Version 5 SE8600 Series Installation Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller CONTENTS Installation 2 Terminal Identification & Function 3 Terminal identification 3 Typical Applications 4 2H / 2C 5 2C / Mod. heat 6 2C / Aux. Eco 6 Remote Sensor Accessories 7 Home Screen Display 8 How to Enter Setup Screen 9 Appendixes 10 Support 112 • If replacing an existing device, label wires before removal of Room Controller. • Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing Room Controller. • A short circuit or wrong wiring may permanently damage Room Controller or equipment. • All SE8600 series controls are designed for use as operating controls only and are not safety devices. Tampering with the devices or unintended application of the devices will result in a void of warranty. • This device must be installed to provide a separation distance of at least 8in (20cm) from all persons and must not be located or operating in conjunction with any other antenna or transmitter. Figure-1 Open cover Figure-2 Install base Figure-3 Reinstall cover INSTALLATION Location • Do not install on outside wall. • Do not install in areas with direct heat source. • Do no install near any air discharge grill. • Do not install in areas exposed to direct sunlight. • Ensure Room Controller has sufficient air circulation. • Ensure wall surface is flat and clean. Installation 1. Remove security screw (if any) on bottom of Room Controller cover. 2. Open unit by pulling on bottom side of Room Controller (Figure 1). 3. Read FCC ID and IC label installed in cover before installing any wireless product. 4. Ensure correct side of base faces up. 5. Pull cables 6in (15cm) out from wall. 6. Align base and mark location of two mounting holes on wall (Figure 2). 7. Install anchors in wall. 8. Insert cable in central hole of base. 9. Insert screws in mounting holes on each side of base. 10. Strip each wire 1/4in (0.6cm) from end. 11. Insert each wire and screw according to wiring chart. 12. Gently push excess wiring back into hole. 13. Gently align cover to top of base and snap in place from bottom (Figure 3). 14. Install security screw. Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 20163 Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 2016 SE86xxU Description / Application Used in applications IAQ, HP & RTU Internal TemperatureX 1- BO1 Aux 2- BO2Y2 3- BO3Y1 4- BO4G 5- RC RC (24 Vac) 6- C Common 7- RH RH 8- BO8W1 9- UO9W2 / OB 10- UO10Econo (0-10 Vdc) 11- UO11 Heat (0-10 Vdc), set "Heat Stages" to 0 to enable 12- UO12Dehumidification output (24 Vac On/Off) 13- RS485 +BACnet (+) 14- RS485 -BACnet (-) 15- RS485 RefBACnet Ref. (do not sire shield in this terminal) 16- UI16UI16 (multifunction input) 17- UI17UI17 (multifunction input) 18 ScomCommon 19- UI19 CO2 (0-10 Vdc input) 20- UI20 RS (Remote sensor input 10K, type 2 thermistor) 21 Scom Common 22- UI22SS (Supply sensor input 10K, type 2 thermistor) 23- UI23OS (Outside sensor input 10K, type 2 thermistor) 24- UI24Airflow (0-10 Vdc input) TERMINAL IDENTIFICATION AND FUNCTION Terminal identification4 TYPICAL APPLICATIONS SE8600 BO 1 - Aux BO 2 - Y2BO 3 - Y1 BO 4 - G RC (24 Vac) C (Common) RH BO 8 - W1 UO 9 - W2 UO 10 - Econo UO 11 - Heat UO 12 BACnet + BACnet - BACnet REFUI 16UI 17CommonUI 19 - CO2UI 20 - RSCommonUI 22 - SSUI 23 - OSUI 24 - Airflow ECONO W2 W1 C R G Y1 Y2 C R CO2 TRANSMITTER (0-10 VDC) OUT C OUT R AIR FLOW MEASURING STATION (0-10 VDC) FILTER DPS SAT SENSOR OAT SENSOR RTU: 2 Heating / 2 Cooling Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 20165 Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 2016 SE8600 BO 1 - Aux BO 2 - Y2BO 3 - Y1 BO 4 - G RC (24 Vac) C (Common) RH BO 8 - W1 UO 9 - W2 UO 10 - Econo UO 11 - Heat UO 12 BACnet + BACnet - BACnet REFUI 16UI 17CommonUI 19 - CO2UI 20 - RSCommonUI 22 - SSUI 23 - OSUI 24 - Airflow ECONO C R G Y1 Y2 C R CO2 TRANSMITTER (0-10 VDC) OUT C OUT R AIR FLOW MEASURING STATION (0-10 VDC) FILTER DPS SAT SENSOR OAT SENSOR Mod. Heat (0-10 VDC) RTU: 2 Cooling / Modulating Heat6 SE8600 BO 1 - Aux BO 2 - Y2BO 3 - Y1 BO 4 - G RC (24 Vac) C (Common) RH BO 8 - W1 UO 9 - O/B UO 10 - Econo UO 11 - Heat UO 12 BACnet + BACnet - BACnet REFUI 16 UI 17 Common UI 19 - CO2UI 20 - RSCommonUI 22 - SSUI 23 - OSUI 24 - Airflow ECONO O W C R G Y1 Y2 C R CO2 TRANSMITTER (0-10 VDC) OUT C OUT R AIR FLOW MEASURING STATION (0-10 VDC) FILTER DPS SAT SENSOR OAT SENSOR HPU: 2 Compressors, Auxiliary Heat and Economizer Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 20167 Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 2016 REMOTE SENSOR ACCESSORIES Model no.Description S3010W1045Wall mounted temperature sensor S3020W1045Wall mounted temperature sensor with override button and occupancy status LED Note: If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting the sensor(s) in RS terminal will re-activate the internal sensor. Remote mount temperature sensors inputs use 10K type 2 NTC thermistors. Features: • Each sensor can be configured for various averaging combinations. Refer to S3000 series remote sensors for more details. Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10KΩ±3%, B25/85°C = 3975K±1.5%) ºCºFKohmºCºFKohmºCºFKohmºCºFKohmºCºFKohm -40-40324.3197-20-494.514903232.1910206812.4601401045.3467 -35-31234.4009-15571.243054125.1119257710.0000451134.3881 -30-22171.3474-101454.1988105019.739030868.0694501223.6202 -25-13126.6109-52341.5956155915.628635956.5499551313.00168 Date Time Occupancy Status Fan Status System Status Up Arrow Raise Temperature Setpoint Actual Setpoint Room Indoor Temperature Outdoor Temperature Down Arrow Lower Temperature Setpoint System Mode Select system mode Temperature Units Select Celsius or Fahrenheit Help Enter help screen Language Select preferred language Fan Mode Select fan mode HOME SCREEN DISPLAY Typical Hospitality User Interface Shown Short Network Message Note: User HMI is configurable and allows display functions such as Outdoor Temperature, Setpoint, and other buttons to be enabled or disabled by setting various parameters in the setup screens. Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 20169 Schneider Electric | II-SE8600A4.EN.04.2016.v5 www.schneider-electric.com/buildings April 2016 HOW TO ENTER SET-UP SCREEN Touch and hold this point for 3 seconds to enter set-up mode SET-UP SCREEN DISPLAY Return to home screen General Note: 1/2 Setup Network Configuration Setpoints - Display Service view Test outputs Language selection Adjustable parameter Non-adjustable parameter Note: If a configuration/installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt shows to prevent access to device configuration components. Discover Mode The Controller becomes discoverable on the wireless ZigBee ® network for 1 minute (this button is hidden if ZigBee ® settings are not configured) Enter BACnet ® & ZigBee ® network settings Enter parameter configuration menu Enter setpoint & display settings Enter output testing mode Enter status and service view For more information on using and configuring the functions of the HMI, refer to SE8600 User Interface Guide Enter language selectionNext >