1 L IEBERT L IQUI - TECT ® 460 K ITS Zone Leak Detection Module With Cable Product Specification Sheet Description The Liebert Liqui-tect 460 (LT460) provides zone detection of leaks, protecting equipment by con- stantly monitoring the area for leaking liquids. The LT460 is the ideal solution for perimeter sensing or serpentine coverage of areas requiring up to 100 feet of cable. Selectable modes of operation provide flexi- ble alarming options and protection for the cable. The LT460 con- stantly monitors a zone for leaks, internal faults and power fail- ures and warns of any abnormal conditions. Top cover LEDs provide status indication and also ensure the cable is prop- erly installed and operational under raised floors. Two independent outputs provide a signal to a local alarm panel, Liebert environmental unit, remote building management system or external equip- ment, such as motorized water shut-off valves. The LT460 kit is ideally suited for the following: Applications •Glycol, Condenser Water and Chilled Water Cooling Piping Leak •Humidification Feed Water Piping •Condensate Pumps and Drains •Unit and Ceiling Auxiliary Drip Pans •Overhead Piping Troughs Locations •Large-Scale Network Control Centers •Data Centers •MRI, CAT Scan Rooms •Server Rooms - Closets •Unattended Remote Shelters •Sensitive Areas With Overhead Piping •Mechanical Equipment Rooms •Industrial Process Control Rooms Components Liqui-tect 460 Module The LT460 consists of a metal enclosure with a hinged top door providing access to the internal cir- cuit board for wiring termination and configuration of DIP switches. The LT460 will monitor up to 100 feet of connected LT500Y leak detection cable. LT500Y Leak Detection Cable The cable material and construction allow the cable to lie flat when used with hold-down clips. The LT500Y is plenum-rated and UL-listed for safe operation. •If obtained separately, cables are available in lengths of 15, 35 and 50 feet. These cables can be connected incrementally to monitor from 15 feet up to 100 feet. An end terminator and hold-down clips (two clips required for each 6-8ft. of cable) must be ordered separately. •If obtained in a kit, cables are available in lengths of 20, 25, 30, 35 and 45 feet. Cables in kits cannot be lengthened. Hold-down clips are provided. Refer to the matrix on page2 (Prepackaged Sizes for Liebert Units) to select a preconfigured kit sized to specific lengths for Liebert environmental units. Configuration Switch Settings A four-position DIP switch is used to select two alarm (filter) delays and three mutually exclusive alarm modes. The switches are located next to the wiring termination blocks. Switch Settings OFFON S1 1.Leak Detect Filter 10sec2min 2.Alarm Latch NoYes 3.Alarm Retest Delay No1hr 4.Not Used —— Contacts Rating: 24V,3A CONNECT ENCLOSURE TO EARTH GROUND TB3-3 TB3-2 TB3-1 TB2-3 TB2-2 TB2-1 TB1-2 TB1-1 Contacts Rating: 24V,3A 24V 50/60Hz 0.12A 2 1 N.C. C N.O. N.C. C N.O. ALL CIRCUITS: CLASS 2 Contacts shown in POWERED, NON-ALARM state2 Specifications Placement on Subfloor Under Cooling Support Equipment Dimensions - Top & Front Views Prepackaged Sizes for Liebert Units Leak Detection Kit Installation Suggestions Ordering Information Liqui-tect 460 Module Power requirements 24 VAC 120 mA, 50/60 Hz 3 VA (max.) Enclosure dimensions W x D x H 5.35" x 3.23" x 3.5" (135.9mm x 82mm x 88.9mm) Mounting hole dimensionsSee diagrams at right Weight (assembled)2.0 lb. (0.9 kg) Sensing cable compatibility All Liebert LT500 sensing cables Maximum length of sensing cable 100ft (30.5m) Metal enclosureNEMA 1, IP 30 Environmental Conditions Operating temperature50°F to 104°F (10°C to 40°C) Operating humidity 10% to 95% relative humidity (non-condensing) Operating altitude0 to 10,000 ft. (0 to 3,048m) Output Relays Contact rating2 Form-C, 3 A rating at 24 VAC Agency Listings