Remote I/O Communication Module Specification and Installation Instructions CMMB1020-211124-ESA Page | 1 Models CMMB1020 Description The CMMB1020 extends your BACnet or Modbus network when your application requires additional inputs and outputs on a physical controller. Capitalizing on the high-density I/O point count of 30 universal inputs and 20 outputs enables the CMMB1020 to provide a cost effective yet advanced integration capability. Features Power & Communication • 24Vac or 24Vdc supply • BACnet ® MS/TP or Modbus communication port (selectable) Inputs & Outputs • 30 universal inputs • 4 universal outputs • 4 analog outputs • 12 binary outputs Installation • LED status indication of each output • DIN rail mounting • Removable, non-strip, raising clamp terminals Other • 16-bit A/D Converter for greater resolution • Supports Pt1000 and Ni1000 CMMB1020 Network Communication • BACnet ® MS/TP or Modbus communication ports (selectable via DIP switch) • Select MAC address via DIP switch or via network BACnet ® • MS/TP @ 9600, 19200, 38400, 76800 or 115000 bps • Automatic baud rate detection • Automatic device instance configuration • Improved BACnet Stack • Firmware upgradable via BACnet • Expansion slot for connection to Neptronic RPB BACnet Router Modbus • Modbus @ 9600, 19200, 38400 or 57600 bps • RTU Slave, 8 bits (configurable parity and stop bits) • Connects to any Modbus master Technical Specifications Specifications CMMB1020 Input Voltage 24 Vac/Vdc ±10% Consumption 12VA Universal Inputs 30 [0-10Vdc, 2-10Vdc, Thermistor, on/off (dry contact), 0-20mA, 4-20mA] / 16-bit resolution Universal Outputs 4 [0-10Vdc, on/off] / 12-bit resolution Analog Outputs 4 [0-10Vdc] / 12-bit resolution Digital Relay Binary Outputs 12 [normally open, independent common per relay, 5A resistive] Service Port BACnet® MS/TP @ 38400 bps Communication Port BACnet® MS/TP @ 9600, 19200, 38400, 76800 or 115000 bps (BAS-C). Modbus RTU slave @ 9600, 19200, 38400 or 57600. Selectable parity and stop bit configuration: • No parity, 2 stop bit • Even parity, 1 stop bit • Odd parity, 1 stop bit Communication Connections 24 AWG twisted-shield cable (Belden 9841 or equivalent) Electrical Connections 0.8 mm 2 [18 AWG] minimum Operational Temperature 0ºC to 50ºC [32ºF to 122ºF] Storage Temperature -30ºC to 50ºC [-22ºF to 122ºF] Relative Humidity 5 to 95% non condensed Weight 0.6 kg [1.3 lb] Dimensions A = 9.18” / 233 mm B = 4.93” / 125 mm C = 2.27” / 58 mm Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 2 Connections and Configurations Please note that all jumper settings must also be set to the same value through BACnet. Some additional configurations are only available through BACnet. Universal Outputs | TB4-5 ** 350mAmax (each) ** COM:Relay Common NO:Normally Open Universal Inputs | TB10-17 ** Selectable ** AI1:Universal Input 1 AI2: Universal Input 2 COM:Common AI3:Universal Input 3 AI4: Universal Input 4 AI5:Universal Input 5 AI6: Universal Input 6 COM:Common AI7:Universal Input 7 AI8: Universal Input 8 AI9:Universal Input 9 AI10: Universal Input 10 COM:Common AI11:Universal Input 11 AI12: Universal Input 12 AI13:Universal Input 13 AI14: Universal Input 14 COM:Common AI15:Universal Input 15 AI16: Universal Input 16 AI17:Universal Input 17 AI18: Universal Input 18 COM:Common AI19:Universal Input 19 AI20: Universal Input 20 AI21:Universal Input 21 AI22: Universal Input 22 COM:Common AI23:Universal Input 23 AI24: Universal Input 24 AI25:Universal Input 25 AI26: Universal Input 26 COM:Common AI27:Universal Input 27 AI28: Universal Input 28 AI29:Universal Input 29 AI30: Universal Input 30 COM:Common COM: Common AI1 Power Input | TB18 ** 500mA max ** COM:Common (GND) 24V:24Vac or 24Vdc POWER AI2 COM AI3 AI4 AI5 AI6 COM AI7 AI8 AI9 AI10 COM AI11 AI12 AI13 AI14 COM AI15 AI16 AI17 AI18 COM AI19 AI20 AI21 AI22 COM AI23 AI24 AI25 AI26 COM AI27 AI28 AI29 AI30 COM COM COM 24V COM B- A+ COM B- A+ AO1 STATUS PCB POWER JP1 JP2 JP3 JP4 JP5 JP6 COM Port | TB2 ** Baud rate and MAC address based on DS1 & DS2 selection ** COM: Common B-: BACnet/Modbus B- A+: BACnet/Modbus A+ Analog Outputs | TB3 ** 0-10 Vdc (1.5mA max) ** AO1: Analog Output 1 AO2: Analog Output 2 AO COM: Common AO3: Analog Output 3 AO4: Analog Output 4 Binary Outputs | TB6-9 NO:Normally Open COM:Relay Common ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 RXD TXD TXD RXD DS2DS1 Not Used Modbus Mode Options | DS2 56Result OFFOFFNo parity, 2 stop bits* OFFONEven parity, 1 stop bit ONOFFOdd parity, 1 stop bit * default setting Service Port | TB1 ** Baud rate of 38,400 bps ** COM: Common B-: BACnet B A+: BACnet A+ MAC Address | DS1 The 8 DIP switches represent a binary logic to calculate the MAC address. Default = 101 BACnet all OFF = 0 Modbus all OFF = 1 Baud Rate | DS2 234Result OFFOFFOFFAuto Detect ONOFFOFF9600 OFFONOFF19,200 ONONOFF38,400 OFF OFFON57,600* ONOFFON 76,800** OFFON ON115,200** * default setting ** only available for BACnet UO1-UO4 Selector | JP3-JP6 Analog Output Binary