Remote I/O Communication Module Specification and Installation Instructions CMMB106-BACnet-Modbus-210713-ESA Page | 1 Models CMMB106 Description The CMMB extends your BACnet or Modbus network when your application requires additional inputs and outputs on a physical controller. Combining the 20 inputs and outputs of the CMMB with your Building Automation System provides simple expansion of a new or existing controller and reduces unnecessary costs of additional components. Features Power & Communication • 24Vac or 30Vdc supply • BACnet ® MS/TP or Modbus communication port (selectable) • Up to 2 STLD24 thermostats Inputs & Outputs • 8 universal inputs • 2 digital inputs • 2 universal outputs (supervised) • 2 analog outputs (supervised) • 6 digital outputs (supervised) Installation • 10 override switches to manually control each output • LED status indication of each input and output • DIN rail mounting • Removable, non-strip, raising clamp terminals CMMB106 Network Communication • BACnet® MS/TP or Modbus communication port (selectable via DIP switch) • Select MAC address via DIP switch or via network BACnet® • MS/TP @ 9600, 19200, 38400 or 76800 bps • Automatic baud rate detection • Automatic device instance configuration • Copy & broadcast configuration to other CMMB modules Modbus • Modbus @ 9600, 19200, 38400 or 57600 bps • RTU Slave, 8 bits (configurable parity and stop bits) • Connects to any Modbus master Technical Specifications Specifications CMMB106 Thermostats Up to 2 STLD24 thermostats (via independent Modbus network), via 4-wire connection Input Voltage 24 Vac or 27-33 Vdc Consumption 5VA (331mA @ 24 Vac) Universal Inputs (12-bit) 8 [0-10Vdc, 10KΩ (Thermistor type III), on/off (dry contact), 4-20mA] / 12-bit resolution Digital Inputs 2 [normally open/closed or direct/reverse] / 12-bit resolution Universal Outputs 2 [0-10Vdc, pulsed signal (20mA drive), on/off, 4-20mA] / 12-bit resolution Analog Outputs 2 [0-10Vdc] / 12-bit resolution Digital Relay Outputs 6 [normally open/closed, independent common per relay, 5A resistive] BACnet BACnet ® MS/TP @ 9600, 19200, 38400 or 76800 bps (BAS-C) Modbus Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration: • No parity, 2 stop bit • Even parity, 1 stop bit • Odd parity, 1 stop bit Communication Connections 24 AWG twisted-shield cable (Belden 9841 or equivalent) Electrical Connections 0.8 mm 2 [18 AWG] minimum Operational Temperature 0ºC to 50ºC [32ºF to 122ºF] Storage Temperature -30ºC to 50ºC [-22ºF to 122ºF] Relative Humidity 5 a 95% non condensed Weight 0.4 kg [0.9 lb] Dimensions A = 6.30” / 160 mm B = 5.00” / 126 mm C = 2.25” / 57 mm Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 2 Connections and Configurations Please note that all jumper settings must also be set to the same value through BACnet. Some additional configurations are only available through BACnet (see Network Conditions on page 4). Network Port | TB10 A+: BACnet/Modbus A+ B-: BACnet/Modbus B- A+ B- Universal Inputs | TB12-15 ** Selectable ** AI1:Universal Input 1 COM:Common AI2: Universal Input 2 AI3:Universal Input 3 COM:Common AI4: Universal Input 4 AI5:Universal Input 5 COM:Common AI6: Universal Input 6 AI7:Universal Input 7 COM:Common AI8: Universal Input 8 Voltage Input | TB17 ** 100mA max ** COM:Common 24V: 24 Vac or 27-33 Vdc Digital Outputs | TB4-9 NC: Normally Closed COM:Common NO:Normally Open MAC Address | DS2 The 8 DIP switches represent a binary logic to calculate the MAC address. ault = all OFF BACnet all OFF = 0 Modbus all OFF = 1 POWER STATUS AI1 COM AI2 End of Line | JP3 / JP4 None* 120 Ohms * default setting Baud Rate | DS1 12Result OFFOFF9,600 ONOFF19,200 ON38,400 ONBACnet: 70 Modbus: 50 AO1-AO4witches | SW1-SW4 Off Vdc / 0mA Auto*utomatic On0Vdc / 20mA * default setting JP3 AI1-nal | JP5-JP12 20mA 0K Ohms / on-off 10Vdc * default setting A+ B- JP4 