AGxx, AHxx Series 11 Erie™ Spring Return Two-Position Actuator Model Chart The PopTop™ series valve bodies and actuators provide easy installation for a variety of heating and cooling applications. The valve’s actuator can be installed after the valve body has been installed onto the fan coil, baseboard or air handler. Features: •Synchronous motor drive with spring return. •Variety of voltages available. •Mounts directly onto the body without the need for linkages or calibration. •Manual override lever on normally closed actuators. General Close-Off, 2-Position, Power (Open or Close): 9 to 11 Seconds; Spring Return (Open or Close): 4 to 5 Seconds Model No.Volts AC Electrical Position Temperature Range F (C) End Of Travel Switch Wiring AG13A01A 24 Normally Closed 32 to 200 ° F (Fluid) @ 104 ° F ( Ambient ) (0 to 93 ° C @40 ° C) YesTerminal Block AG13A020 24No 18 in. Leads AG13A02A 24Yes AG13B020 120No AG13B02A 120Yes AG13D020 208No AG13D02A 208Yes AG13T020 277No AG13T02A 277Yes AG13U020 230No AG13U02A 230Yes AG14A020 24 32 to 250 ° F (Fluid)@ 169 ° F ( Ambient ) (0 to 121 ° C @ 76 ° C) No AG14A02A 24Yes AG14B020 120No AG14B02A 120Yes AG14D020 208No AG14D02A 208Yes AG14T020 277No AG14U020 230No AG14U02A 230Yes AG23A01A 24 Normally Open (can only be used on 2-way valve) 32 to 200 ° F (Fluid)@ 104 ° F ( Ambient ) (0 to 93 ° C @40 ° C) YesTerminal Block AG23A020 24No 18 in. Leads AG23A02A 24Yes AG23B020 120No AG23B02A 120Yes AG23D020 208No AG23D02A 208Yes AG23T020 277No AG23T02A 277Yes Gxx, AHxx ries AHxx Series High Close-off AGxx Series General Close-offAGxx, AHxx Series 12 Model Chart (Continued) Model No.Volts AC Electrical Position Temperature Range F (C) End Of Travel Switch Wiring AG24T020 277 Normally Open 32 to 250 ° F (Fluid) @ 169 ° (0 to 121 ° @ 76 ° ) No 18 in. Leads AG24U020 230No High Close Off, 2-Position, Power (Open or Close): 13 to 18 Seconds; Spring Return (Open or Close): 4 to 5 Seconds AH13A020 24 Normally Closed 32 to 200 ° F (Fluid) @ 104 ° F ( Ambient ) (0 to 93 ° C @40 ° C) No 18 in. Leads AH13A02A 24Yes AH13B020 120No AH13B02A 120Yes AH13D020 208No AH13D02A 208Yes AH13T020 277No AH13T02A 277Yes AH13U020 230No AH13U02A 230Yes AH14A020 24 32 to 250 ° F (Fluid) @ 169 ° F ( Ambient ) (0 to 121 ° C @ 76 ° C) No AH14A02A 24Yes AH14B020 120No AH14B02A 120Yes AH14D020 208No AH14D02A 208Yes AH14T020 277No AH14U020 230No AH23A020 24 Normally Open (can only be used on 2-way valve) 32 to 200 ° F (Fluid) @ 104 ° F ( Ambient ) (0 to 93 ° C @40 ° C) No AH23A02A 24Yes AH23B020 120No AH23B02A 120Yes AH23U020 230No AH23U02A 230Yes AH24A020 24 32 to 250 ° F (Fluid) @ 169 ° F ( Ambient ) (0 to 121 ° C @ 76 ° C) No AH24A02A 24Yes AH24B020 120No AH24B02A 120Yes AH24D020 208No AH24D02A 208Yes AH24T020 277No AH24U020 230No AH24U02A 230YesAGxx, AHxx Series 13 Specifications Typical Applications Figure 1 Typical Wiring/Erie Terminal Block. Figure 2 Typical Wiring of a PopTop with Wire Leads. Inputs Control signalOn/off, 2 position SPST, spring return. Power 6.5 watts 7.5 VA @ 50/60 Hz. End Switch24-240 Vac/101 mA minimum to 5A maximum and 90-30 Vdc@ 100 mA maximum. Outputs Motor TypeHysteresis synchronous. Mechanical Control action: 2-way accepts N.O or N.C. actuator, 3-way N.C. (piping determines N.O./N.C. status of flow to coil.) Timing: Environment Ambient temperature limitsRefer to Model Chart. Humidity5 to 95% RH, non-condensing. Agency Listings Actuator only: CUL #MH25807, CE compliant, C-Tick Declaration (N2223). Actuator/Valve Assembly: UL #Mp916, CE Compliant. European CommunityEMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). General InstructionsRefer to F-27384 Valve Catalog, Zone Valve section. THERMOSTAT BURNER CONTROL TH TR ES ES TH/TR T T L1 L2 1 ES = End switch (optional) 1 Motor End SwitchRed To Aux. Circuit Red Black Black L1 (HOT) L2 Invensys - Erie Wire Leads THERMOSTATNext >