X Series Linear Actuators Specification & Installation Instructions XM-XT-190409-ESL Page | 1 Technical Data XM000 XM060 XT000 XT060 Minimum force 200N [45lbs] Power supply 22 to 26 Vac or 22 to 26 Vdc Power consumption 5VA 10VA peak, 6VA 5VA 10VA peak, 6VA Electrical connection 4-wire (except XT000 is 3-wire) halogen free cable 0.8 mm 2 [18AWG], 1 m (3.2 ft) long Control mode & signal Analog, 0-10Vdc or 2-10Vdc; 4-20mA with external 500Ω resistor Digital, 2 positions or 3 point floating Feedback signal 0-10Vdc or 2-10Vdc No feedback Running time 18.5 sec/mm - 120 sec for 6.5mm Failsafe running time No failsafe 9.2 sec/mm 60 sec for 6.5mm No failsafe 9.2 sec/mm 60 sec for 6.5mm Maximum stroke Up to 6.5 mm [¼ in], self adjustable Direction Reversible, normally up position (open) or normally down position (close) Ambient temperature 2ºC to 50ºC [36ºF to 122ºF] Storage temperature -30ºC to 50ºC [-22ºF to 122ºF] Relative humidity 5 to 95 % non condensing Medium temperature (in valve) 2ºC to 120ºC [36ºF to 248ºF] Weight 0.24 kg [0.53 lbs.] 0.3 kg [0.66 lbs.] 0.24 kg [0.53 lbs.] 0.3 kg [0.66 lbs.] Ingress protection IP54 equivalent to NEMA type 3R Country of manufacture Made in Canada Certifications Features: Power supply 24 Vac/Vdc Minimum force 200N [45lbs] Control mode: digital (XT models) or analog (XM models) Patented Enerdrive Fail-Safe System* (060 models) Auto stroke on power up (XM models) Anti-stick option (XM models) Manual override Direct or reverse acting (configurable) Status LED Standard cable 1 meter (3.2 ft) long Easy installation, no tools required Small size allows for easy installation in limited space Stall-proof, maintenance free IP54 enclosure Equal percentage available upon request (XM only) XM000 XM060 XT000 XT060 XM and XT series Specification & Installation Instructions www.neptronic.com Page | 2 Dimensions XM000 / XT000 A = 2.08” | 53mm B = 4.09” | 104mm C = 3.62” | 92mm adaptor -500 XM060 / XT060 A = 2.08” | 53mm B = 4.09” | 104mm C = 4.18” | 107mm adaptor -500 Mechanical installation Mounting of the actuated valve on system Correct mounting Incorrect mounting 1. The actuated valve installation should be easily accessible and provide sufficient clearance for service and replacement. 2. Horizontal and vertical positions are preferred orientation for the installation of actuated valve. However, this actuator can be installed at any in between angle. Caution: Do not install at more than 90º from horizontal. Mounting of the actuator on valve 1. Mount the valve adaptor to the valve and fingers tighten only. 2. Rotate knob clockwise to open the valve. Do not force knob in either direction! 3. Manually adjust the knob to test piping network. 4. Once satisfied that the network is working properly, engage the actuator over the valve adaptor and turn 30º clockwise (CW). You should hear an audible click. To disengage the actuator, press the release button while turning the actuator CCW 30º. Caution: Actuator specifically calibrated to its adapter. DO NOT exchange original adapter with a different actuator. WARNING! You must connect the actuator to its adaptor and mount it on a valve before applying power. Failure to do so will result in incorrect operation of the actuator. If you plan to add foam insulation, do not add insulation foam beyond the chrome ring and around the adaptor. Improper installation of insulation material could lead to a build-up of condensate water around the valve and the chrome ring of the adaptor, which could lead to build up of rust and compromise the structure of the chrome ring that holds the adaptor. NoXM and XT series Specification & Installation Instructions www.neptronic.com Page | 3 Wiring (XM000 & XM060) BLACK COMMON/GND RED 24 Vac / Vdc WHITE ANALOG SIGNAL FEEDBACK Wiring (XT000) 3-wire / Digital 2 positions 