USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com schneider-electric.com | 1 Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk Product Description The SpaceLogic SLA Series of air quality sensors for living space is a flexible multisensor platform for use with BAS con- trollers designed to accept 4 to 20mA, 0 to 5Vdc or 0 to 10Vdc outputs. Housings are available in Medium matte white and Op- timum faces available in black and white. All housing types are available with three user interface options: touchscreen, LCD with three buttons and blank. CO 2 and temperature sensors are included with all SLA Series air quality sensors. Models with VOC sensors and relative humidity sensors are also available. Available Products Matrix Features • Medium matte white housing or optimum glass panel housing available in white or black • Field calibratable non-dispersive infrared CO 2 sensor • Replaceable RH element available in 1% & 2% with NIST certificate • VOC sensor available • Temperature output on all models • 61 mm (2.4”) backlit color touchscreen and LCD, three button display options available - Digital temperature indication (0.1° display resolution of °F or °C - Digital humidity indication (0.1% RH display resolution) - Digital CO 2 indication (1 ppm display resolution) - Selectable temp, RH and fan speed setpoint (0-10V) - Configurable screen/button lock and display timeout - Override • Selectable 4 to 20mA, 0 to 5V and 0 to 10V analog outputs • 18-24 AWG screw terminals Note: A subset of models shown. SLA S = Medium white matte housing W = Optimum white housing B = Optimum black housing T = Color touchscreen L = 3-button LCD display X = None C = NDIR CO 2 CV = NDIR CO 2 / VOC 2 = 2% X = None HousingUser InterfaceCO 2 SensorRH Sensor** ** RH elements are replaceable. SpaceLogic Sensors Air Quality Sensors – Analog Example: SLAC2TS schneider-electric.com | 2 SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Specifications Operating Environment Input powerClass 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz Analog outputSelectable 4 to 20 mA, 0 to 5 V, 0 to 10 V Operating temp. range 0 to 50 °C (32 to 122 °F) Operating hu- midity range 0 to 95% RH non-condensing Housing material High impact ABS plastic IP ratingIP 30 CO 2 Sensor Sensor typeNon-dispersive infrared (NDIR), diffusion sampling Output range0 to 2000/5000 ppm (selectable) Accuracy±30 ppm ±3% of measured value Repeatability±20 ppm ±1% of measured value Response time<60 seconds for 90% step change VOC Sensor Sensor typeSolid state Output range0 to 100% AQI for VOC Accuracy±15% of measured value Output scale0 to 1,000 ppb of total VOC (TVOC) AQI table* Level Ventilation Recommendation TVOC (ppb) >61% Greatly increased >610 20 to 61% Significantly increased200 to 610 10 to 20% Slightly increased 100 to 200 5 to 10% Average50 to 100 0 to 5% Target value0 to 50 RH Sensor HS sensorThin-film capacitive, replaceable Accuracy±2% from 10 to 80% RH @ 25°C (77 °F) Hysteresis1.5% typical LinearityIncluded in accuracy specification Stability±1% @ 20°C (68 °F) annually for 2 years Output range0 to 100% RH Temperature coefficient ±0.1% RH/°C above or below 25 °C (77 °F) typical Temperature Sensor Sensor typeSolid state, integrated circuit Accuracy ± 0.2 °C ( ± 0.4 °F) typical Resolution0.1 °C (0.1 °F) Range0 to 50 °C (32 to 122 °F) Dimensions mm (in.) Optimum Housing Medium Housing 115 (4.5) 85 (3.3) 23.7 (0.9) 115 (4.5) 85 (3.3) 24 (0.9) * Air Quality Index for VOC aligns with TVOC levels for IAQ as specified by the WHO (World Health Organization). ** DIP switch selectable. *** One setpoint type is selectable via DIP switch on display models only. Display Models Touchscreen 61 mm (2.4 in), color, backlit, capacitive, 240x300px Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable Timeout override: Display timeout** Lockout override: Touchscreen/button lockout** LCD 52mm (2.05 in), segmented with 3 buttons Setpoint: 0-10Vdc. Temperature, humidity or fan speed selectable Timeout override: Display timeout** Lockout override: Touchscreen/button lockout** Setpoints*** Temperature setpoint 0 to 10V output Scale: 10 to 35 °C (50 to 95 °F) / 0 to 50 °C (32 to 122 °F) Humidity setpoint 0 to 10V output Scale: 0 to 100% RH Fan speed setpoint 0 to 10V output Off 0V, Low 3.3V, Med. 6.7V, High 10.0V Override Override button Display models feature a momentary-to-ground override button Wiring Terminals Terminal blocks Screw terminals, 18-24 AWG Screw terminal torque 0.2 N-m (2.0 in-lbF) max. Regulatory Information Agency approvals UL 916, European conformance CE: EN61000-6-2 EN61000-6-3 EN61000 Series - industrial immunity EN 61326-1 FCC Part 15 Class B, REACH, RoHS, Green Premium, RCM (Australia), ICES-003 (Canada), EAC (Russia) schneider-electric.com | 3 SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Installation 1. Remove the cover from the base at the bottom of the device. 