599 Series Zone Valves Submittal Sheet Document No. 154-034 February 9, 2018 2-Way, 3-Way Zone Valve Electric and Thermic Actuators Siemens Industry, Inc. Description The 599 Series Zone Valves work with any SFA/P Series or SSA/P Series electric actuator, or with the STA/P73U Series thermic actuator (See Table 5). The actuators accept one of either 24 Vac or 120 Vac power supplies signal to provide two-position, three-position or 0 to 10 Vdc control. Typical applications include hot or chilled water for zones with radiators; floor heating via manifolds; fan coil units; cooling ceilings (Zone Valves); wall-mounted boilers (zone valves); and VAV applications. Features Zone valves have a direct-coupled universal bonnet. SF and SSA/P actuators are UL listed. Actuators have a direct- coupled installation; are hand-tightened without tools, provide manual override and visual position indication. Product Numbers Use the product numbers in the tables to order the valve and the actuator assembled together. The product number consists of a 3-digit prefix code, a hyphen, and a 5-digit suffix code. The prefix specifies an actuator. The suffix specifies the valve body. Figure 1. Preferred Mounting Position For the SFA/P Series or SSA/P Series Electric Actuator. Table 1. Product Numbers: Electric Actuator/2-Way Zone Valve Assemblies. C o n n e c t i o n Line Size Flow Rate Valve Body 120 Vac 24 Vac Fail Safe (SR)Fail Safe (SR)Fail-in-Place 2-Position2-Position3-Position0 to 10 Vdc Modulating Normally Closed Normally Open Normally Closed Normally Open Normally Closed Normally Closed Normally Open Inch Mm Cv Kvs SFA11USFP11USFA71USFP71USSA81USSA61USSP61U Actuator Code 240 Actuator Code 241 Actuator Code 242 Actuator Code 243 Actuator Code 244 Actuator Code 245 Actuator Code 248 N P T .50151.0 .85 599-00210240-00210241-00210242-00210243-00210244-00210245-00210248-00210 .50152.5 2.0 599-00211240-00211241-00211242-00211243-00211244-00211245-00211248-00211 .50154.0 3.4 599-00214240-00214241-00214242-00214243-00214244-00214245-00214248-00214 .75204.1 3.5 599-00212240-00212241-00212242-00212243-00212244-00212245-00212248-00212 1.00257.0 6.0 599-00213240-00213241-00213242-00213243-00213244-00213245-00213248-00213 S w e a t .50151.0 .85 599-00510240-00510241-00510242-00510243-00510244-00510245-00510248-00510 .50152.5 2.0 599-00511240-00511241-00511242-00511243-00511244-00511245-00511248-00511 .50154.0 3.4 599-00514240-00514241-00514242-00514243-00514244-00514245-00514248-00514 .75204.1 3.5 599-00512240-00512241-00512242-00512243-00512244-00512245-00512248-00512 1.00257.0 6.0 599-00513240-00513241-00513242-00513243-00513244-00513245-00513248-00513 NOTE:For more information, seeTechnical Instructions (155-320P25, 155-321P25, and 155-710). 240-00211 3-Digit Prefix Code for Actuator 5-Digit Valve Body Suffix CodeSubmittal Sheet599 Series Zone Valves 2-Way, 3-Way; Electric and Thermic Actuators Document No. 154-034 February 9, 2018 Page 2Siemens Industry, Inc. Table 2. Product Numbers: Electric Actuator/3-Way Zone Valve Assemblies. C o n n e c t i o n Line Size Flow Rate ABËA Valve Body 120 Vac24 Vac 2-Position2-Position3-Position0 to 10 Vdc Modulating Fail AB ► B Fail AB ► A Fail AB ► B Fail AB ► A Fail-In-PlaceFail-In Place Inch Mm Cv Kvs SFA11USFP11USFA71USFP71USSA81USSA61USSP61U Actuator Code 240 Actuator Code 241 Actuator Code 242 Actuator Code 243 Actuator Code 244 Actuator Code 245 Actuator Code 248 N P T .5015 1.0 .85 599-00230 