STLD24 Port | TB11 ** 2 STLD24 thermostats ** A+: Modbus A+ B-: Modbus B-AI1AI2 AI3 COM AI4 AI4AI3 AI5AI6 AI5 COM AI6 AI7 COM AI8 AI8AI7 DI1 COM DI2 COM 24V Digital Inputs | TB16 ** Configurable ** DI1:Digital Input 1 COM:Common DI2: Digital Input 2 CM NO COM NO NC COM NO NC COM NO NC COM NO NC COM NO DO6 DO5 DO4 DO3 DO2 DO1 AO2 COM AO1 COM AO3 JP1 = AO4 JP2 = AO3 AO3-AO4 Signal | JP1-JP2 0-10 Vdc* 4-20 mA * default setting Universal Outputs | TB1 ** Selectable ** AO4:Universal Output 4 COM:Common AO3: Universal Output 3 DO1-DO6 Swites | SW5-SW10 Off = Devated (normal state) Auto*= Autatic On= Acted (opposite state) * default setting Analog Outputs | TB2 ** 0-10 Vdc ** AO2:Analog Output 2 COM:Common AO1: Analog Output 1 Network | DS1 4Mode OFFBACnet* ONModbus 3Mode Options If BACnet OFFAuto Detect* ONManual (see DS1-1 & DS1-2) If Modbus OFFConfig via Modbus Register ONNo parity, 2 stop bits * default setting BACnet/Modbus Up to two STLD24 Thermostats Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 3 MAC Address DIP Switch (DS2) MAC address for BACnet and Modbus communication, are selectable by DIP switch DS2 using binary logic. BACnet • Highest MAC address is 254. • Default is all switches OFF = MAC address 0 • If you do not change device instance in program mode, it will be automatically modified according to the MAC address. MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance 0 OFF OFF OFF OFF OFF OFF OFF OFF 153000 1 ON OFF OFF OFF OFF OFF OFF OFF 153001 2 OFF ON OFF OFF OFF OFF OFF OFF 153002 3 ON ON OFF OFF OFF OFF OFF OFF 153003 4 OFF OFF ON OFF OFF OFF OFF OFF 153004 … … … … … … … … … … 126 OFF ON ON ON ON ON ON OFF 153126 … … … … … … … … … … 254 OFF ON ON ON ON ON ON ON 153254 Modbus • Highest MAC address is 247. • Default is all switches OFF = MAC address 1 • MAC address is binary value +1 • There is no device instance for Modbus. MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 0+1 = 1 OFF OFF OFF OFF OFF OFF OFF OFF 1+1 = 2 ON OFF OFF OFF OFF OFF OFF OFF 2+1 = 3 OFF ON OFF OFF OFF OFF OFF OFF 3+1 = 4 ON ON OFF OFF OFF OFF OFF OFF 4+1 = 5 OFF OFF ON OFF OFF OFF OFF OFF … … … … … … … … … 126+1 = 127 OFF ON ON ON ON ON ON OFF … … … … … … … … … 246+1 = 247 OFF ON ON OFF ON ON ON ON LEDs Power On = Input voltage normal Off = No power Status Flashing = Normal operation (watchdog) RX/TX (BACnet) Flashing = Receiving (RX) and/or transmitting (TX) data. RX/TX (Modbus) Flashing = Receiving (RX) and/or transmitting (TX) data. Input Status On = Input on Off = Input off Flashing = Input not connected (thermistor setting only) Analog = When Universal Inputs are set to analog values (Vdc, mA, or 10KΩ); the LED intensity corresponds to the input value. For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off. Output Status On = Activated Off = Deactivated Flashing = Output pulsed Analog = When Universal and Analog outputs are set to analog values (Vdc or mA); the LED intensity corresponds to the output value. For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off. ON 1 2 3 4 5 6 7 81 2 3 4 ON DS1 Input Status LEDs (one per input) Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 4 Network Conditions Please note that all jumper settings must also be set to the same value through BACnet or Modbus. The following is a list of conditions and additional BACnet or Modbus objects. Universal Inputs (AI1-AI8) • When the jumper is set to Thermistor, you can select either °C or °F or you can set the input as a digital on/off input. • If the universal input is set as a digital on/off input, you can also set the polarity to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal. • When the jumper is set to 0-10 Vdc, you can also set the range to 0-5 Vdc. Digital Inputs (DI1-DI2) • You can set the polarity to direct or reverse. For example, in Reverse an “on” signal would be recognized as