Data sheet3RT1054-6AF36 Power contactor, AC-3 115 A, 55 kW / 400 V AC (50-60 Hz) / DC operation 110-127 V UC Auxiliary contacts 2 NO + 2 NC 3-pole, Size S6 Busbar connections Drive: conventional screw terminal product brand nameSIRIUS product designationPower contactor product type designation3RT1 General technical data size of contactorS6 product extension ● function module for communication No ● auxiliary switch Yes power loss [W] for rated value of the current ● at AC in hot operating state 21 W ● at AC in hot operating state per pole 7 W power loss [W] for rated value of the current without load current share typical 5.2 W surge voltage resistance ● of main circuit rated value 8 kV ● of auxiliary circuit rated value 6 kV maximum permissible voltage for safe isolation ● between coil and main contacts acc. to EN 60947-1 690 V 3RT1054-6AF36Subject to change without notice Page 1/11 12/11/2020© Copyright Siemensshock resistance at rectangular impulse ● at AC 8,5g / 5 ms, 4,2g / 10 ms ● at DC 8,5g / 5 ms, 4,2g / 10 ms shock resistance with sine pulse ● at AC 13,4g / 5 ms, 6,5g / 10 ms ● at DC 13,4g / 5 ms, 6,5g / 10 ms mechanical service life (switching cycles) ● of contactor typical 10 000 000 ● of the contactor with added electronically optimized auxiliary switch block typical 5 000 000 ● of the contactor with added auxiliary switch block typical 10 000 000 reference code acc. to IEC 81346-2Q Ambient conditions ● installation altitude at height above sea level maximum 2 000 m ambient temperature ● during operation -25 ... +60 °C ● during storage -55 ... +80 °C Main circuit number of poles for main current circuit3 number of NO contacts for main contacts3 operating voltage ● at AC-3 rated value maximum 1 000 V operational current ● at AC-1 at 400 V — at ambient temperature 40 °C rated value 160 A ● at AC-1 — up to 690 V at ambient temperature 40 °C rated value 160 A — up to 690 V at ambient temperature 60 °C rated value 140 A — up to 1000 V at ambient temperature 40 °C rated value 80 A — up to 1000 V at ambient temperature 60 °C rated value 80 A ● at AC-3 — at 400 V rated value 115 A — at 500 V rated value 115 A — at 690 V rated value 115 A — at 1000 V rated value 53 A ● at AC-4 at 400 V rated value 97 A 3RT1054-6AF36Subject to change without notice Page 2/11 12/11/2020© Copyright Siemens● at AC-5a up to 690 V rated value 140 A ● at AC-5b up to 400 V rated value 95 A ● at AC-6a — up to 230 V for current peak value n=20 rated value 115 A — up to 400 V for current peak value n=20 rated value 115 A — up to 500 V for current peak value n=20 rated value 115 A — up to 690 V for current peak value n=20 rated value 115 A — up to 1000 V for current peak value n=20 rated value 53 A ● at AC-6a — up to 230 V for current peak value n=30 rated value 98 A — up to 400 V for current peak value n=30 rated value 98 A — up to 500 V for current peak value n=30 rated value 98 A — up to 690 V for current peak value n=30 rated value 98 A — up to 1000 V for current peak value n=30 rated value 53 A minimum cross-section in main circuit ● at maximum AC-1 rated value 70 mm² operational current for approx. 200000 operating cycles at AC-4 ● at 400 V rated value 54 A ● at 690 V rated value 48 A operational current ● at 1 current path at DC-1 — at 24 V rated value 160 A — at 110 V rated value 18 A — at 220 V rated value 3.4 A — at 440 V rated value 0.8 A — at 600 V rated value 0.5 A ● with 2 current paths in series at DC-1 — at 24 V rated value 160 A — at 110 V rated value 160 A — at 220 V rated value 20 A — at 440 V rated value 3.2 A — at 600 V rated value 1.6 A 3RT1054-6AF36Subject to change without notice Page 3/11 12/11/2020© Copyright Siemens● with 3 current paths in series at DC-1 — at 24 V rated value 160 A — at 110 V rated value 160 A — at 220 V rated value 160 A — at 440 V rated value 11.5 A — at 600 V rated value 4 A operational current ● at 1 current path at DC-3 at DC-5 — at 24 V rated value 160 A — at 110 V rated value 2.5 A — at 220 V rated value 0.6 A — at 440 V rated value 0.17 A — at 600 V rated value 0.12 A ● with 2 current paths in series at DC-3 at DC-5 — at 24 V rated value 160 A — at 110 V rated value 160 A — at 220 V rated value 2.5 A — at 440 V rated value 0.65 A — at 600 V rated value 0.37 A ● with 3 current paths in series at DC-3 at DC-5 — at 24 V rated value 160 A — at 110 V rated value 160 A — at 220 V rated value 160 A — at 440 V rated value 1.4 A — at 600 V rated value 0.75 A operating power ● at AC-3 — at 230 V rated value 37 kW — at 400 V rated value 55 kW — at 500 V rated value 75 kW — at 690 V rated value 110 kW — at 1000 V rated value 75 kW operating power for approx. 