CONTENTS Installation2 Preparation2 Location2 Installation2 Terminal, Identification and Function3 Wiring3 Main outputs wiring4 Typical applications4 Remote sensor accessories7 Configuring and Status Display Instructions9 Status display9 User interface11 SE7200 Series Installation Guide Install Guide for Low Voltage Zoning Room Controller For Commercial HVAC Applications 2 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 INSTALLATION Preparation • Remove security screw on bottom of Room Controller cover. • Open unit by pulling on bottom side of Room Controller (Figure 1). • Remove wiring terminals from sticker. • Read the FCC ID and IC label installed in the cover. Location 1. Should not be installed on an outside wall. 2. Must be installed away from any direct heat source. 3. Should not be installed near air discharge grill. 4. Should not be affected by direct sun radiation. 5. Nothing should restrict vertical air circulation to Room Controller. Installation 1. Swing open Room Controller PCB to left by pressing PCB locking tabs (Figure 2). 2. Pull out cables 6” out from wall. Ensure wall surface must be flat and clean. 3. Insert cable in central hole of base. 4. Align base and mark location of two mounting holes on wall ensuring base is in the proper orientation. Arrow on base should be facing up. 5. Install anchors in wall. 6. Insert screws in mounting holes on each side of base (Figure 2). 7. Gently swing back circuit board on base and push until tabs lock. 8. Strip each wire 1/4 inch from end. 9. Insert each wire according to wiring diagram. 10. Gently push excess wiring back into hole (Figure 3). 11. Re-Install wiring terminals in correct locations (Figure 3). 12. Re-install cover (top side first) and gently push extra wire length back into hole in wall. 13. Install security screw. • If replacing an old Room Controller, label the wires before removal of the old Room Controller. • Electronic controls are static sensitive devices. Discharge yourself properly before manipulating and installing the Room Controller. • A short circuit or wrong wiring may permanently damage the Room Controller or the equipment. • All SE7000 series Room Controllers are designed for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc…) and/or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty. Figure-3 Re-install terminal blocks Figure-2 Location of PCB locking tabs Figure-1 Open the cover3 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 TERMINAL, IDENTIFICATION AND FUNCTION Terminal identification Schneider Part NumbersSE7200C5x45(x)Viconics NumberSE7200F5x45(x) Description / Application1 or 2 Floating outputsDescription / Application1 or 2 Analog outputs 1 or 2 On/Off outputs 4- 24 V~ Hot24 V~ Hot4- 24 V~ Hot24 V~ Hot 5- 24 V~ Com24 V~ Com5- 24 V~ Com24 V~ Com 6- Aux BO 5BO 5-Aux6- Aux BO 5BO 5-Aux 7- Aux BO 5BO 5-Aux7- Aux BO 5BO 5-Aux 8- BO 3 Open HeatBO 3 9- BO 4 Close HeatBO 49- AO 2 HeatAO 2 10- BO 1 Open CoolBO 1 10- AO 1 CoolAO 1 11- BO 2 Close CoolBO 2Not used BlankBlank 12- BI 1BI 112- BI 1BI 1 13- RSRS13- RSRS 14- ScomScom14- ScomScom 15- BI 2BI 215- BI 2BI 2 16- UI 3 COS / COC /SSUI 316- UI 3 COS / COC /SSUI 3 Wiring #4 24 V~ Hot #5 24 V~ Com #6 #7 #4 24 V~ Hot #5 24 V~ Com #6 #7 Auxiliary output ( All models ) - Dry contact to end device 24 V~ maximum - 24 VAC power to relay R R 4 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 Main outputs wiring Single output applicationsDual output applications On-Off control SE7200C5x45(x) Heating / Cooling valve 24 VAC Com OR 24 V~ Hot 24 V~ Com BO1 if N.O. BO2 if N.C. 24 V~ Hot 24 V~ Com BO3 if N.O. BO4 if N.C. BO1 if N.O. BO2 if N.C. Heating valve Cooling valve OR OR 24 VAC Com Heating valve Cooling valve 24 VAC Com OR OR Floating control SE7200C5x45(x) Open Com Close Heating / Cooling valve 24 V~ Hot 24 V~ Com BO1 BO2 Open Com Close Heating valve Open Com Close Cooling valve 24 V~ Hot 24 V~ Com BO3 BO4 BO1 BO2 Analog control SE7200C5x45(x) Heating / Cooling valve Com 24 VAC 0-10 VDC 24 V~ Hot 24 V~ Com AO 1 24 V~ Hot 24 V~ Com AO 2 AO 1 Com 24 VAC 0-10 VDC Heating valve Cooling valve Com 24 VAC 0-10 VDC Typical applications SchematicWiringSettings Pressure dependent VAV cooling only:SE7200C5x45(x) Floating actuator Modulating Floating VAV Actuator Room Temperature Control Minimum & Maximum Position Adjusted on the actuator Mandatory • Out1Conf = 2.0 • CntrltTyp = Floating • FL time = as per actuator • SeqOpera = 0 Cooling only Pressure dependent VAV cooling only: SE7200F5x45(x) Analog actuator Analog VAV Actuator Room Temperature Control Minimum & Maximum Position Adjusted on the actuator Mandatory • Out1Conf = 2.0 • RA/DA = as per actuator • SeqOpera = 0 Cooling only5 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 SchematicWiringSettings Pressure dependent VAV cooling or heating with changeover: SE7200C5x45(x) Floating actuator Room Temperature Control Minimum & Maximum Position Adjusted on the actuator Mandatory • Out1Conf = 2.0 • CntrltTyp = Floating • FL time = as per actuator If heat / cool auto- changeover