USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com schneider-electric.com | 1 Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk Product Description The SpaceLogic SLP Series of air quality sensors for living space is a flexible multisensor platform for use with BAS con- trollers designed to accept BACnet or Modbus outputs. Hous- ings are available in Medium matte white and Optimum faces available in black and white. All housing types are available with three user interface options: touchscreen, LCD with three buttons and blank. CO 2 and temperature sensors are included with all SLP Series air quality sensors. Models with VOC sen- sors and relative humidity sensors are also available. Features • Medium matte white housing or optimum glass panel housing available in white or black • Field calibratable non-dispersive infrared CO 2 sensor • Replaceable RH element available in 1% & 2% with NIST certificate • VOC sensor available • Temperature output on all models • 61 mm (2.4”) backlit color touchscreen and LCD, three button display options available - Digital temperature indication (0.1° display resolution of °F or °C - Digital humidity indication (0.1% RH display resolution) - Digital CO 2 indication (1 ppm display resolution) - Selectable temp, RH and fan speed setpoint - Configurable screen/button lock and display timeout - Override • Selectable BACnet MSTP and Modbus outputs via RS-485 • 18-24 AWG screw terminals Note: A subset of models shown. SpaceLogic Sensors Air Quality Sensors – BACnet and Modbus Available Products Matrix Replaceable RH Elements SLP S = Medium white matte housing W = Optimum white housing B = Optimum black housing T = Color touchscreen L = 3-button LCD display X = None C = NDIR CO 2 CV = NDIR CO 2 / VOC 2 = 2% X = None HousingUser InterfaceCO 2 SensorRH Sensor** ** RH elements are replaceable. ModelRH AccuracyCalibration CertificateDescription SLXRHS1N ±1%XReplaceable RH sensor, 1% with NIST certification SLXRHS2N±2%XReplaceable RH sensor, 2% with NIST certification SLXRHS2X ±2%Replaceable RH sensor, 2% Example: SLPC2TS schneider-electric.com | 2 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Specifications Operating Environment Input powerClass 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz Protocol outputBACnet or Modbus via RS-485, selectable Operating temp. range 0 to 50 °C (32 to 122 °F) Operating hu- midity range 0 to 95% RH non-condensing Housing material High impact ABS plastic IP ratingIP 30 CO 2 Sensor Sensor typeNon-dispersive infrared (NDIR), diffusion sampling Output range0 to 2000 ppm Accuracy±30 ppm ±3% of measured value Repeatability±20 ppm ±1% of measured value Response time<60 seconds for 90% step change VOC Sensor Sensor typeSolid state Output range0 to 100% AQI for VOC Accuracy±15% of measured value Output scale0 to 1,000 ppb of total VOC (TVOC) AQI table* Level Ventilation Recommendation TVOC (ppb) >61% Greatly increased >610 20 to 61% Significantly increased200 to 610 10 to 20% Slightly increased 100 to 200 5 to 10% Average50 to 100 0 to 5% Target value0 to 50 RH Sensor HS sensorThin-film capacitive, replaceable Accuracy±2% from 10 to 80% RH @ 25°C (77 °F) Hysteresis1.5% typical LinearityIncluded in accuracy specification Stability±1% @ 20°C (68 °F) annually for 2 years Output range0 to 100% RH Temperature coefficient ±0.1% RH/°C above or below 25 °C (77 °F) typical Temperature Sensor Sensor typeSolid state, integrated circuit Accuracy ± 0.2 °C ( ± 0.4 °F) typical Resolution0.1 °C (0.1 °F) Range0 to 50 °C (32 to 122 °F) Dimensions mm (in.) Optimum Housing Medium Housing 115 (4.5) 85 (3.3) 23.7 (0.9) 115 (4.5) 85 (3.3) 24 (0.9) * Air Quality Index for VOC aligns with TVOC levels for IAQ as specified by the WHO (World Health Organization). Display Models Touchscreen 61 mm (2.4 in), color, backlit, capacitive, 240x300px Setpoint: Temperature, humidity or fan speed selectable Timeout override: Display timeout Lockout override: Touchscreen/button lockout LCD 52mm (2.05 in), segmented with 3 buttons Setpoint: Temperature, humidity or fan speed selectable Timeout override: Display timeout Lockout override: Touchscreen/button lockout Setpoints Temperature setpoint Scale: 0 to 50 °C (32 to 122 °F) max., adjustable span Humidity setpoint Scale: 0 to 100% RH Fan speed setpoint Off, Low, Med., High Override Override button Display models feature a momentary override button Wiring Terminals Terminal blocks Screw terminals, 18-24 AWG Screw terminal torque 0.2 N-m (2.0 in-lbF) max. Regulatory Information Agency approvals UL 916, European conformance CE: EN61000-6-2 EN61000-6-3 EN61000 Series - industrial immunity EN 61326-1 FCC Part 15 Class B, REACH, RoHS, Green Premium, RCM (Australia), ICES-003 (Canada), EAC (Russia) schneider-electric.com | 3 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Installation 1. Remove the cover from the base at the bottom of the device. 