200000 operating cycles at AC-4 ● at 400 V rated value 29 kW ● at 690 V rated value 48 kW operating apparent power at AC-6a ● up to 230 V for current peak value n=20 rated value 40 000 kV·A ● up to 400 V for current peak value n=20 rated value 80 000 V·A 3RT1054-6AF36Subject to change without notice Page 4/11 12/11/2020© Copyright Siemens● up to 500 V for current peak value n=20 rated value 100 000 V·A ● up to 690 V for current peak value n=20 rated value 130 000 V·A ● up to 1000 V for current peak value n=20 rated value 90 000 V·A operating apparent power at AC-6a ● up to 230 V for current peak value n=30 rated value 30 000 V·A ● up to 400 V for current peak value n=30 rated value 60 000 V·A ● up to 500 V for current peak value n=30 rated value 80 000 V·A ● up to 690 V for current peak value n=30 rated value 110 000 V·A ● up to 1000 V for current peak value n=30 rated value 90 000 V·A short-time withstand current in cold operating state up to 40 °C ● limited to 1 s switching at zero current maximum 2 565 A; Use minimum cross-section acc. to AC-1 rated value ● limited to 5 s switching at zero current maximum 1 654 A; Use minimum cross-section acc. to AC-1 rated value ● limited to 10 s switching at zero current maximum 1 170 A; Use minimum cross-section acc. to AC-1 rated value ● limited to 30 s switching at zero current maximum 729 A; Use minimum cross-section acc. to AC-1 rated value ● limited to 60 s switching at zero current maximum 572 A; Use minimum cross-section acc. to AC-1 rated value no-load switching frequency ● at AC 2 000 1/h ● at DC 2 000 1/h operating frequency ● at AC-1 maximum 800 1/h ● at AC-2 maximum 400 1/h ● at AC-3 maximum 1 000 1/h ● at AC-4 maximum 130 1/h Control circuit/ Control type of voltage of the control supply voltageAC/DC control supply voltage at AC ● at 50 Hz rated value 110 ... 127 V ● at 60 Hz rated value 110 ... 127 V control supply voltage at DC ● rated value 110 ... 127 V 3RT1054-6AF36Subject to change without notice Page 5/11 12/11/2020© Copyright Siemensoperating range factor control supply voltage rated value of magnet coil at DC ● initial value 0.8 ● full-scale value 1.1 operating range factor control supply voltage rated value of magnet coil at AC ● at 50 Hz 0.8 ... 1.1 ● at 60 Hz 0.8 ... 1.1 design of the surge suppressorwith varistor apparent pick-up power of magnet coil at AC ● at 50 Hz 300 V·A inductive power factor with closing power of the coil ● at 50 Hz 0.9 apparent holding power of magnet coil at AC ● at 50 Hz 5.8 V·A inductive power factor with the holding power of the coil ● at 50 Hz 0.8 closing power of magnet coil at DC360 W holding power of magnet coil at DC5.2 W closing delay ● at AC 20 ... 95 ms ● at DC 20 ... 95 ms opening delay ● at AC 40 ... 60 ms ● at DC 40 ... 60 ms arcing time10 ... 15 ms control version of the switch operating mechanismStandard A1 - A2 Auxiliary circuit number of NC contacts for auxiliary contacts ● instantaneous contact 2 number of NO contacts for auxiliary contacts ● instantaneous contact 2 operational current at AC-12 maximum10 A operational current at AC-15 ● at 230 V rated value 6 A ● at 400 V rated value 3 A ● at 500 V rated value 2 A ● at 690 V rated value 1 A operational current at DC-12 ● at 24 V rated value 10 A ● at 48 V rated value 6 A 3RT1054-6AF36Subject to change without notice Page 6/11 12/11/2020© Copyright Siemens● at 60 V rated value 6 A ● at 110 V rated value 3 A ● at 125 V rated value 2 A ● at 220 V rated