2. Position the sensor base vertically on the wall 1.35 m (4.5 ft.) above the floor with the “UP” arrow facing upward. Lo- cate away from windows, vents and other sources of draft. If possible, do not mount on an external wall, as this may cause inaccurate temperature readings. 3. Pull 18 or 22 AWG cable(s) through the hole in the back- plate. 4. Mount the backplate onto the wall using the screws provided. Six screw holes available. Use a minimum of two for secure mounting. 5. Connect the wires to the screw terminals. Do not over-tighten the screws. Wiring diagram: 10987654321 VOC OUT CO 2 OUT OVERRIDE* SETPOINT OUT** RH OUT TEMP OUT COMMON POWER SUPPLY 20-30 Vdc, 24 Vac CONTROL SYSTEM COMMON + - POWER (+24) * Momentary to ground. ** 0-10V DIP switch selectable for temperature, RH (if equipped) or fan speed (off, 0V, Low 3.3V, Medium 6.7V or high 10V). schneider-electric.com | 4 SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com 6. Set the DIP switches. ON 12345678 Temp / RH-Fan SetpointTemp Range 1 / 2 RH / Fan SetpointScreen Timeout On/OffTouch-Button Disable On/OffmA / Voltag e 5V / 10 V 2000 / 5000pp m ABC On / Of f SwitchFunctionDescription 1Output modeON - 4-20mA output mode enabled OFF - Voltage output mode enabled 2Voltage output range* ON - 0-5V output range enabled OFF 0-10V output range enabled 3CO 2 output range ON - 0-2000 ppm CO 2 output range enabled OFF - 0-5000 ppm CO 2 output range enabled 4Automatic Baseline Calibration (ABC) for CO 2 ON - ABC enabled OFF - ABC disabled 5Setpoint output type ON - Temperature setpoint enabled (temp range selected on DIP switch 6) OFF - RH or Fan Speed setpoint ena- bled (specific setpoint output type to be selected on DIP switch 6) Models without RH option select only temp or fan setpoint 6Setpoint output temper- ature range or RH/Fan Speed output type Temperature setpoint (must be enabled on DIP switch 5) ON - Temp range 1, 50 to 95 °F (10 to 35 °C) enabled OFF - Temp range 2, 32 to 122 °F (0 to 50 °C) enabled RH or Fan Speed setpoint (must be enabled on DIP switch 5) ON - RH setpoint enabled OFF - Fan Speed setpoint enabled Models without RH option, set to OFF 7Display times out and turns off after 6-10 seconds of touchscreen/ button press ON - Display Timeout enabled OFF - Display Timeout disabled SwitchFunctionDescription 8Touchscreen touch functions and buttons are disabled ON - Touchscreen touch/button functions disabled OFF - Touchscreen touch/button functions enabled * Only used with voltage output mode enabled. Not applicable to setpoint output. Setpoint is 0-10V fixed. 7. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover down- ward until it latches at the bottom. 8. Install locking screw to secure cover in closed position. 9. 400 ppm baseline calibration allows the sensor to be set at 400 ppm. Push and hold the calibration button for 3 to 5 seconds. The LED will flash green. Once the button is released, calibration is complete and the LED switches off. Calibration button access hole LED Touchscreen Operation Main Screen The touchscreen user interface displays applicable sensor output values (temperature, RH, CO 2 and VOC), setpoint value, menu button and CO 2 stoplight status (if enabled). Setpoint value (temperature setpoint shown) Fahrenheit/Celsius Temperature value Menu button RH value CO 2 value VOC AQI value Installation (cont.) schneider-electric.com | 5 SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Menu Screen The menu screen opens when pressing the Menu button on the main screen. Integrator’s submenu, occupancy/override, Fahrenheit/Celsius, settings, setpoint submenu (temp, RH or fan, determined by DIP switch settings) and CO 2 stoplight but- tons are displayed on the menu