Actuators Specification & Installation Instructions TM-W RM-W-210811-ESA 1 Technical Data TM000W TM020W TM060W TM080W RM000W RM020W RM060W RM080W Auxiliary switches No Yes (2) non adjustable No Yes (2) non adjustable No Yes (2) non adjustable No Yes (2) non adjustable Fail safe - Enerdrive No Yes No Yes Power consumption 8VA 30VA peak, 8VA 10VA 30VA peak, 10VA Torque 180 in.lb. [20 Nm] at rated voltage 360 in.lb. [40 Nm] at rated voltage Weight 4.5 lbs. [2 kg] 7 lbs. [3.2 kg] Power supply 28 to 32 VDC or 22 to 26 VAC Running time through 90º 60 to 85 sec torque dependant Control signal Analog (2-10 VDC) Feedback signal 4-20mA Angle of rotation 0 to 93 degrees max., after power up automatically self adjustable to ≤ Electrical connection 1 meter long 6 wires plenum cable, 18 AWG [0.8 mm2] option 020, & 080 supplied with a second 1 meter long 3 wires plenum cable, 18 AWG [0.8 mm 2 ]. Direction of rotation Reversible, clockwise (CW) or counter clockwise (CCW) Ambient temperature 0ºF to +122ºF [-18º C to +50º C] Storage temperature -22ºF to +122ºF [-30º C to +50º C] Relative Humidity 5 to 95 % non condensing. Ingress protection IP65 equivalent to Nema type 4 with special protection against corrosive agents Warning: Do not press the clutch when actuator is powered Dimensions Dimension inch mm A 5.20 132.1 B 1.33 33.8 C 9.75 247.7 D 4.00 101.6 Caution We strongly recommend that all Neptronic® products be wired to a separate transformer and that transformer shall service only Neptronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. 1 Enerdrive System U.S.A. Patent #5,278,454 Features: ➢ IP 65 equivalent to Nema Type 4 enclosure. ➢ Dust and water proof clutch for manual adjustments. ➢ Supplied with cable (pigtail). ➢ Control signal 2-10Vdc. ➢ Fail safe by Enerdrive System1. ➢ Maintenance free. TM000W TM020W TM060W TM080W RM000W RM020W RM060W RM080W TM000W, TM020W, TM060W, TM080W RM000W, RM020W, RM060W, RM080W Specification & Installation Instructions 2 Wiring Diagrams TM000W, TM020W or RM000W, RM020W TM060W, TM080W or RM060W, RM080W Direction Selection Rotation CW (0-90º) Rotation CCW (90-0º) Leave cable #4 (Direction selection) open Connect cable #4 (Direction selection) to cable #1 (Common VAC) Fail Safe Direction Selection Fail safe (Enerdrive) is available only with “060” and “080” models. Fail safe return to 0º Fail safe return to 90º Leave cable #5 (Direction selection) open Connect cable #5 (Direction selection) to cable #1 (Common 0 VAC) Auxiliary Switches (models 020 and 080) Auxiliary switches are available only with “020” and “080” models. Auxiliary switch rating: 5 Amp resistive, 250 Vac Auto Stroke The auto stroke (actuator automatically runs from 0 to end position) is activated every time the actuator is powered up. 3 ACTUATORACTUATOR 3Next >