WIRING EXAMPLESINSTALLATION INSTRUCTIONSINSTALLATION1. Determine mounting location for the sensor near the conductor to be monitored. The sensor should be located AT LEAST 1/2” from any uninsulated conductor.2. Drill a single 3/32” pilot hole for mounting the sensor; ensure no drill shavings are present in enclosure.3. Thread INSULATED CONDUCTOR ONLY, 600VAC MAX to be monitored through the iris of the sensor.4. Reconnect the conductor and torque appropriately.5. Screw mount the sensor to the enclosure.6. Wire the output of the sensor to a control panel digital input loop not to exceed 30VAC/DC wetting voltage. Tighten terminals to 3.5 in-lb.Disconnect, lock out and tag out all power supplies during installation senvainc.com 1-866-660-8864 (F)1-503-296-2529 9290 SW Nimbus Ave. Beaverton Oregon 97008C-1200, Go/NoMini Solid-CoreDigital OutputFailure to follow these instructions will result in death or serious injury.• Follow ALL requirements in NFPA 70E for safe work practices and for Personal Protective Equipment (USA) and other appli-cable local codes when installing this product• Only qualified electrical personnel should install this product. • Read, understand, and follow all instructions thoroughly• Install only on insulated conductors• Lock out and tag out all power sources prior to installation. Use properly rated voltage sensing instrument to determine no voltage is present Failure to follow these instructions could result in death or serious injury.• Equipment monitored/operated by this device may start without warning. Keep clear of apparatus at all timesIMPORTANT WARNINGS• Only qualified trade installers should install this product• This product is not intended for life-safety applications• Do not install in hazardous or classified locations• The installer is responsible for all applicable codes• This product must be installed in a suitable electrical enclosureAutomated equipment may start without warningDANGERWARNINGHazard of electrical shock, explosion, and arc flashWARNING!Status Output0.5A @ 30VAC/DCNormally OpenV+DICONTROLLER(SINKING)24VACDIV+DI(SOURCING)(AC)ALTERNATECONTROLLER ARRANGEMENTSINSULATED PRIMARYAC CONDUCTOR600VAC MAXV+DIDIDIVACGNDNOTE: Device is NOT polarity sensitive.vPRODUCT APPLICATION LIMITATION:Senva products are not designed for life or safety applications. Senva products are not intended for use in critical applications such as nuclear facilities, human implantable device or life support. Senva is not liable, in whole or in part, for any claims or damages arising from such uses.3PZSTECH TIPSOn low current loads, wrap sensor multiple times to increase sensitivityCAUTION: Do not exceed sensor maximum current. The current detected by the sensor will increase 1X with each wrap.To monitor loads greater than the current sensor maximum ratingUse a properly rated 5A CT as shown below CAUTION!5A CTs can present hazardous voltages. Install CTs in accordance with manufacturers instructions. Terminate the CT secondary wiring before energizing primary conductor.Part NumberC-1200Amperage Range0.25A (on)-50A (50A Max.)Output TypeNO, solid-state FETOutput Rating1.0A@30VAC/DC Max.Temperature Rating-15~60 ° CInsulation Class600V RMS. For use on insulated conductors only! Use minimum 75 ° C insulated conductorSensor PowerInducedFrequency Range50/60HzDimensions ( LxWxH)1.78” x 1.32” x 0.66”Sensor Aperture0.30”OPERATIONThe C-1200 output changes state whenever current above 0.25A is present. This provides “go/no” status on loads that are not subject to mechanical failures.Typical on/off status applications include: z Lighting circuits z Heater elements z Direct drive fans (e.g. exhaust fans) z Process motorsDIMENSIONS50-250AMPS250:5A CT1-5AMPSMonitored Load Sensor MinimumCurrent 0.25ASensorOutput EnergizedOFFRUN1.781.310.66O0.300.750.47O0.120.88TroubleshootingSymptomCausesRemedySensor output does not change stateAmperage is below sensor minimum thresholdWrap monitored conductor turns through sensor. See Tech TipTesting with ohm meter yields incorrect resultsSolid state output may show approx. 1 ohm or less.Incorrect control wiringEnsure control loop voltage is present 1. Maximum surrounding air ambient, 60 ° C. For use in Pollution Degree 2 Environment.152-0300-0ANext >