2. Position the sensor base vertically on the wall 1.35 m (4.5 ft.) above the floor with the “UP” arrow facing upward. Lo- cate away from windows, vents and other sources of draft. If possible, do not mount on an external wall, as this may cause inaccurate temperature readings. 3. Pull 18 or 22 AWG cable(s) through the hole in the back- plate. 4. Mount the backplate onto the wall using the screws provided. Six screw holes available. Use a minimum of two for secure mounting. 5. Connect the wires to the screw terminals. Do not over-tight- en the screws. 54321 RS-485 (+) RS-485 (-) POWER SUPPLY 20-30 Vdc, 24 Vac CONTROL SYSTEM COMMON COMMON + - POWER (+24) 6. Configure the device. Address Configuration: Each device on a single network must have a unique ad- dress. Set the DIP switch labeled “ADDRESS” to assign a unique address before the device is connected to the net- work. If an address is selected that conflicts with another device, neither device will be able to communicate. Address the device as any whole number between and including 1 to 127. Note that zero is not a valid address for Modbus; zero is a valid address for BACnet. Positions 1 through 7 of the “ADDRESS” DIP switch designate the ad- dress. Position 8 toggles between the Modbus and BACnet communication protocols, as shown in the diagram below. This is the left bank of DIP switches on the sensor. LSBMSB 1 24 8 1632 64 DecimalValues Modbus/BACnet Toggle On = Modbus O = BACnet Binary Address schneider-electric.com | 4 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com To set an address using the DIP switch, simply add the values of any switches that are in the ON position. For example, an address of 73 is set as shown in the diagram below. 73 = LSBMSB 1248163264 Position number 1 has an ON value of 1, position number 4 has an ON value of 8 and position number 7 has an ON value of 64 (1 + 8 + 64 = 73). Communications Configuration: See the Product Diagram section for the location of the DIP switch labeled “CONFIG”. The following parameters are configurable: • Parity (Modbus only): None, Odd, None1 (one stop bit), Even • Baud rate: 9600, 19200, 38400, 57600 (Modbus), 76800 (BACnet) oo ono oon onon None Odd None1 Even 9600 19200 38400 57600 (Modbus) 76800 (BACnet) oo ono oon onon Parity (Modbus Only) Baud DIP Switches 5 to 8 are Unused Example: No Parity, 19200 Baud 12345678 offoffonoffoffoffoffoff None19200 BaudUnused Modbus Point Map Function Codes: Function CodeFunction 03Read holding (RW) registers 04Read input (RO) registers 06Write single register* 16Write multiple registers 01Read coils 05Write single coil 15Write multiple coils * Not supported. All of these values correspond to BACnet objects with the same name. See the BACnet Conformance Statement for their definitions. Note that an attempt to write to “read only” holding regis- ters will give an error and the entire write command will not be executed even if writing to read/write locations were also requested. Exception code 2 is given in this case. “Preserved” means the values is maintained through power outages. 32-Bit Input Registers (Read Only): RegisterDescription 1Temperature reading in IEEE 32-bit floating point 3Humidity reading in IEEE 32-bit floating point 5CO 2 reading in IEEE 32-bit floating point 7VOC reading in IEEE 32-bit floating point 9Model (numeric representation of ASCII characters) 42 Serial number (numeric representation of ASCII characters) 32-Bit Holding Registers (Read/Write): RegisterDescription 1Temperature setpoint 3Humidity setpoint 5Screen color set 7Device name 40Fan speed Note: All holding registers are preserved during power outages. schneider-electric.com | 5 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Coils (Read/Write): RegisterDescription 2*CO 2 stoplight 3*Touch button disable 4*Invoke