Version 6 SE8300 Series Installation Guide 24 Vac Low Voltage Commercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Terminal Identification & Function 3 Terminal identification 3 Wiring 4 Typical Applications 5 2 pipe systems cooling and/or heating 6 4 pipe systems cooling and heating 7 2 pipe systems cooling or heating with reheat 7 Remote Sensor Accessories 8 Home Screen Display 9 How to Enter Setup Screen 10 Appendix 11 Support 122 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 • If replacing an existing Room Controller, label wires before removal of Controller. • Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing Room Controller. • A short circuit or wrong wiring may permanently damage Room Controller or equipment. • All SE8300 series controls are designed for use as operating controls only and are not safety devices. Tampering with the devices or unintended application of the devices will result in a void of warranty. • This device must be installed to provide a separation distance of at least 8in (20cm) from all persons and must not be located or operating in conjunction with any other antenna or transmitter. Figure-1 Open the cover Figure-2 Install the base Figure-3 Reinstall cover INSTALLATION Location • Do not install on outside wall. • Do not install in areas with direct heat source. • Do no install near any air discharge grill. • Do not install in areas exposed to direct sunlight. • Ensure Controller has sufficient air circulation. • Ensure wall surface is flat and clean. Installation 1. Remove security screw (if any) on bottom of Room Controller cover. 2. Open unit by pulling on bottom side of Room Controller (Figure 1). 3. Read FCC ID and IC label installed in cover before installing any wireless product. 4. Ensure correct side of base faces up. 5. Pull cables 6in (15cm) out from wall. 6. Align base and mark location of two mounting holes on wall. 7. Install anchors in wall (Figure 2). 8. Insert cable in central hole of base. 9. Insert screws in mounting holes on each side of base. 10. Strip each wire 1/4in ( 0.6cm) from end. 11. Insert each wire and screw according to wiring chart. 12. Gently push excess wiring back into hole. 13. Gently align cover to top of base and snap in place from bottom (Figure 3). 14. Install security screw.3 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 CLEANING SE8300 ROOM CONTROLLER • Use a soft, pre-moistened lint-free cloth for cleaning. • Avoid getting moisture in openings. • Do not spray anything directly on SE8000 Room Controller or use compressed air. • Do not use caustic/corrosive products, ammonia, solvents or any cleaning product containing alcohol or grit. • Never use tools directly on the touchscreen. • Never use paint on SE8000 Room Controller. • Do not drop or crush SE8000 Room Controller, or allow SE8000 Room Controller to come into contact with liquids. • Do not use a damaged device (such as one with a cracked screen). • Functionality guarantees are no longer valid if the glass on the screen is broken. Failure to comply with these recommendations will result in damage to the unit and void the manufacturer’s warranty.4 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 SE83xxU Description / Application Used in applications 2 & 4 Pipe2 & 4 Pipe2 & 4 Pipe Control Type = On/OffControl Type = FloatingControl Type = Analog Internal TemperatureXXX Internal HumidityModel DependentModel DependentModel Dependent 1- BO1 Not usedNot usedNot used 2- BO2Fan-LFan-LFan-L 3- BO3Fan-MFan-MFan-M 4- BO4Fan-HFan-HFan-H 5- RC / 24 V~ Hot24 V~ Hot24 V~ Hot24 V~ Hot 6- C / 24 V~ Com24 V~ Com24 V~ Com24 V~ Com 7- RH Aux HeatAux HeatAux Heat 8- BO8Aux HeatAux