ULUL916 C-ULC22.2, No. 205-M1983 CEYes FCC Compliance47 CFR, Part 15 *Output connections to external alarm monitoring panels such as the Liebert contact closure alarm panels Leak detection zone (directly beneath unit) Leak detection cable To a Liebert environmental unit and an optional* monitoring panel To external power supply or directly from unit LT460 Scenarios Upflow Unit Detection around entire unit Upflow Unit Detection on sides and in front of unit Downflow Unit Detection around entire unit Downflow Unit Detection on sides and in front of unit Distance:Distance From Unit In back On sides In front 2 ft 2 ft 2 ft (No cable) 2 ft 2 ft 1 ft 1 ft 6 ft (No cable) 1 ft 6 ft Unit (footprint-in.) P ART N UMBER Challenger (32.5 x 32.5)LT460-Z30LT460-Z20LT460-Z30LT460-Z25 Himod (69 x 35)LT460-Z35LT460-Z20LT460-Z35LT460-Z25 Deluxe System/3 (50 x 35)LT460-Z30LT460-Z20LT460-Z35LT460-Z25 (74 x 35)LT460-Z35LT460-Z20LT460-Z35LT460-Z25 (99 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30 (122 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30 DS (73 x 35)LT460-Z35LT460-Z20LT460-Z45LT460-Z30 (86 x 35) LT460-Z35LT460-Z20LT460-Z45LT460-Z30 (98 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30 (109 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30 (132 x 35)LT460-Z45LT460-Z25LT460-Z45LT460-Z30 4.75" (121mm) 4.25" (108mm) 3.25" (83mm) 4.75" (121mm) 2" (51mm) Shipping weight:2 Ibs (0.9 kg) Mounting holes:#8 screws TOP VIEW Leak detection cable connector Form-C relay outputs & power wiring connection FRONT VIEW Note: indicates placement of LT460 module 2' clearance in front 2' clearance in front 6' clearance in front 6' clearance in front PackagingQuantityProduct NumberDescription Prepackaged Kits LT460-Z20Zone Leak Detection Kit With Cable and Hold-Down Clips20-Foot Cable LT460-Z25Zone Leak Detection Kit With Cable and Hold-Down Clips25-Foot Cable LT460-Z30Zone Leak Detection Kit With Cable and Hold-Down Clips30-Foot Cable LT460-Z35Zone Leak Detection Kit With Cable and Hold-Down Clips35-Foot Cable LT460-Z45Zone Leak Detection Kit With Cable and Hold-Down Clips45-Foot Cable Available Separately LT460Zone Leak Detection Module LT500-15YLeak Detection Cable15-Foot Cable LT500-35YLeak Detection Cable35-Foot Cable LT500-50YLeak Detection Cable50-Foot Cable LT500-ETEnd Terminator for LT500Y Cable HDCHold-Down Clips3 Power Wiring The LT460 is rated for 24 VAC, 50/60 Hz and 0.12amp. Figure124V from Liebert environmental units to LT460 Figure224V from transformer to LT460 4 h a t From 24V transformer* TB1-2 TB1-1 TB1 Liebert Mini-Mate2 (1 to 5 ton)LT460 *Requires a 24V external transformer (there are no designated terminal connections on the unit) 4 h a t T5 (24V) TB1-2 TB1-1 G5 (Ground) TB1TB1 Liebert DS, Deluxe System/3, Challenger, Himod or Mini-Mate2 (8 ton)LT460 Location of T5 (24V) connection on Liebert unit From 24V transformer TB1-2 TB1-1 TB1 TransformerLT4604 © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SL-31052_REV0_06-07 Liebert Corporation 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Telephone: 1-800-877-9222 Facsimile: 1-614-841-6022 www.liebert.com Wiring to Auxiliary Alarm Panels The LT460 has two Form-C dry contact alarm output contacts (TB2 & TB3). Each contact is rated for 24 VAC at 3 amp. Figure3LT460 to Liebert environmental units Figure4LT460 to Liebert contact monitor panel TB1-2 TB2-3 (N.C.) TB2 Liebert DSLT460 TB2-2 (C) TB2-1 (N.O.) Environmental unit 24 (24V) 50, 51, 55 or 56 TB2-3 (N.C.) TB2 Liebert Deluxe System/3, Challenger, Himod or Mini-Mate2 (8 ton) LT460 TB2 Liebert Mini-Mate2 (1 to 5 ton) LT460 TB2-2 (C) TB2-1 (N.O.) TB2-3 (N.C.) TB2-2 (C) TB2-1 (N.O.) Environmental unit Environmental unit 24 (24V) 51, 55 or 56 TB1-1 (24V) TB1-2 or TB1-3 TB2-3 (N.C.) TB2-2 (C) TB2-1 (N.O.) TB2 LT460 Alarm panel Liebert contact monitor panel Input contact (N.O.)Next >