Output* * default setting Network | DS2 1Mode OFFBACnet ONModbus* * default setting End of Line | JP1-JP2 120 Ohms* None * default setting COM NO COM NO COM NO Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 3 FCC Compliance WARNING: Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: • Reorient or relocate the receiving antenna. • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. • Consult the dealer or an experienced radio/TV technician for help. MAC Address DIP Switch (DS1) MAC address for BACnet and Modbus communication, are selectable by DIP switch DS1 using binary logic. BACnet • Highest MAC address is 254. • Default is all switches OFF = MAC address 0 • If you do not change device instance in program mode, it will be automatically modified according to the MAC address. MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance 0 OFF OFF OFF OFF OFF OFF OFF OFF 153000 1 ON OFF OFF OFF OFF OFF OFF OFF 153001 2 OFF ON OFF OFF OFF OFF OFF OFF 153002 3 ON ON OFF OFF OFF OFF OFF OFF 153003 4 OFF OFF ON OFF OFF OFF OFF OFF 153004 … … … … … … … … … … 126 OFF ON ON ON ON ON ON OFF 153126 … … … … … … … … … … 254 OFF ON ON ON ON ON ON ON 153254 Modbus • Highest MAC address is 247. • Default is all switches OFF = MAC address 1. • There is no device instance for Modbus. MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 1 OFF OFF OFF OFF OFF OFF OFF OFF 1 ON OFF OFF OFF OFF OFF OFF OFF 2 OFF ON OFF OFF OFF OFF OFF OFF 3 ON ON OFF OFF OFF OFF OFF OFF 4 OFF OFF ON OFF OFF OFF OFF OFF … … … … … … … … … 126 OFF ON ON ON ON ON ON OFF … … … … … … … … … 247 ON ON ON OFF ON ON ON ON Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 4 LEDs JP6 POWER STATUS JP1 JP2 JP3 JP4 JP5 RXD TXD TXD RXD Output Status LEDs (one per output) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Power On = Input voltage normal Off = No power Status Flashing = Normal operation (watchdog) RX/TX (BACnet) Flashing = Receiving (RX) and/or transmitting (TX) data. RX/TX (Modbus) Flashing = Receiving (RX) and/or transmitting (TX) data. Output Status On = Activated Off = Deactivated Analog = When Universal and Analog outputs are set to analog values (Vdc); the LED intensity corresponds to the output value. For example: At 10Vdc, the LED will be fully on. At 5Vdc, the LED will be at 50% intensity. At 0 Vdc, the LED will be off. UO in AO Mode – Wiring Example AO1 AO2 AO COM AO4 AO3 COM JP3 JP4 COM 10VDC UO1 when used as AO5 - + Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 5 Modbus Network Conditions Modbus Registers and their Relevance Based on Different Input Modes Voltage/Current Mode: • When UI1 is configured as 0-10VDC or 4-20mA, the raw voltage/current value is seen on register 40012 (Universal Input 1 Reading). • The value seen in register 40051 (Universal Input 1 Impedance or Linearization) will be based on the value that is entered by the user for registers 40118 (Universal Input 1 Minimum Linear Value) and 40119 (Universal Input 1 Maximum Linear Value). • The register 40115 (Universal Input 1 Linear Value Scale) functions as scaling for the linearized value that you see for register 40051. • The range of the sensor/input type (2-10V or 4-20mA) is set by registers 40116 (Universal Input 1 Minimum Voltage) and 40117 (Universal Input 1 Maximum Voltage) and the linearized value is read on register 40051. • The register 40120 (Universal Input 1 Linear Value Bias) adds a bias to the value read on register 40051. • The same is applicable for UI2 to UI30 with the registers corresponding to minimum and maximum voltage and/or linear values. Thermistor Mode: • When UI1 is configured as a temperature sensor, the raw resistance value is seen on register 40051 and the temperature value based on the type of sensor selected is available on register 40012. • The user can perform calibration of the temperature value by adding a reading bias on register 40114. The value set here affects the reading on register 40012. • The same is applicable for UI2 to UI30 with the registers corresponding to minimum and maximum voltage and/or linear values. UO1 to UO4 Operation • UO1 to UO4 can be configured to operate as an analog output or a binary output using jumpers JP3 to JP6. • When using UO1 to UO4 as BO13-BO16 through the jumpers, the user must ensure not to write on the registers for AO5-AO8 as it will interfere with the LED operation and the failsafe modes. • The failsafe presets for the unused/unrouted outputs (AO5 to AO8) in this case must be set to the value required for safe operation of the equipment. • When using UO1 to UO4 as AO5-AO8 through the jumpers, the user must ensure not to write on the bits for BO13- BO16 as it will interfere with the LED operation and the failsafe modes. • The failsafe presets for the unused/unrouted outputs (AO5 to AO8) in this case must be set to the value required for safe operation of the equipment. Universal Input Mode Default Settings Cfg UI.x Mode (Reg. # for UI1: 112/40113) Cfg UI.x Reading Bias (113/40114) Cfg UI.xLinear Value Scale (114/40115) Cfg UI.x Min Voltage (115/40116) Cfg UI.x Max Voltage (116/40117) Cfg UI.x Min Linear Value (117/40118) Cfg UI.x Max Linear Value (118/40119) Cfg UI.x Linear Value Bias (119/40120) 1= "0-10V" N/A 1 0 10000 0 100 0 2= "4-20mA" N/A 1 0 20000 0 100 0 3= "Dry Contact" N/A N/A N/A N/A N/A N/A N/A 4-8 = Thermistors 0 N/A N/A N/A N/A N/A N/A Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 6 BACnet Objects Table ID 1 Name Description Writable? Range AI.1 UI1 Reading Universal input 1 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.2 UI2 Reading Universal input 2 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.3 UI3 Reading Universal input 3 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.4 UI4 Reading Universal input 4 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.5 UI5 Reading Universal input 5 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 302ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.6 UI6 Reading Universal input 6 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.7 UI7 Reading Universal input 7 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.8 UI8 Reading Universal input 8 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.9 UI9 Reading Universal input 9 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.10 UI10 Reading Universal input 10 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.11 UI11 Reading Universal input 11 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.12 UI12 Reading Universal input 12 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.13 UI13 Reading Universal input 13 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.14 UI14 Reading Universal input 14 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.15 UI15 Reading Universal input 15 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.16 UI16 Reading Universal input 16 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 1 ID is equal to ObjectType.Instance Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 7 ID 1 Name Description Writable? Range AI.17 UI17 Reading Universal input 17 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.18 UI18 Reading Universal input 18 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.19 UI19 Reading Universal input 19 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.20 UI20 Reading Universal input 20 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.21 UI21 Reading Universal input 21 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.22 UI22 Reading Universal input 22 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.23 UI23 Reading Universal input 23 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.24 UI24 Reading Universal input 24 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.25 UI25 Reading Universal input 25 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.26 UI26 Reading Universal input 26 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.27 UI27 Reading Universal input 27 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.28 UI28 Reading Universal input 28 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.29 UI29 Reading Universal input 29 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AI.30 UI30 Reading Universal input 30 Reading Out of service COV Increment 0 to 10Volt or -40 to 150ºC or -40 to 212ºF or 0 to 20mA or 0 to 1 Resolution: 0.001Volt or 0.01ºC/0.02ºF or 0.001mA or 1 AO.1 AO1 Voltage Voltage of analog output 1 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt AO.2 AO2 Voltage Voltage of analog output 2 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt AO.3 AO3 Voltage Voltage of analog output 3 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt AO.4 AO4 Voltage Voltage of analog output 4 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt AO.5 AO5 Voltage* Voltage of analog output 5 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt AO.6 AO6 Voltage* Voltage of analog output 6 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 8 ID 1 Name Description Writable? Range AO.7 AO7 Voltage* Voltage of analog output 7 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt AO.8 AO8 Voltage* Voltage of analog output 8 Out of service Present Value 0 to 10 Volt | Resolution 0.001 Volt AV.1 UI1 Impedance Universal Input 1 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.2 UI2 Impedance Universal Input 2 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.3 UI3 Impedance Universal Input 3 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.4 UI4 Impedance Universal Input 4 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.5 UI5 Impedance Universal Input 5 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.6 UI6 Impedance Universal Input 6 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.7 UI7 Impedance Universal Input 7 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.8 UI8 Impedance Universal Input 8 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.9 UI9 