HeatAux Heat 9- UO9Normally Close Cool ValveClose Cool ValveNot used 10- UO10Normally Close Heat ValveClose Heat ValveNot used 11- UO11Normally Open Cool ValveOpen Cool ValveAnalog Heat valve 12- UO12Normally Open Heat ValveOpen Heat ValveAnalog Cool Valve 13- RS485 +BACnet MS-TP +BACnet MS-TP +BACnet MS-TP + 14- RS485 -BACnet MS-TP -BACnet MS-TP -BACnet MS-TP - 15- RS485 RefBACnet MS-TP RefBACnet MS-TP RefBACnet MS-TP Ref 16- UI16UI16 FunctionUI16 FunctionUI16 Function 17- UI17UI17 FunctionUI17 FunctionUI17 Function 18 ScomCommonCommonCommon 19- UI19 UI19 FunctionUI19 FunctionUI19 Function 20- UI20Remote Room SensorRemote Room SensorRemote Room Sensor 21 ScomCommonCommonCommon 22- UI22Remote Supply SensorRemote Supply SensorRemote Supply Sensor 23- UI23Not usedNot usedNot used 24- UI24Not usedNot usedNot used TERMINAL IDENTIFICATION AND FUNCTION Terminal identification5 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 Wiring Main outputs wiring 2 Pipe Applications4 Pipe Applications Control type = On-Off OR Heating / Cooling valve Com 24Vac UO9 UO11 Heating valve Cooling valve OR OR UO10 NC UO12 NO UO 09 NC UO11 NO Com 24Vac Com 24Vac Floating control Heating / Cooling valve UO11 UO9 Com Open Close Heating valve Cooling valve UO12 UO10 UO11 UO9 Com Open Close Com Open Close Analog control Heating / Cooling valve UO12 Com 24Vac 0-10Vdc Heating valve Cooling valve UO11 UO12 Com 24 Vac 0-10 Vdc Com 24 Vac 0-10 Vdc BO2 - Fan L 3 Speed 2 Speed Single speed HIGHHIGH MED LOWLOW HIGH Power & Fan ( All models ) 24 Vac Transformer 3 Speed 2 Speed Single speed HIGHHIGH MED LOWLOW HIGH RC (24 Vac) C (Common) RH BO8 - Aux Heat BO8 Auxiliary output wiring Dry contact to end device 24 Vac maximum R RC (24 Vac) C (Common) RH BO8 - Aux Heat 24 Vac power to relay R6 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 TYPICAL APPLICATIONS SchematicWiringSettings 2 pipe system cooling and/or heating Control type = On / Off Cooling / Heating Valve 3 Speed Fan Sensor Normally Closed On/Off Room Temperature Control Thermostat BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 NC UO10 UO11 UO12 24 Vac fan relays 24 Vac Transformer HIGH MED LOW Common UI 19 Normally Closed Optional supply water temperature sensor 2 3 4 5 6 7 8 9 10 11 12 18 19 Mandatory • Pipe no = 2 pipes • CntrltTyp = On/Off • Fan Menu = 0 (L-M-H) • FL time = N/A If cooling only set: • SeqOpera = Cooling only If heating only set: • SeqOpera = Heating only If heat / cool auto-changeover with a local water temperature sensor set: • SeqOpera = Cooling only • UI19 = COS 2 pipe system cooling and/or heating Control type = Floating7 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 SchematicWiringSettings Cooling / Heating Valve 3 Speed Fan Sensor Modulating Floating Room Temperature Control Thermostat BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 UO10 UO11 UO12 24 Vac fan relays 24 Vac Transformer HIGH MED LOW Common UI19 Normally Closed Optional supply water temperature sensor 2 3 4 5 6 7 8 9 10 11 12 18 19 Mandatory • Pipe no = 2 pipes • CntrltTyp = Floating • Fan Menu = (L-M-H) • FL time = as per actuator If cooling only set: • SeqOpera = Cooling only If heating only set: • SeqOpera = Heating only If heat / cool auto-changeover with a local water temperature sensor set: • SeqOpera = Cooling only • UI19 = COS 2 pipe system cooling and/or heating Control type = Analog Cooling / Heating Valve 3 Speed Fan Sensor Modulating Analog Room Temperature Control Thermostat BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 UO10 UO11 UO12 24 Vac fan relays 24 Vac Transformer HIGH MED LOW Common UI 19 Normally Closed Optional supply water temperature sensor 