CO 2 calibration 5*Temperature (°C) 6Occupancy override 7*Touch timeout 8*Display shows humidity 9*Display shows CO 2 level 10*Display shows VOC level 11Set 400 ppm as CO 2 baseline * Preserved during power outages. BACnet Descriptions Note: In the tables below, all properties are read-only unless otherwise noted. “Preserved” means the value is maintained through power outages. Present_Value Range Restrictions: Object NameMinimum ValueMaximum Value DEV - Object_ Name 1 Character65 Characters Temperature Setpoint Min_Pres_Value Max_Pres_Value Min_Pres_Value 0 Min_Pres_Value +1 Max_Pres_Value Max_Pres_Value -1 50 Humidity Setpoint Min_Pres_Value Max_Pres_Value Min_Pres_Value 0 Min_Pres_Value +1 Max_Pres_Value Max_Pres_Value -1 100 Screen Color Set Fan Speed 14 Device_Instance04,194,302 Standard Object Types Supported: Object Type Supported Optional Properties Writable Properties Analog Input - AIReliabilityNone Analog Value - AVMin_Pres_Value Max_Pres_Value Min_Pres_Value Max_Pres_Value Present_Value Binary Value - BVNonePresent Value Multistate Value - MSVNonePresent Value Device - DEVMax Info Frames Max_Master APDU_Timeout Max_Master Object_Name Objects Table: Object Name Object IdentifierObject Property Room Temperature AI 1Temperature in Room Room HumidityAI 2Humidity in Room CO2 SensorAI 3CO 2 Concentration VOC SensorAI 4VOC Level Temperature Setpoint* AV 1Setpoint Value for Temperature Humidity Setpoint* AV2Setpoint Value for Humdidity CO2 Stoplight*BV 1ACTIVE enables CO 2 Stoplight INACTIVE disables CO2 Stoplight Touch Disable*BV2ACTIVE disables Touch Re- sponse INACTIVE enables Touch Response CO2 ABC Cal*BV3ACTIVE enables ABC Calibra- tion INACTIVE disables ABC Cali- bration Temperature Units* BV4ACTIVE displays temperature in Fahrenhiet INACTIVE displays temperature in Celsius Occupancy Override BV5ACTIVE means room is not occupied INACTIVE means room is occupied Screen Timeout*BV 6ACTIVE enables Screen Timeout INACTIVE disables Screen Timeout Display Humidity*BV7ACTIVE displays humidity on Screen INACTIVE removes humdity from Screen Display CO2*BV8ACTIVE displays CO 2 level on Screen INACTIVE removes CO 2 level from Screen Display VOC*BV9ACTIVE displays VOC level on Screen INACTIVE removes VOC level from Screen CO2 FRC 400BV10ACTIVE sets 400 ppm as CO 2 baseline INACTIVE after Present_Value is read Screen Color Set* MSV 1Selection for Screen Color Theme Fan Speed*MSV 2Fan Speed Selection * Preserved during power outages. schneider-electric.com | 6 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Device Objects Table: Object Name Object IdentifierObject PropertyDescrip. Living Space Room Unit XXXXXXX Vendor_ID + nnn Object _Identifer (R/W) Unique value where nnn initially is the MS/TP address BACnet Protocol Implementation Conformance Statement Vendor Name: Schneider Electric Product Name: Living Space Room Unit Product Model: SLPXXXX BACnet Protocol Version : 1 BACnet Protocol Revision: 16 Product Description: Environmental Sensor BACnet Standardized Device Profile (AnnexL): BACnet Application Specific Controller (B-ASC) List All BACnet Interoperatvility Building Blocks Support- ed(Annex K): DS-RP-B, DS-WP-B, DM-DDB-B, DM-DOB-B, DM-DCC-B Data Link Layer Options: MS/TP (Clause 9), baud rates, 9600, 19200, 38400, 76800 Device Address Binding: Static Device binding is not sup- ported. Networking Options: None Character Sets supported: ISO 10646 (UTF-8) 7. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover down- ward until it latches at the bottom. 8. Install locking screw to secure cover in closed position. 9. 400 ppm baseline calibration allows the sensor to be set at 400 ppm. Push and hold the calibration button for 3 to 5 seconds. The LED will flash green. Once the button is released, calibration is complete and the LED switches off. Calibration button access hole LED Touchscreen Operation Main Screen The touchscreen user interface displays applicable sensor output values (temperature, RH, CO 2 and VOC), setpoint value, menu button and CO 2 stoplight status (if enabled). Setpoint value (temperature setpoint shown) Fahrenheit/Celsius Temperature value Menu button RH value CO 2 value VOC AQI value Menu Screen The menu screen opens when pressing the Menu button on the main screen. Integrator’s submenu, occupancy/override, Fahrenheit/Celsius, settings, setpoint submenu (temp, RH