screen. Temperature setpoint DIP switch selected RH setpoint DIP switch selected Fan Speed setpoint DIP switch selected Menu Button Functions Integrator’s Submenu Press this icon to access the Integrator’s menu. Submenu Only Submenu Only Submenu Only Submenu Only Occupied Override Button Press this icon to provide momentary ground output to the controller Signals occupied/override call to controller. Single Press Only Fahrenheit/Celsius Switch Press this icon to display either °C or °F. Settings This icon provides the ability to change the color scheme of the display. Changes units to Fahrenheit when pressed. Changes units to Celsius when pressed. Single Press Only Temp Setpoint Adjustment Click this icon to access the setpoint change menu. Mutually exclusive with fan speed, set by DIP switch. Humidity Setpoint Adjustment Click this icon to access the setpoint change menu. Mutually exclusive with humidity and fan speed. Set by DIP switch. schneider-electric.com | 6 SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Menu Button Functions (cont.) Submenu Only Submenu Only Selected Feature is ON Feature is OFF Fan Speed Click this icon to access the fan speed menu. Mutually exclusive with humidity and fan speed. Set by DIP switch. CO 2 Stoplight Menu Click this icon to toggle the CO 2 Stoplight feature on and off. With CO 2 Stoplight turned on, the background color of the main screen changes with CO 2 level. This provides a visual indicator of CO 2 levels to the room occupants. Green CO 2 <1000 ppm Yellow & Single Flag CO 2 = 1000 to 1500 ppm Red & Double Flag CO 2 > 1500 ppm LCD Display Operation Button Functions Display Icons The main screen displays sensor values for CO 2 , VOC (if equipped), RH (if equipped), temperature and Celsius/Fahren- heit. Change Values Menu Advance Change Values Alternates between CO 2 and VOC every 6 seconds Humidity Value (if equipped) Temperature Value Override Press Indicator CO 2 Value VOC Value (if equipped) schneider-electric.com | 7 SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com Setpoint Function A single 0-10V setpoint (temperature, RH (if equipped) or fan speed) can be selected via DIP switch. Temperature Setpoint Adjustment Changing Celsius and Fahrenheit Scales Occupied/Override Button Adjusts setpoint up Adjusts setpoint down Note: Numeric information will flash while in Set mode. Press the Menu Advance button After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears. RH Setpoint Adjustment Fan Speed Setpoint Adjustment Adjusts setpoint up Adjusts setpoint down Press the Menu Advance button After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears. Note: Numeric information will flash while in Set mode. Adjusts setpoint up Adjusts setpoint down Press the Menu Advance button After adjustment, wait 6 seconds or press the Menu Advance button. Setpoint is accepted and main screen appears. Low Medium High Note: Fan speed scale flashes when in Set mode. Off setting is default. Adjusts from ºF to ºC Adjusts from ºC to ºF Press the Menu Advance button 2 times After adjustment, wait 6 seconds or press the Menu Advance button to return to the main screen. 2x Note: ºF or ºC text will flash while in Set mode. Press and hold the Menu Advance button for 1 second Override Press Indicator illuminates for 6 seconds. schneider-electric.com | 8 SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions © 2021 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. April 2021 Z207900-0D nk USA: +1 888-444-1311 Europe: +46 10 478 2000 Asia: +65 6484 7877 www.schneider-electric.com China RoHS Compliance Information Environment-Friendly Use Period (EFUP) Table 本表格依据 SJ/T11364 的 规定编制。 O: 表示 该有害物质在该部件所有均质材料中的含量均在 GB/T 26572 规定的限量要求以下。 X: 表示 该有害物质至少在该部件的某一均质材料中的含量超出 GB/T 26572 规定的限量要求。 (企 业可在此处,根据实际情况对上表中打 的技 术原因进行进一步说明。) This table is made according to SJ/T 11364. O: indicates that the concentration of hazardous substance in all of the homogeneous materials for this part is below the limit as stipulated in GB/T 26572. X: indicates that concentration of hazardous substance in at least one of the homogeneous materials used for this part XOOOOO is above the limit as stipulated in GB/T 26572 Z000057-0B 部件名称 Part Name 有害物 质- Hazardous Substances 铅 (Pb) 汞 (Hg) 镉 (Cd)六价 铬 (Cr (VI))多溴 联苯 (PBB)多溴二苯 醚 (PBDE) 电子件 ElectronicNext >