an “off” signal. Universal/Analog Outputs (AO1-AO4) • You can set the polarity to direct or reverse. For example, in reverse the output range would be 10-0 Vdc instead of 0-10 Vdc. The polarity applies to all settings 0-10Vdc, 4-20mA, on/off and pulsed. • You can also set the outputs to pulsed or digital on/off. • A fixed output value can only be modified via BACnet when the override switch is in the “Automatic” position. Digital Outputs (DO1-DO6) • A fixed output (open/closed) can only be modified via BACnet when the override switch is in the “Automatic” position. • The displayed text can be set to either Open/Closed, On/Off, or Alarm/Normal (BACnet only). Supervised Outputs • All outputs are fully supervised via BACnet. This provides the actual state of the output including any manual overrides done using the on-board switches. BACnet Objects Table ID 1 Name Description Writable? Notes (* = default) ( † = only when UniversalInputxFunction is set to 10K_Type3/G) AI.1 UniversalInput1 Universal input 1 mode selected by MSV.1 Out of service 0 to 10Volt or -40 to 100ºC (150ºC) † or -40 to 212ºF (302ºF)† or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AI.2 UniversalInput2 Universal input 2 mode selected by MSV.12 Out of service 0 to 10Volt or -40 to 100ºC (150ºC) † or -40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AI.3 UniversalInput3 Universal input 3 mode selected by MSV.15 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)† or -40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AI.4 UniversalInput4 Universal input 4 mode selected by MSV.48 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)† or -40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AI.5 UniversalInput5 Universal input 5 mode selected by MSV.57 Out of service 0 to 10Volt or -40 to 100ºC (150ºC) † or -40 to 212ºF (302ºF)† or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AI.6 UniversalInput6 Universal input 6 mode selected by MSV.58 Out of service 0 to 10Volt or -40 to 100ºC (150ºC) † or -40 to 212ºF (302ºF)† or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AI.7 UniversalInput7 Universal input 7 mode selected by MSV.59 Out of service 0 to 10Volt or -40 to 100ºC (150ºC) † or -40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AI.8 UniversalInput8 Universal input 8 mode selected by MSV.60 Out of service 0 to 10Volt or -40 to 100ºC (150ºC)† or -40 to 212ºF (302ºF) † or 4 to 20mA or 0 to 1 Resolution: 0.01Volt or 0.01ºC/0.02ºF or 0.01mA or 1 AV.52 AnalogOutput1Min Min. voltage of analog output 1 Present Value 0* Volt to AV.54 | Resolution 0.1 Volt AV.53 AnalogOutput2Min Min. voltage of analog output 2 Present Value 0* Volt to AV.55 | Resolution 0.1 Volt AV.54 AnalogOutput1Max Max. voltage of analog output 1 Present Value AV.52 to 10.0* Volt | Resolution 0.1 Volt AV.55 AnalogOutput2Max Max. voltage of analog output 2 Present Value AV.53 to 10.0* Volt | Resolution 0.1 Volt AV.72 AnalogOutput1 Analog output 1 value Present Value 0-100% | Resolution 0.1% 1 ID is equal to ObjectType.Instance Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 5 ID1 Name Description Writable? Notes (* = default) († = only when UniversalInputxFunction is set to 10K_Type3/G) AV.73 AnalogOutput2 Analog output 2 value Present Value 0-100% | Resolution 0.1% AV.118 AnalogOutput3Min Min. voltage of analog output 3 Present Value 0* Volt to AV.120 | Resolution 0.1 Volt AV.119 AnalogOutput4Min Min. voltage of analog output 4 Present Value 0* Volt to AV.121 | Resolution 0.1 Volt AV.120 AnalogOutput3Max Max. voltage of analog output 3 Present Value AV.118 to 10.0* Volt | Resolution 0.1 Volt AV.121 AnalogOutput4Max Max. voltage of analog output 4 Present Value AV.119 to 10.0* Volt | Resolution 0.1 Volt AV.124 AnalogOutput3 Analog output 3 value Present Value 0-100% | Resolution 1% AV.125 AnalogOutput4 Analog output 4 value Present