Actuators Specification & Installation Instructions LM-W-210802-ESA 1 Technical Data LM000W LM020W LM060W LM080W LM100W LM160W LM200W LM260W Auxiliary switches No Yes (2) non adjustable No Yes (2) non adjustable No No No No Fail safe - Enerdrive No Yes No Yes No Yes Power consumption 8VA 30VA peak, 8VA 10VA 30VA peak, 10VA 10VA 30VA peak, 10VA Power supply 28 to 32 VDC or 22 to 26 VAC 110 to 130 VAC 50/60Hz 220 to 250 VAC 50/60Hz Weight 4.5 lbs. [2 kg] 4.8 lbs. [2.2 kg] Approvals Torque 140 in.lb. [16 Nm] at rated voltage Running time through 90º 60 to 85 sec torque dependant Control signal Analog (2-10 VDC) Feedback Signal 4-20mA Angle of rotation 0 to 93 degrees max., after power up automatically self adjustable to ≤ Electrical connection 1 meter long 6 wires plenum cable, 18 AWG [0.8 mm2] Direction of rotation Reversible, clockwise (CW) or counter clockwise (CCW) Ambient temperature 0ºF to +122ºF [-18º C to +50º C] Storage temperature -22ºF to +122ºF [-30º C to +50º C] Relative Humidity 5 to 95 % non condensing. Ingress protection IP65 equivalent to Nema type 4 with special protection against corrosive agents Warning: Do not press the clutch when actuator is powered Dimensions Dimension inch mm A 5.20 132.1 B 1.33 33.8 C 9.75 247.7 D 4.00 101.6 Caution We strongly recommend that all Neptronic® products be wired to a separate transformer and that transformer shall service only Neptronic® products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. 1 Enerdrive System U.S.A. Patent #5,278,454 Features: ➢ IP 65 equivalent to Nema Type 4 enclosure. ➢ Dust and water proof clutch for manual adjustments. ➢ Supplied with cable (pigtail). ➢ Control signal 2-10Vdc. ➢ Fail safe by Enerdrive System1. ➢ Maintenance free. LM000W LM020W LM060W LM080W LM100W LM160W LM200W LM260W LM000W, LM020W, LM060W, LM080W LM100W, LM160W, LM200W, LM260W Specification & Installation Instructions 2 Wiring Diagrams LM000W & LM020W LM060W & LM080W LM100W & LM200W LM160W & LM260W Direction Selection Rotation CW (0-90º) Rotation CCW (90-0º) Leave cable #4 (Direction selection) open Connect cable #4 (Direction selection) to cable #1 (Common VAC) Fail Safe Direction Selection Fail safe (Enerdrive) is available only with “x60” and “x80” models. Fail safe return to 0º Fail safe return to 90º Leave cable #5 (Direction selection) open Connect cable #5 (Direction selection) to cable #1 (Common 0 VAC) Auxiliary Switches (models 020 and 080) Auxiliary switches are available only with “020” and “080” models. Auxiliary switch rating: 5 Amp resistive, 250 Vac Auto Stroke The auto stroke (actuator automatically runs from 0 to end position) is activated every time the actuator is powered up. 3 ACTUATOR LM000W LM020W ACTUATOR LM060W LM080W 3 ACTUATOR LM100W LM200W TB2 TB4 ACTUATOR LM160W LM260W TB2 TB4Next >