Impedance Universal Input 9 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.10 UI10 Impedance Universal Input 10 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.11 UI11 Impedance Universal Input 11 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.12 UI12 Impedance Universal Input 12 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.13 UI13 Impedance Universal Input 13 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.14 UI14 Impedance Universal Input 14 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.15 UI15 Impedance Universal Input 15 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.16 UI16 Impedance Universal Input 16 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.17 UI17 Impedance Universal Input 17 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.18 UI18 Impedance Universal Input 18 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.19 UI19 Impedance Universal Input 19 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.20 UI20 Impedance Universal Input 20 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.21 UI21 Impedance Universal Input 21 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.22 UI22 Impedance Universal Input 22 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.23 UI23 Impedance Universal Input 23 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.24 UI24 Impedance Universal Input 24 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.25 UI25 Impedance Universal Input 25 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.26 UI26 Impedance Universal Input 26 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.27 UI27 Impedance Universal Input 27 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.28 UI28 Impedance Universal Input 28 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.29 UI29 Impedance Universal Input 29 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms AV.30 UI30 Impedance Universal Input 30 Impedance Out of service 0 to 100% or 0 to 806800 ohms Resolution: 1% or 1 ohms Remote I/O Communication Module Specification and Installation Instructions www.neptronic.com Page | 9 ID 1 Name Description Writable? Range AV.31 Cfg AO1 Failsafe Preset Failsafe preset for analog output 1 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt AV.32 Cfg AO2 Failsafe Preset Failsafe preset for analog output 2 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt AV.33 Cfg AO3 Failsafe Preset Failsafe preset for analog output 3 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt AV.34 Cfg AO4 Failsafe Preset Failsafe preset for analog output 4 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt AV.35 Cfg AO5 Failsafe Preset* Failsafe preset for analog output 5 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt AV.36 Cfg AO6 Failsafe Preset* Failsafe preset for analog output 6 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt AV.37 Cfg AO7 Failsafe Preset* Failsafe preset for analog output 7 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt AV.38 Cfg AO8 Failsafe Preset* Failsafe preset for analog output 8 Out of service Present Value 0 to 10Volt | Resolution: 0.001Volt BO.1 BO1 State Binary Output 1 State Out of service Present Value 0 = Open 1 = Closed BO.2 BO2 State Binary Output 2 State Out of service Present Value 0 = Open 1 = Closed BO.3 BO3 State Binary Output 3 State Out of service Present Value 0 = Open 1 = Closed BO.4 BO4 State Binary Output 4 State Out of service Present Value 0 = Open 1 = Closed BO.5 BO5 State Binary Output 5 State Out of service Present Value 0 = Open 1 = Closed BO.6 BO6 State Binary Output 6 State Out of service Present Value 0 = Open 1 = Closed BO.7 BO7 State Binary Output 7 State Out of service Present Value 0 = Open 1 = Closed BO.8 BO8 State Binary Output 8 State Out of service Present Value 0 = Open 1 = Closed BO.9 BO9 State Binary Output 9 State Out of service Present Value 0 = Open 1 = Closed BO.10 BO10 State Binary Output 10 State Out of service Present Value 0 = Open 1 = Closed BO.11 BO11 State Binary Output 11 State Out of service Present Value 0 = Open 1 = Closed BO.12 BO12 State Binary Output 12 State Out of service Present Value 0 = Open 1 = Closed BO.13 BO13 State* Binary Output 13 State Out of service Present Value 0 = Open 1 = Closed BO.14 BO14 State* Binary Output 14 State Out of service Present Value 0 = Open 1 = Closed BO.15 BO15 State* Binary Output 15 State Out of service Present Value 0 = Open 1 = Closed BO.16 BO16 State* Binary Output 16 State Out of service Present Value 0 = Open 1 = Closed BV.1 Cfg Temperature Units Select the unit system to use on the device. Present Value 0= Celsius 1= Fahrenheit MSV.0 Cfg IO Profile Select input/output profile. Out of service Present Value 1= Custom 2= Profile 1 3= Profile 2 4= Profile 3 MSV.1 Cfg UI1 Mode Select universal input 1 mode Out of service Present Value 1= 0-10V 2= 4-20mA 3= Dry Contact 4= 10K Type3/G/4A1 5= 10K Type2/3A1/NTC(Danfoss) 6= 10K_ NTC Carel 7= 20K Type6A1 8= 30K Type6A1 Next >