SER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 3 Location 3 Installation 3 Terminal, Identification and Function 4 Communication wiring to SC3xxxE Relay Pack 4 BACnet ® Communication Wiring (if applicable) 4 Network wiring topology 4 Home Screen Display 5 How to Enter Setup Screen 6 Version 4SER8300 Series2Installation Guide Schneider Electric | II-SER8300-A4.EN.01.2016.v4 www.schneider-electric.com/buildings January 2016 SER8300 ControllerSC3000 Relay Pack DISCLAIMER • The SER8300 series Room Controller is only to be used in conjunction with the SC3000 line voltage switching relay pack. Together they are used as operating controls for high voltage fan coil units. • If replacing an existing Line Voltage FCU Controller, label the wires before removal of the Room Controller. • Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing the Room Controller. A short circuit or wrong wiring may permanently damage the Room Controller or equipment. • All SER8300 series Room Controllers are designed for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user/installer/electrical system designer to incorporate safety devices such as relays, flow switches, thermal protections, and/or an alarm system to protect the entire system against any catastrophic failures. Tampering with the devices or unintended application of the devices results in a void of warranty. • If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. • These devices are not serviceable and must be returned to the supplier for any repair. • A switch or circuit breaker must be installed. It must be suitably located, easily reached, and marked as the disconnecting device. • Never apply more than 9VDC to the Room Controller. • This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. IMPORTANT SYMBOLS Products marked with this symbol state that the manuals must be consulted in all cases to any hazards. This product has been tested to the requirements of CAN/CAS-C22.2 No. 61010-1, second edition, including Amendment 1, or a later version of the same standard incorporating the same level of testing requirements. Alternating Current Direct Current Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION SER8300 Series3Installation Guide Schneider Electric | II-SER8300-A4.EN.01.2016.v4 www.schneider-electric.com/buildings January 2016 • If replacing an existing SER8300 Room Controller, label wires before removal of Controller. • Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing Controller. • A short circuit or wrong wiring may permanently damage Room Controller or equipment. • All SER8300 series Room Controllers are designed for use as operating controls only and are not safety devices. Tampering with the devices or unintended application of the devices will result in a void of warranty. • This transmitter must be installed to provide a separation distance of at least 4in (10cm) from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter. Figure-1 Open the cover Figure-2 Install the base Figure-3 Reinstall cover INSTALLATION Location • Do not install on outside wall. • Do not install in areas with direct heat source. • Do no install near any air discharge grill. • Do not install in areas exposed to direct sunlight. • Ensure Room Controller has sufficient air circulation. • Ensure wall surface is flat and clean. Installation 1. Open unit by pulling on bottom side of Room Controller (Figure 1). 2. Read FCC ID and IC label installed in cover before installing any wireless product. 3. Ensure correct side of base faces up. 4. Pull cables 6in (15cm) out from wall. 5. Align base and mark location of two mounting holes on wall (Figure 2). 6. Install anchors in wall. 7. Insert cable in central hole of base. 8. Insert screws in mounting holes on each side of base. 9. Strip each wire 1/4in ( 0.6cm) from end. 10. Insert each wire according to wiring chart (next page). 11. Gently push excess wiring back into hole. 12. Gently align cover to top of base and snap in place from bottom (Figure 3). 