value 1 A ● at 600 V rated value 0.15 A operational current at DC-13 ● at 24 V rated value 10 A ● at 48 V rated value 2 A ● at 60 V rated value 2 A ● at 110 V rated value 1 A ● at 125 V rated value 0.9 A ● at 220 V rated value 0.3 A ● at 600 V rated value 0.1 A contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA) UL/CSA ratings full-load current (FLA) for 3-phase AC motor ● at 480 V rated value 124 A ● at 600 V rated value 125 A yielded mechanical performance [hp] ● for single-phase AC motor — at 230 V rated value 25 hp ● for 3-phase AC motor — at 200/208 V rated value 40 hp — at 220/230 V rated value 50 hp — at 460/480 V rated value 100 hp — at 575/600 V rated value 125 hp contact rating of auxiliary contacts according to ULA600 / Q600 Short-circuit protection design of the fuse link ● for short-circuit protection of the main circuit — with type of coordination 1 required gG: 355 A (690 V, 100 kA) — with type of assignment 2 required gG: 250 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 250 A (415 V, 50 kA) ● for short-circuit protection of the auxiliary switch required gG: 10 A (500 V, 1 kA) Installation/ mounting/ dimensions mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back fastening methodscrew fixing ● side-by-side mounting Yes height172 mm 3RT1054-6AF36Subject to change without notice Page 7/11 12/11/2020© Copyright Siemenswidth120 mm depth170 mm required spacing ● with side-by-side mounting — forwards 20 mm — upwards 10 mm — downwards 10 mm — at the side 0 mm ● for grounded parts — forwards 20 mm — upwards 10 mm — at the side 10 mm — downwards 10 mm ● for live parts — forwards 20 mm — upwards 10 mm — downwards 10 mm — at the side 10 mm Connections/ Terminals width of connection bar17 mm thickness of connection bar3 mm diameter of holes9 mm number of holes1 type of electrical connection ● for main current circuit Connection bar ● for auxiliary and control circuit screw-type terminals ● at contactor for auxiliary contacts Screw-type terminals ● of magnet coil Screw-type terminals type of connectable conductor cross-sections ● at AWG cables for main contacts 4 ... 250 kcmil connectable conductor cross-section for main contacts ● stranded 25 ... 120 mm² connectable conductor cross-section for auxiliary contacts ● solid or stranded 0.5 ... 4 mm² ● finely stranded with core end processing 0.5 ... 2.5 mm² ● type of connectable conductor cross-sections for auxiliary contacts — solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) — solid or stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²) — finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) 3RT1054-6AF36Subject to change without notice Page 8/11 12/11/2020© Copyright Siemens● type of connectable conductor cross-sections at AWG cables for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14), 1x 12 AWG number as coded connectable conductor cross section ● for auxiliary contacts 18 ... 14 Safety related data B10 value ● with high demand rate acc. to SN 31920 1 000 000 product function ● mirror contact acc. to IEC 60947-4-1 Yes ● positively driven operation acc. to IEC 60947-5- 1 No suitability for use safety-related switching OFFYes Certificates/ approvals General Product ApprovalEMC KC Declaration of ConformityTest CertificatesMarine / Ship- ping MiscellaneousType Test Certific- ates/Test Report Special Test Certi- ficate Miscellaneous Marine / ShippingotherRailway ConfirmationMiscellaneousSpecial Test Certi- ficate Further information Information- and Downloadcenter (Catalogs, Brochures,…) https://www.siemens.com/ic10 Industry Mall (Online ordering system) https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT1054-6AF36 Cax online generator http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT1054-6AF36 Service&Support (Manuals, Certificates, Characteristics, FAQs,...) https://support.industry.siemens.com/cs/ww/en/ps/3RT1054-6AF36 Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT1054-6AF36&lang=en 3RT1054-6AF36Subject to change without notice Page 9/ 12/11/2020© Copyright SiemensNext >