240-00230241-00230242-00230243-00230244-00230245-00230248-00230 .5015 2.5 2.0 599-00231 240-00231241-00231242-00231243-00231244-00231245-00231248-00231 .5015 4.0 3.4 599-00234 240-00234241-00234242-00234243-00234244-00234245-00234248-00234 .7520 4.1 3.5 599-00232 240-00232241-00232242-00232243-00232244-00232245-00232248-00232 1.00 25 7.0 6.0 599-00233 240-00233241-00233242-00233243-00233244-00233245-00233248-00233 S w e a t .5015 1.0 .85 599-00530 240-00530241-00530242-00530243-00530244-00530245-00530248-00530 .5015 2.5 2.0 599-00531 240-00531241-00531242-00531243-00531244-00531245-00531248-00531 .5015 4.0 3.4 599-00534 240-00534241-00534242-00534243-00534244-00534245-00534248-00534 .7520 4.1 3.5 599-00532 240-00532241-00532242-00532243-00532244-00532245-00532248-00532 1.00 25 7.0 6.0 599-00533 240-00533241-00533242-00533243-00533244-00533245-00533248-00533 NOTE:For more information, seeTechnical Instructions (155-320P25, 155-321P25 and 155-710). Valve Specifications Line size: 1/2-inch to 1-inch (15 mm to 25 mm) Action: 2-way NO/NC determined by actuator 3-way diverting (mixing, limited application) Valve body rating: ANSI Class 125 Leakage rate: ANSI Class III Close off ratings: According to ANSI/FCI 70-2 Medium temperature range: 34°F to 230°F (1°C to 110°C) Flow characteristic: Linear Electric Actuator SFA/P Series Specifications Control Signal: Two-position Operating voltage: 24 Vac ±20% 120 Vac ±20% Power Consumption: 9.8 VA 9.8 VA Frequency: 50/60 Hz Agency certification: UL listed to UL873 cUL certified to Canadian Standard C22.2 No. 24-93 Mounting location: NEMA 1 (interior only) Weight: 1.18 lb (0.54 kg) Dimensions inches (mm): 3.4 (85) H × 4.4 (111) W × 2.3 (58) D Figure 2. SFA/P Electric Actuator with 2-Way Valve: Assembly Service Envelope. Figure 3. SFA/P Electric Actuator with 3-Way Valve: Assembly Service Envelope.599 Series Zone Valves 2-Way, 3-Way; Electric and Thermic ActuatorsSubmittal Sheet Document Number: 154-034 February 9, 2018 Siemens Industry, Inc. Page 3 Table 3. SFA/P Electric Actuator/Valve Assembly Dimensions and Recommended Service Envelope in Inches (mm). Actuator Prefix Codes Valve Line Size Valve Centerline to Top of Actuator H1 Service Height H Width or Diameter of Actuator W1 Assembly Service Width W 2-Way 3-Way2-Way 3-Way2-Way3-Way2-Way3-Way 240 241 242 243 .50 (15) 4.38 (112) 4.38 (112) 12.38 (315) 12.38 (315) 4.38 (112) 4.38 (112) 12.38 (315) 12.38 (315) .75 (20) 1.00 (25) Electric Actuator SSA/P Series Specifications SSA81USSA/P61U Control Signal:3-Position0 to 10 Vdc Operating voltage: 24 Vac ±20% 24 Vac ±20% Power Consumption: 0.8 VA2.5 VA Frequency:50/60 Hz Agency Certification: UL873 Conforms to CE requirements, cUL conforms to Canadian Standard 22.2 No. 24-93 Mounting location: NEMA 1 (interior only) Weight:9 oz (0.25 kg) Dimensions inches: 3.26 H × 3.26 W × 1.9 D (mm)(82×83×48) Figure 4. Electric Actuator SSA/P Series with 2-Way Valve: Assembly Service Envelope. Figure 5. Electric Actuator SSA/P Series with 3-Way Valve: Assembly Service Envelope. Table 4. SSA/P Electric Actuator/Valve Assembly Dimensions and Recommended Service Envelope in Inches (mm). Actuator Prefix Codes Valve Line Size Valve Centerline to Top of Actuator H1 Service Height H Valve Centerline to Actuator Coupling C Width or Diameter of Actuator W1 Service Width W 2-Way3-Way2-Way3-Way2-Way3-Way2-Way3-Way2-Way3-Way 244 245 248 .50 (15) 4.26 (108) 4.26 (108) 12.26 (311) 12.26 (311) 1.00 (25) 1.00 (25) 3.26 (83) 3.26 (83) 11.26 (286) 11.26 (286) .75 (20) 1.00 (25)Submittal Sheet 599 Series Zone Valves 2-Way, 3-Way; Electric and Thermic Actuators Document Number 154-034 February 9, 2018 Pa ge 4Siemens Industry, Inc. Thermic Actuators: STA/P73U Series Specifications Control Signal: Two-Position Operating voltage: 24 Vac or 24 Vdc ±20% Power Consumption: Normal Operation: 2.5W Power up: 6 VA Frequency: 50/60 Hz Agency certification: Conforms to CE requirements Mounting: NEMA 3 (IP54) Weight: 0.40 lb (0.18 kg) Dimensions Inches (mm): 2.9 H × 2.6 W (74 × 65) NOTE: Actuators may be installed in any position. Figure 6. Acceptable Mounting Positions. Table 5. Product Numbers: STA/P73U Thermic Actuator/Two-way Valve Assembly V a l v e B o d y C o n n e c t i o n Line Size Flow RateValve Body 24 Vac 2-Position Normally Closed Normally Open Fail AB►B Fail AB►A Inch mm Cv Kvs STA73U STP73USTA73USTP73U Actuator Code 346 Actuator Code 347 Actuator Code 346 Actuator Code 347 2 - w a y N P T .5015 1.0 .85 599-00210 346-00210 347-00210—— .5015 2.5 2.0 599-00211 346-00211 347-00211—— .5015 4.0 3.4 599-00214 346-00214 347-00214 —— .7520 4.1 3.5 599-00212 346-00212 347-00212 —— 1.00 25 7.0 6.0 599-00213 346-00213 347-00213 —— S w e a t .5015 1.0 .85 599-00510 346-00510 347-00510 —— .5015 2.5 2.0 599-00511 346-00511 347-00511 —— .5015 4.0 3.4 599-00514 346-00514 347-00514 —— .7520 4.1 3.5 599-00512 346-00512 347-00512 —— 1.00 25 7.0 6.0 599-00513 346-00513 347-00513 —— 3 - W a y N P T .5015 1.0 .85 599-00230——346-00230347-00230 .5015 2.5 2.0 599-00231 —— 346-00231347-00231 .5015 4.0 3.4 599-00234——346-00234347-00234 .7520 4.1 3.5 599-00232 —— 346-00232347-00232 1.00 25 7.0 6.0 599-00233 —— 346-00233347-00233 S w e a t .5025 1.0 .85 599-00530 —— 346-00530347-00530 .5015 2.5 2.0 599-00531 —— 346-00531347-00531 .5015 4.0 3.4 599-00534 —— 346-00534347-00534 .7520 4.1 3.5 599-00532 —— 346-00532347-00532 1.00 25 7.0 6.0 599-00533 —— 346-00533347-00533 NOTE: For more information, see Technical Instructions (155-320P25 and 155-780).599 Series Zone Valves 2-Way, 3-Way; Electric and Thermic ActuatorsSubmittal Sheet Document Number: 154-034 February 9, 2018 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. © 2018 Siemens Industry, Inc. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 USA + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them toSBT_technical.editor.us.sbt@siemens.com Document No. 154-034 Printed in the USA Page 5 Dimensions Figure7. Thermic Actuator: 2-Way Valve Assembly Service Envelope. Figure8. Thermic Actuator: 3-Way Valve Assembly Service Envelope. Table 6. Thermic Actuator STA/P Series Dimensions and Recommended Service Envelope in Inches (mm). Actuator Prefix Codes Valve Line Size Inches (mm) Valve Centerline to Top of Actuator H 1 Service Height H Valve Centerline to Actuator Coupling C Width or Diameter of Actuator W 1 Service Width W 2-Way3-Way2-Way3-Way2-Way3-Way2-Way3-Way2-Way3-Way 346 347 .50 (15) 3.90 (99) 3.90 (99) 8.20 (200) 8.20 (200) 1.00 (25) 1.00 (25) 1.75 (44) 1.75 (44) 9.86 (251) 9.86 (251) .75 (20) 1.00 (25) Disposal The actuators are considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage. • Dispose of the actuators through channels provided for this purpose. • Comply with all local and currently applicable laws and regulations. Do not dispose of valves as household waste. • Special handling of individual components may be mandated by law or make ecological sense. • Observe all local and currently applicable laws and regulations.Next >