3-wire / Digital 3 point floating BLACK COMMON/GND WHITE OPEN CLOSE BLACK COMMON/GND WHITE OPEN CLOSE Wiring (XT060) Digital 2 positions Digital 3 point floating BLACK COMMON/GND WHITE OPEN 24 Vac / Vdc CLOSE BLACK COMMON/GND WHITE OPEN 24 Vac / Vdc CLOSE DIP Switches Each model has a different number of DIP switches, which are located behind the translucent silicone cap at the back of the actuator. Read the following sections carefully for detailed information on the different options. The DIP switches can be changed at any time. The changed option (DIP switch setting) takes effect immediately. If a change is made during an Auto-Stroke sequence (analog models only), the change takes effect once the Auto-Stroke sequence is complete (up to 240 seconds). Enerdrive* Fail Safe System The Enerdrive* system is a patented method of storing energy (using super capacitors) that is later used to drive the actuator to its failsafe position during a power failure. It takes approximately 90 seconds to fully charge the Enerdrive* system. With the restoration of power, the actuator immediately resumes operation and the Enerdrive* system is recharged. Use the Failsafe Direction DIP switch (#4 for XM060 or #2 for XT060) to set the actuator to respond according to the application requirements. Failsafe Direction Final position during failsafe operation Failsafe Direction DIP Switch (#2 or #4) Stem Down ON (default) XM and XT series Specification & Installation Instructions www.neptronic.com Page | 4 Settings: Analog Models (XM000 & XM060) Auto-Stroke Analog actuators perform an Auto-Stroke sequence upon every power-up. The Auto-Stroke sequence runs from 0 to the end position and back in order to automatically detect the stroke limits and calibrate the input signal to the detected stroke limits. The Auto-Stroke sequence can take up to a maximum of 2 minutes to complete. During the Auto-Stroke sequence, the status LED remains on and the actuator will not perform any other action. If the actuator and/or adaptor are removed from the valve after initial installation, an Auto-Stroke sequence must be initiated to recalibrate the actuator. To do so, remove and reapply the power. Rotation Direction The motor direction for analog actuators is reversible. By default, the actuator is set to reverse acting (DIP switch #1 = ON). Reverse Acting (default) DIP Switch #1 = ON Valve Closed Stem Down 0Vdc (or 2Vdc) Valve Open Stem Up 10Vdc Direct Acting DIP Switch #1 = OFF Valve Closed Stem Down 10Vdc Valve Opened Stem Up 0Vdc (or 2Vdc) XM000 XM060 XM and XT series Specification & Installation Instructions www.neptronic.com Page | 5 Settings: Digital Models (XT000 & XT060) Rotation Direction The motor direction for digital actuators is reversible. By default, the actuator is set to reverse acting (DIP switch #1 = ON). Reverse Acting (default) DIP Switch #1 = ON Valve Closed Stem Down Red Wire (CCW) Valve Open Stem Up White Wire (CW) Direct Acting DIP Switch #1 = OFF Valve Closed Stem Down White Wire (CW) Valve Opened Stem Up Red Wire (CCW) XT000 XT060 * Enerdrive Fail-Safe System: US Patent # 5,278,454 | European Patent # 0647366 Caution We strongly recommend that all Neptronic ® products be wired to a separate transformer and that transformer shall service only Neptronic ® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. Notes Recycling at end of life At end of life, please return the product to your Neptronic ® local distributor for recycling. If you need to find the nearest Neptronic ® authorized distributor, please consult www.neptronic.com. 400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com Toll free in North America: 1-800-361-2308 Tel.: (514) 333-1433 Fax: (514) 333-3163 Customer service fax: (514) 333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time) Next >