Value 0-100% | Resolution 1% AV.226 UniversalInput1Offset Universal input 1 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.227 UniversalInput2Offset Universal input 2 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.228 UniversalInput3Offset Universal input 3 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.229 UniversalInput4Offset Universal input 4 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.230 UniversalInput5Offset Universal input 5 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.231 UniversalInput6Offset Universal input 6 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.232 UniversalInput7Offset Universal input 7 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.233 UniversalInput8Offset Universal input 8 offset Present Value -5.00 to 5.00 ºC/ºF/Volt/mA (default 0*) Resolution: 0.01 ºC/ºF/Volt/mA AV.235 SD1_Type_ADD Remote sensor model and Modbus address See STLD24 document for information AV.236 SD1_Baudrate Remote sensor baud rate of Modbus communication Present Value See STLD24 document for information AV.237 SD1_Firmware_version Remote sensor version See STLD24 document for information AV.238 SD1_Status_Config Remote sensor config and status Present Value See STLD24 document for information AV.239 SD1_Intern_Temp Remote sensor internal temp. See STLD24 document for information AV.240 SD1_Temp_SetPoint Remote sensor temp. setpoint Present Value See STLD24 document for information AV.241 SD1_Min_Temp_SetPoint Remote sensor min. setpoint Present Value See STLD24 document for information AV.242 SD1_Max_Temp_SetPoint Remote sensor max. setpoint Present Value See STLD24 document for information AV.243 SD1_Int_Temp_Offset Remote sensor internal temperature offset Present Value See STLD24 document for information AV.249 SD1_Extern_Temp Remote sensor external temp. See STLD24 document for information AV.250 SD1_Extern_Temp_Offset Remote sensor external temperature offset Present Value See STLD24 document for information AV.251 SD1_Button_Cfg_Status Remote sensor button configuration and status Present Value See STLD24 document for information AV.252 SD1_Let76 Remote sensor text characters 7 and 6 Present Value See STLD24 document for information AV.253 SD1_Let54 Remote sensor text characters 5 and 4 Present Value See STLD24 document for information AV.254 SD1_Let32 Remote sensor text characters 3 and 2 Present Value See STLD24 document for information AV.255 SD1_Let1 Remote sensor text character 1 Present Value See STLD24 document for information AV.256 SD1_Digit43 Remote sensor digit number 4 and 3 Present Value See STLD24 document for information AV.257 SD1_Digit21 Remote sensor digit number 2 and 1 Present Value See STLD24 document for information AV.258 SD1_Icon1 Remote sensor icon to display Present Value See STLD24 document for information AV.259 SD1_Icon1_Blink Remote sensor icon to blink Present Value See STLD24 document for information AV.260 SD1_Icon2 Remote sensor icon to display Present Value See STLD24 document for information AV.261 SD1_Icon2_Blink Remote sensor icon to blink Present Value See STLD24 document for information AV.262 SD1_Icon3 Remote sensor icon to display Present Value See STLD24 document for information AV.263 SD1_Icon3_Blink Remote sensor icon to blink Present Value See STLD24 document for information AV.264 SD2_Type_ADD Remote sensor model and Modbus address See STLD24 document for information Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 6 ID1 Name Description Writable? Notes (* = default) († = only when UniversalInputxFunction is set to 10K_Type3/G) AV.265 SD2_Baudrate Remote sensor baud rate of Modbus communication Present Value See STLD24 document for information AV.266 SD2_Firmware_version Remote sensor version See STLD24 document for information AV.267 SD2_Status_Config Remote sensor config and status Present