13. Install security screw.SER8300 Series4Installation Guide Schneider Electric | II-SER8300-A4.EN.01.2016.v4 www.schneider-electric.com/buildings January 2016 Terminal Identification All SER83xxA Terminal Equipment Controller Terminal 4Tx – Rx Communication Terminal 5Power Hot 7.0 VDC Terminal 6Power Common Terminal 12Modulating 0-10 VDC output. See note below. Terminal 13BACnet + Terminal 14BACnet - Terminal 16BI 1 ( Configurable ) Terminal 17BI 2 ( Configurable ) Terminal 18Scom COMMUNICATION WIRING TO SC3XXXE RELAY PACK TERMINAL IDENTIFICATION AND FUNCTION To other SC3xxxE Relay Pack Te rminal ControllerRelay Pack SER83xxASC3504E 4 - Tx / Rx 5 - 7 Vdc Power Hot 6 - Power Common 1 - Tx / Rx 2 - 7 Vdc Power Hot 3 - Power Common Relay Pack SC3300E 1 - Tx / Rx 2 - 7 Vdc Power Hot 3 - Power Common Only ONE SC3xxxE Relay Pack with remote monitoring inputs can be used under a single SER83xxA Room Controller. All other slave units must be SC3xxxE Relay Pack(s) without remote inputs. A maximum of 10 SC3xxxE Relay Packs can be used for a single SER83xxA Room Controller. From SER83xxA to First SC3xxxE Relay Pack • Uses existing or new field wires. • A minimum of 3 wires are required 14-22 Ga, Solid, or Stranded. Shield not necessary. From First SC3xxxE to all Other Slave SC3xxxE Relay Pack(s) • Uses existing or new field wires. • A minimum of 2 wires are required 14-22 Ga, Solid, or Stranded. Shield not necessary. • Connect only two wires: Tx/Rx (1) and Power Common (3). Daisy Chained TopologyStar Topology Mixed Daisy Chained & Star Topology Network Wiring Topology Termina l ControllerTerminal Controller To others To others 13 - COM + 14 - COM - SER83xxA SER83xxA 13 - COM + 14 - COM - BACnet ® Communication Shielded Wiring (if required) NOTE: See SER8300 BACnet ® integration manual for more details NOTE: never use any terminal on Room Controller not mentioned in above table. Warning: • only the following models can be Slave Relays: SC3500E5045, SC3400E5045, and SC3300E5045. • Only one SC3x4X Relay Pack with monitoring input can be used for a single SERX3xxA Room Controller. Terminal 12 (UO12) - 0-10 VDC Modulating Output This output is not used by the SER8300 internal control logic. A Lua4RC is required to use this terminal. Example: UO12 (0 - 10 VDC) = PI_Cool (%) /10 ME.AO124=ME.AO22/10SER8300 Series5Installation Guide Schneider Electric | II-SER8300-A4.EN.01.2016.v4 www.schneider-electric.com/buildings January 2016 Date Time Occupancy Status Fan Status System Status Up Arrow Raise Temperature Setpoint Actual Setpoint Room Indoor Temperature Room Indoor Humidity Outdoor Temperature Down Arrow Lower Temperature Setpoint System Mode Select system mode Temperature Units Select Celsius or Fahrenheit Help Enter help screen Language Select preferred language Fan Mode Select fan mode HOME SCREEN DISPLAY Hospitality User Interface Shown Short Network Message Note: User HMI is configurable and allows display functions such as Date, Time, Humidity, Outdoor Temperature, Setpoint, and others to be enabled or disabled by setting various parameters. SER8300 Series6Installation Guide Schneider Electric | II-SER8300-A4.EN.01.2016.v4 www.schneider-electric.com/buildings January 2016 ENTER SET-UP SCREEN Touch and hold this point for 3 seconds to enter set-up mode SET-UP SCREEN DISPLAY Return to home screen General Note: 1/2 Setup Network Configuration Setpoints - Display Setpoints view Test outputs Language Selection Adjustable parameter Non-adjustable parameter Note: If a configuration/installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt shows to prevent access to device configuration components. Discover Mode The Controller becomes discoverable on the wireless ZigBee® network for 1 minute (this button is hidden if ZigBee ® settings are not configured) Enter BACnet ® & ZigBee ® network settings Enter parameter configuration menu Enter setpoint & display settings Enter output testing mode Enter status and service view Note: The "Network" button does not show if no BACnet ® or ZigBee ® card is installed. Enable selected language(s)* *only available in recent versions of firmwareNext >