2 3 4 5 6 7 8 9 10 11 12 18 19 0 to 10 Vdc Mandatory • Pipe no = 2 pipes • CntrltTyp = Analog • Fan Menu = (L-M-H) • RA/DA = as per actuator If cooling only set: • SeqOpera = Cooling only If heating only set: • SeqOpera = Heating only If heat / cool auto-changeover with a local water temperature sen- sor set: • SeqOpera = Cooling only • UI19 = COS 4 pipe system cooling and heating Control type = On / Off Heating Valve 3 Speed Fan Normally Closed On/Off Room Temperature Control Thermostat Cooling Valve Mandatory • Pipe no = 4 pipes • CntrltTyp = On/Off • Fan Menu = (L-M-H) • SeqOpera = Cool/Heat BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 NC UO10 UO11 NC UO12 24 Vac fan relays 24 Vac Transformer HIGH MED LOW Heating 2 3 4 5 6 7 8 9 10 11 12 Cooling Normally Closed8 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 SchematicWiringSettings 4 pipe system cooling and heating Control type = Floating Heating Valve 3 Speed Fan Modulating Floating Room Temperature Control Thermostat Cooling Valve BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 UO10 UO11 UO12 24 Vac fan relays 24 Vac Transformer HIGH MED LOW Heating 2 3 4 5 6 7 8 9 10 11 12 Cooling Mandatory • Pipe no = 4 pipes • CntrltTyp = Floating • Fan Menu = (L-M-H) • FL time = as per actuator • SeqOpera = Cool/Heat 4 pipe system cooling and heating Control type = Analog Heating Valve 3 Speed Fan Modulating Analog Room Temperature Control Thermostat Cooling Valve BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 UO10 UO11 UO12 24 Vac fan relays 24 Vac Transformer HIGH MED LOW Heating 2 3 4 5 6 7 8 9 10 11 12 Cooling Mandatory • Pipe no = 4 pipes • CntrltTyp = Analog • Fan Menu = (L-M-H) • RA/DA = as per actuator • SeqOpera = Cool/Heat 2 pipe system cooling or heating with reheat Control type = Floating Electric Reheat 3 Speed Fan Modulating Floationg Room Temperature Control Thermostat Cooling / Heating Valve Sensor BO2 - Fan L BO3 - Fan M BO4 - Fan H RC (24 Vac) C (Common) RH BO8 - Aux Heat UO9 UO10 UO11 UO12 24 Vac fan relays 24 Vac Transformer HIGH MED LOW SCom UI 19 Optional supply water temperature sensor 2 3 4 5 6 7 8 9 10 11 12 18 19 Electric Reheat Normally Closed Mandatory • Pipe no = 2 pipes • CntrltTyp = Floating • Fan Menu = (L-M-H) • FL time = as per actuator • SeqOpera = Cool/Reheat • UI19 = COS9 Schneider Electric | II-S8300-A4.EN.04.2017.v7 www.schneider-electric.com/buildings April 2017 REMOTE SENSOR ACCESSORIES Model no.Description S3010W1000Wall mounted temperature sensor S3020W1000Wall mounted temperature sensor with override button and occupancy status LED The SE8300 Room Controller is compatible with remote mount temperature sensors using 10K type 2 NTC thermistors. Note: If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting the sensor(s) in the RS terminal will re-activate the internal sensor. Features: • Each sensor can be configured for various averaging combinations (refer to S3000 series remote sensors for more details) • Optional occupancy led • Optional override key Wiring example of single remote room sensor: Common UI 20 BO8 24 Vac Com UI17 SE8300 Series Controller S3020W1045 Remote wiring 1 sensor S2-1= On, S2-2=On S3010W1045 Remote wiring 1 sensor S2-1= On, S2-2=On SCom RS Aux C DI SCom RS OR Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10KΩ±3%, B25/85°C = 3975K±1.5%) ºCºFKohmºCºFKohmºCºFKohmºCºFKohmºCºFKohm -40-40324.3197-20-494.514903232.1910206812.4601401045.3467 -35-31234.4009-15571.243054125.1119257710.0000451134.3881 -30-22171.3474-101454.1988105019.739030868.0694501223.6202 -25-13126.6109-52341.5956155915.628635956.5499551313.0016 Dip switch setting for: 1 sensor S2-1 = ON S2-2 = ON ON 12Next >