Value See STLD24 document for information AV.268 SD2_Intern_Temp Remote sensor internal temp. See STLD24 document for information AV.269 SD2_Temp_SetPoint Remote sensor temp. setpoint Present Value See STLD24 document for information AV.270 SD2_Min_Temp_SetPoint Remote sensor min. setpoint Present Value See STLD24 document for information AV.271 SD2_Max_Temp_SetPoint Remote sensor max. setpoint Present Value See STLD24 document for information AV.272 SD2_Int_Temp_Offset Remote sensor internal temperature offset Present Value See STLD24 document for information AV.278 SD2_Extern_Temp Remote sensor external temp. See STLD24 document for information AV.279 SD2_Extern_Temp_Offset Remote sensor external temperature offset Present Value See STLD24 document for information AV.280 SD2_Button_Cfg_Status Remote sensor button configuration and status Present Value See STLD24 document for information AV.281 SD2_Let76 Remote sensor text characters 7 and 6 Present Value See STLD24 document for information AV.282 SD2_Let54 Remote sensor text characters 5 and 4 Present Value See STLD24 document for information AV.283 SD2_Let32 Remote sensor text characters 3 and 2 Present Value See STLD24 document for information AV.284 SD2_Let1 Remote sensor text character 1 Present Value See STLD24 document for information AV.285 SD2_Digit43 Remote sensor digit number 4 and 3 Present Value See STLD24 document for information AV.286 SD2_Digit21 Remote sensor digit number 4 and 3 Present Value See STLD24 document for information AV.287 SD2_Icon1 Remote sensor icon to display Present Value See STLD24 document for information AV.288 SD2_Icon1_Blink Remote sensor icon to blink Present Value See STLD24 document for information AV.289 SD2_Icon2 Remote sensor icon to display Present Value See STLD24 document for information AV.290 SD2_Icon2_Blink Remote sensor icon to blink Present Value See STLD24 document for information AV.291 SD2_Icon3 Remote sensor icon to display Present Value See STLD24 document for information AV.292 SD2_Icon3_Blink Remote sensor icon to blink Present Value See STLD24 document for information AV.467 NumberOfSlaveSensor Number of remote sensors Present Value 0*-2 (# of STLD24 connected to CMMB) AV.468 CopyCfgStartAdd Copy configuration start address Present Value 0-254 Address of first CMMB to copy Available only if BV.101 is set to No AV.469 CopyCfgEndAdd Copy configuration end address Present Value AV.468 – (AV.468 + 64) Address of last CMMB to copy Available only if BV.101 is set to No AV.470 CopyCfgResult2 Copy configuration result Present Value AV.468 – AV.469 Result of copy is available on Description property and is available only if BV.101 is set to Yes. Results: Succeed, Prog_Error, Type_Error, Model_Error, FW_Error, Mem_Error, Size_Error, Comm_Error, SlaveDevice, InProgress, AllSucceed AV.500 U1_MinInputValue Universal input 1 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.501 U1_MaxInputValue Universal input 1 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.502 U1_MinValue Universal input 1 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.503 U1_MaxValue Universal input 1 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.504 U2_MinInputValue Universal input 2 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.505 U2_MaxInputValue Universal input 2 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.506 U2_MinValue Universal input 2 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 2 Write 526address in present value, result will be available in description. Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 7 ID1 Name Description Writable? Notes (* = default) († = only when UniversalInputxFunction is set to 10K_Type3/G) AV.507 U2_MaxValue Universal input 2 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.508 U3_MinInputValue Universal input 3 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.509 U3_MaxInputValue Universal input 3 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.510 U3_MinValue Universal input 3 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.511 U3_MaxValue Universal input 3 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.512 U4_MinInputValue Universal input 4 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.513 U4_MaxInputValue Universal input 4 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.514 U4_MinValue Universal input 4 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.515 U4_MaxValue Universal input 4 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.516 U5_MinInputValue Universal input 5 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.517 U5_MaxInputValue Universal input 5 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.518 U5_MinValue Universal input 5 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.519 U5_MaxValue Universal input 5 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.520 U6_MinInputValue Universal input 6 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.521 U6_MaxInputValue Universal input 6 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.522 U6_MinValue Universal input 6 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.523 U6_MaxValue Universal input 6 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.524 U7_MinInputValue Universal input 7 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.525 U7_MaxInputValue Universal input 7 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.526 U7_MinValue Universal input 7 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.527 U7_MaxValue Universal input 7 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.528 U8_MinInputValue Universal input 8 minimum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.529 U8_MaxInputValue Universal input 8 maximum input value Present Value 0-10Volt or 4-20mA, Resolution: 0.01Volt or 0.01mA AV.530 U8_MinValue Universal input 8 minimum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.531 U8_MaxValue Universal input 8 maximum scaled value Present Value -32768 to 32767, Resolution: 0.01 AV.532 AO1FailsafePreset Analog output 1 failsafe preset value Present Value 0 to 100%, Resolution: 0.1% AV.533 AO2FailsafePreset Analog output 2 failsafe preset value Present Value 0 to 100%, Resolution: 0.1% AV.534 AO3FailsafePreset Analog output 3 failsafe preset value Present Value 0 to 100%, Resolution: 0.1% AV.535 AO4FailsafePreset Analog output 4 failsafe preset value Present Value 0 to 100%, Resolution: 0.1% AV.536 TimeoutValue Network Timeout value Present Value 30 to 600 sec, Resolution: 1 sec BI.1 DigitalInput1 Digital input 1 status Out of service 0= Open / Ouvert * 1= Close / Fermé Text depends of selection in MSV.76 BI.2 DigitalInput2 Digital input 2 status Out of service 0= Open / Ouvert * 1= Close / Fermé Text depends of selection in MSV.77 BV.22 ContactOutput1 Digital output 1 status Present Value 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.66 Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 8 ID1 Name Description Writable? Notes (* = default) († = only when UniversalInputxFunction is set to 10K_Type3/G) BV.23 ContactOutput2 Digital output 2 status Present Value 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.67 BV.24 ContactOutput3 Digital output 3 status Present Value 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.68 BV.25 ContactOutput4 Digital output 4 status Present Value 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.69 BV.26 ContactOutput5 Digital output 5 status Present Value 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.70 BV.27 ContactOutput6 Digital output 6 status Present Value 0= Open / Ouvert / Off / Arret / Normal * 1= Close / Fermé / On / Marche / Alarm Text depends of selection in MSV.71 BV.33 