with a local water temperature sensor set: • SeqOpera = 0 Cooling only • UI3 = COS Pressure dependent VAV cooling or heating with changeover: SE7200F5x45(x) Analog actuator Room Temperature Control Minimum & Maximum Position Adjusted on the actuator Mandatory • Out1Conf = 2.0 • RA/DA = as per actua- tor • SeqOpera = 0 Cooling only If heat / cool auto- changeover with a local water temperature sensor set: • SeqOpera = 0 Cooling only • UI3 = COS Pressure dependent VAV cooling or heating with changeover and reheat:SE7200C5x45(x) Floating actuator Modulating Floating VAV Actuator Heating and or Cooling & On-Off Duct Heater Room Temperature Control Minimum & Maximum Position Adjusted on the actuator Mandatory • Out1Conf = 2.0 • CntrltTyp = Floating • FL time = as per actuator If heat / cool auto- changeover with a local water temperature sensor set: • SeqOpera = 2 Cooling with Reheat • UI3 = COS Modulating Floating VAV Actuator Changeover Sensor 0 to 10 VDC Analog Actuator Changeover Sensor Changeover Sensor6 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 SchematicWiringSettings Pressure dependent VAV cooling or heating with changeover and reheat: SE7200F5x45(x) Analog actuator Analog VAV Actuator Heating and or Cooling & On-Off Duct Heater Room Temperature Control Minimum & Maximum Position Adjusted on the actuator Mandatory • Out1Conf = 2.0 • RA/DA = as per actuator If heat / cool auto- changeover with a local water temperature sensor set: • SeqOpera = 2 Cooling with Reheat • UI3 = COS Heating or cooling hydronic valve control: SE7200C5x45(x) Floating actuator Modulating Floating Valve Cooling or Heating Room Temperature Control Controller Mandatory • Out1Conf = 2.0 • CntrltTyp = Floating • FL time = as per actuator If cooling only set:: • SeqOpera = 0 Cooling only If heating only set:: • SeqOpera = 1 Heating only Heating or cooling hydronic valve control: SE7200F5x45(x) Analog actuator Analog Valve Cooling or Heating Room Temperature Control Controller Mandatory • Out1Conf = 2.0 • RA/DA = as per actuator If cooling only set:: • SeqOpera = 0 Cooling only If heating only set:: • SeqOpera = 1 Heating only Changeover Sensor7 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 Cooling or heating with changeover hydronic valve control: SE7200C5x45(x) Floating actuator Modulating Floating Valve Heating and / or Cooling Room Temperature Control Controller Mandatory • Out1Conf = 2.0 • CntrltTyp = Floating • FL time = as per actuator If heat / cool auto- changeover with a local water temperature sensor set: • SeqOpera = 0 Cooling only • UI3 = COS Cooling or heating with changeover hydronic valve control: SE7200F5x45(x) Analog actuator Analog Valve Heating and / or Cooling Room Temperature Control Controller Mandatory • Out1Conf = 2.0 • RA/DA = as per actua- tor If heat / cool auto- changeover with a local water temperature sensor set: • SeqOpera = 0 Cooling only • UI3 = COS REMOTE SENSOR ACCESSORIES Model no.Description S3010W1000Wall mounted temperature sensor S3020W1045 Wall mounted temperature sensor with override key and occupancy status LED Remote mount temperature sensors use 10K NTC thermistors. This sensor can be used for: • Each sensor can be configured for various averaging combinations • Optional occupancy led • Optional override key S3020W10458 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 Wall Mounted Sensor Wiring example of single remote room sensor: Wiring examples of 2 remote room sensors for averaging applications:9 Schneider Electric | II-SE7200-A4.EN.12.2015.v2 www.schneider-electric.com/buildings December 2015 Wiring examples of 3 remote room sensors for averaging applications: Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10KΩ±3%, B25/85°C = 3975K±1.5%) ºCºFKohmºCºFKohmºCºFKohmºCºFKohmºCºFKohm -40-40324.3197-20-494.514903232.1910206812.4601401045.3467 -35-31234.4009-15571.243054125.1119257710.0000451134.3881 -30-22171.3474-101454.1988105019.739030868.0694501223.6202 -25-13126.6109-52341.5956155915.628635956.5499551313.0016 CONFIGURATION AND STATUS DISPLAY INSTRUCTIONS Status display The Room Controller features a two-line, eight-character display. There is a low level backlight level that is always active and can only be seen at night. When left unattended, the Room Controller has an auto scrolling display that shows the actual status of the system. There is an option in the configuration menu to lockout the scrolling display and to only present the room temperature and conditional outdoor temperature to the user. With this option enabled, no local status is given of mode, occupancy and relative humidity. Each item is scrolled one by one with the back lighting in low level mode. Pressing any key will cause the back light to come on to high level. When left unattended for 10 seconds after changes are made, the display will resume automatic status display scrolling. To turn on the back light to high level, press any key on the front panel. The back lit display will return to low level when the Room Controller is left unattended for 45 seconds Next >