Technical data Operating voltage Max. voltage tolerance Safety extra low-voltage SELV to Power consumption AC 24 V, 50…60 Hz or DC 15…24 V at AC ± 20 %, at DC + 35 %/ –10 % EN 60 730-1 0.3 W Materials Cover and mounting base Setting knob Polycarbonate Polycarbonate / ASA Color Cover plate Setting knob transparent RAL 9003 (signal-white) Operation Climatic conditions Temperature (housing) Humidity (housing) To IEC 60721-3-3 class 3K5 -5…+55 °C 5…95 % r. h. Transport Climatic conditions to IEC 60721-3-2 class 2K3 Mounting Position of function selector S1 General unit data Environmental conditions4/4 SiemensSetpoint Adjuster, active BSG61CE1N1992en Building Technologies2018-03-06 Temperature Humidity Mechanical environmental conditions -25…+70 °C <95 % r. h. class 2M2 EU Conformity (CE)CE1T1992xx *) Safety class Degree of protection (built-in) III to EN 60 730-1 IP42 to EN 60 529 The product environmental declaration CE1E1992 *) contains data on environmentally com- patible product design and assessments (RoHS compliance, materials composition, packag- ing, environmental benefit, disposal). Input voltage Input resistance DC 0…10 V 100 kOhm ± 5 % Output signal Output current DC 0 ...10 V I Source 1.0 mA I Sink 1.5 mA Screw terminals for a cross- sectional area ofmax. 2.5 mm 2 Between BSG61 and controller 0.25 mm 2 copper 0.50 mm 2 copper 1.0 mm 2 copper 40 m 75 m 110 m Incl. package0.06 kg *) The documents can be downloaded fromhttp://siemens.com/bt/download. Connection terminals 1 2 3 4 GL/G+ GN/G? out in 1992Z02 AC/ DC supply Output to the controlling element or controller Input for limit functions Dimensions 1991M01 48 15 31 4 8 Drilling template 14 14 ø 7ø 3,5ø 3,5 Norms and standards Environmental Compatibility Input Output Electrical connection Max. cable lengths Weight Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd 2001-2018 Technical specifications and availability subject to change without notice.Next >