and fan) and CO 2 stoplight buttons are displayed on the menu screen. Note: RH setpoint will not appear on non-RH models. schneider-electric.com | 7 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Menu Button Functions Integrator’s Submenu Press this icon to access the Integrator’s menu. Submenu Only Submenu Only Submenu Only Submenu Only Occupied Override Button Press this icon to provide momentary signal output to the controller Signals occupied/override call to controller. Single Press Only Fahrenheit/Celsius Switch Press this icon to display either °C or °F. Settings This icon provides the ability to change the color scheme of the display. Changes units to Fahrenheit when pressed. Changes units to Celsius when pressed. Single Press Only Temp Setpoint Adjustment Click this icon to access the setpoint change menu. Humidity Setpoint Adjustment Click this icon to access the setpoint change menu. Model Device page 1 of 3 SLPSTCV2 Serial Number4E54FB0A Firmware Revision LSA_APP_REV00800 Sensor Address Protocol page 2 of 3 1 Baud Rate38400 Sensors page 3 of 3 Temperature C24.7 Humidity %100 1287CO 2 PPM 20VOC % 100% 2000 .5 23 85 65 °C 100% 2000 .5 23 °C 100% 2000 .5 23 °C 100% 2000 .5 23 °C Submenu Only Submenu Only Selected Feature is ON Feature is OFF Fan Speed Click this icon to access the fan speed menu. CO 2 Stoplight Menu Click this icon to toggle the CO 2 Stoplight feature on and off. With CO 2 Stoplight turned on, the background color of the main screen changes with CO 2 level. This provides a visual indicator of CO 2 levels to the room occupants. Green CO 2 <1000 ppm Yellow & Single Flag CO 2 = 1000 to 1500 ppm Red & Double Flag CO 2 > 1500 ppm schneider-electric.com | 8 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com LCD Display Operation Button Functions Display Icons The main screen displays sensor values for CO 2 , VOC (if equipped), RH (if equipped), temperature and Celsius/Fahren- heit. Change Values Menu Advance Change Values Alternates between CO 2 and VOC every 6 seconds Humidity Value (if equipped) Temperature Value Override Press Indicator CO 2 Value VOC Value (if equipped) Setpoint Function The Menu Advance button cycles between Temperature, RH (if equipped), Fan Speed setpoints and Celsius/Fahrenheit adjust- ment screens in order. Temperature Setpoint Adjustment Adjusts setpoint up Adjusts setpoint down Note: Numeric information will flash while in Set mode. Press the Menu Advance button After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears. RH Setpoint Adjustment Fan Speed Setpoint Adjustment Adjusts setpoint up Adjusts setpoint down Press the Menu Advance button After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears. Note: Numeric information will flash while in Set mode. Adjusts setpoint up Adjusts setpoint down Press the Menu Advance button After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears. Low Medium High Note: Fan speed scale flashes when in Set mode. Off setting is default. schneider-electric.com | 9 SpaceLogic Sensors, Air Quality Sensors – BACnet and Modbus Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207902-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com China RoHS Compliance Information Environment-Friendly Use Period (EFUP) Table 本表格依据 SJ/T11364 的 规定编制。 O: 表示 该有害物质在该部件所有均质材料中的含量均在 GB/T 26572 规定的限量要求以下。 X: 表示 该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572 规定的限量要求。 (企 业可在此处,根据实际情况对上表中打 的技 术原因进行进一步说明。) This table is made according to SJ/T 11364. O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572. X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part XOOOOO is above the limit as stipulated in GB/T 26572 Z000057-0B 部件名称 Part Name 有害物 质- Hazardous Substances 铅(Pb) 汞(Hg) 镉(Cd) 六价 铬(Cr (VI)) 多溴 联苯(PBB) 多溴二苯 醚(PBDE) 电子件 Electronic Setpoint Function (cont.) Changing Celsius and Fahrenheit Scales The Menu Advance button cycles between Temperature, RH (if equipped), Fan Speed setpoints and Celsius/Fahrenheit adjust- ment screens in order. Occupied/Override Button Press and hold the Menu Advance button for 1 second Override Press Indicator illuminates for 6 seconds. Adjusts from ºF to ºC Adjusts from ºC to ºF After adjustment, wait 6 seconds or press the Menu Advance button to return to the main screen. Note: ºF or ºC text will flash while in Set mode. Press the Menu Advance buttonNext >