DigitalInput1Polarity Polarity of digital input 1 Present Value 0= Direct * 1= Reverse BV.34 DigitalInput2Polarity Polarity of digital input 2 Present Value 0= Direct * 1= Reverse BV.66 AnalogOutput1Direction Polarity of analog output 1 Present Value 0= Direct * 1= Reverse BV.67 AnalogOutput2Direction Polarity of analog output 2 Present Value 0= Direct * 1= Reverse BV.68 AnalogOutput3Direction Polarity of analog output 3 Present Value 0= Direct * 1= Reverse BV.69 AnalogOutput4Direction Polarity of analog output 4 Present Value 0= Direct * 1= Reverse BV.93 UI1_DI_Polarity Polarity of universal input 1 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.94 UI2_DI_Polarity Polarity of universal input 2 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.95 UI3_DI_Polarity Polarity of universal input 3 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.96 UI4_DI_Polarity Polarity of universal input 4 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.97 UI5_DI_Polarity Polarity of universal input 5 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.98 UI6_DI_Polarity Polarity of universal input 6 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.99 UI7_DI_Polarity Polarity of universal input 7 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.100 UI8_DI_Polarity Polarity of universal input 8 when used in digital input mode Present Value 0= Direct * 1= Reverse BV.101 CopyCfgExecute Start or stop copy configuration Present Value 0= No * 1= Yes Start copy and give results, must be reset by user. BV.102 SystemUnit Select the unit system to use on the device Present Value 0= Celsius * 1= Fahrenheit BV.103 Inhibit Output Override Inhibit the override of the outputs Present Value 0= Off * 1= On BV.104 TimeoutStatus Network timeout status 0= Inactive * 1= Active MSV.1 UniversalInput1Function Selected analog input 1 mode Present Value 1= 0_10Volt 2= 4_20mA 3= 10K_Type3/G * 4= 10K_Type3A1 5= 10K_Type4A1 6= 10K_Type2 7= 20K_Type6A1 8= 30K_Type6A1 9= DigitalInput 10= ScaledValue_Volt 11= ScaledValue_mA Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 9 ID1 Name Description Writable? Notes (* = default) († = only when UniversalInputxFunction is set to 10K_Type3/G) MSV.12 UniversalInput2Function Selected analog input 2 mode Present Value 1= 0_10Volt 2= 4_20mA 3= 10K_Type3/G * 4= 10K_Type3A1 5= 10K_Type4A1 6= 10K_Type2 7= 20K_Type6A1 8= 30K_Type6A1 9= DigitalInput 10= ScaledValue_Volt 11= ScaledValue_mA MSV.15 UniversalInput3Function Selected analog input 3 mode Present Value 1= 0_10Volt 2= 4_20mA 3= 10K_Type3/G * 4= 10K_Type3A1 5= 10K_Type4A1 6= 10K_Type2 7= 20K_Type6A1 8= 30K_Type6A1 9= DigitalInput 10= ScaledValue_Volt 11= ScaledValue_mA MSV.48 UniversalInput4Function Selected analog input 4 mode Present Value 1= 0_10Volt 2= 4_20mA 3= 10K_Type3/G * 4= 10K_Type3A1 5= 10K_Type4A1 6= 10K_Type2 7= 20K_Type6A1 8= 30K_Type6A1 9= DigitalInput 10= ScaledValue_Volt 11= ScaledValue_mA MSV.54 AnalogOutput1Mode Select analog output 1 mode Present Value 1= Analog * 2= On_Off 3= Pulsing MSV.55 AnalogOutput2Mode Select analog output 2 mode Present Value 1= Analog * 2= On_Off 3= Pulsing MSV.57 UniversalInput5Function Selected analog input 5 mode Present Value 1= 0_10Volt 2= 4_20mA 3= 10K_Type3/G * 4= 10K_Type3A1 5= 10K_Type4A1 6= 10K_Type2 7= 20K_Type6A1 8= 30K_Type6A1 9= DigitalInput 10= ScaledValue_Volt 11= ScaledValue_mA MSV.58 UniversalInput6unction Selected analog input 6 mode Present Value 1= 0_10Volt 2= 4_20mA 3= 10K_Type3/G * 4= 10K_Type3A1 5= 10K_Type4A1 6= 10K_Type2 7= 20K_Type6A1 8= 30K_Type6A1 9= DigitalInput 10= ScaledValue_Volt 11= ScaledValue_mA MSV.59 UniversalInput7Function Selected analog input 7 mode Present Value 1= 0_10Volt 2= 4_20mA 3= 10K_Type3/G * 4= 10K_Type3A1 5= 10K_Type4A1 6= 10K_Type2 7= 20K_Type6A1 8= 30K_Type6A1 9= DigitalInput 10= ScaledValue_Volt 11= ScaledValue_mA Next >