Contacts Converter Specification & Installation Instructions CCCseries 100426.doc/100426 1 Technical Data Contact Converter series models CCC013-07 CCC014-07 CCC015-07 CCC023-07 CCC024-07 CCC025-07 CCC713-07 CCC714-07 CCC715-07 CCC723-07 CCC724-07 CCC725-07 Number of Outputs 3 on/off outputs 4 on/off outputs 5 on/off outputs 3 on/off outputs 4 on/off outputs 5 on/off outputs Power supply 110 to 130 Vac 1 phase 50/60Hz 220 to 240 Vac 1phase 50/60Hz Contacts ratings Resistive: 7 Amp / 1680 W ; Motor and or compressor: ¼ Hp / 10 LRA / 2.5 FLA approved for 30,000 operations at 240 Vac Extra Low Voltage Power output 24 Vac / 0.5A, 12 VA max Electrical connection 0.8 mm 2 [18 AWG] minimum Software type Type A Degree of Pollution Suitable for use in normal pollution situation Operating temperature 0ºC to 50ºC [32ºF to 122ºF] Storage & transport temperature -30ºC to 50ºC [-22ºF to 122ºF] Relative Humidity 5 to 95 % non condensing Weight 400 g. [0.9 lb] Risk of electric shock. Disconnect power supply before connection and/or servicing. ! Installation should be done by skilled and qualified technician Observe local regulations concerning provision of electrical installation For installation in electrical compartment. Dimensions CCC 7XX series (with enclosure) A D E F CB Dimension Imperial (in) Metric (mm) A5.18 131.5 B 1.81 45.9 C 4.57 116.1 D5.67 144.0 E 4.73 120.2 F 2.02 51.2 Holes Dia. 0.188 4.77 CCC 0XX series (without enclosure) A BC D F G Dimension Imperial (in) Metric (mm) A 4.25 108.0 B3.01 76.5 C 3.50 88.9 D 4.65 118.1 F 1.77 45.0 G 0.37 9.5 Holes Dia. 0.167 4.24 Features: • LED indication of relay Status • Quality “non strip” Terminals • 120 Vac or 230 Vac fused and 24 Vac thermal fuse • Captive screw for enclosure cover • Designed to operate with TFC series thermostat. Without enclosure With enclosure CCC013-07 CCC713-07 CCC014-07 CCC714-07 CCC015-07 CCC715-07 CCC023-07 CCC723-07 CCC024-07 CCC724-07 CCC025-07 CCC725-07 CCC Series Specification & Installation Instructions 2 Mechanical Installation CCCxxx series contact converter can be attached directly on wall or ventilation duct with self tapping screws (not included). Hinged cover of CCC7xx series contact converter with enclosure is maintained with 1 screw located on top. Electrical installation Terminal description Typical Applications (connection with TFC series thermostat) Terminals TB1 (Power Supply) Output 24 VAC / 0.5A TO1 DO3 DO2 DO1 TO2 Common External Sensor Output NSB Output Digital output signal selector on 24V 123456789 COM 24VAC EXT.TS OCCUP.STA TO1TO2 DO1DO2DO3 Thermostat Terminal JP2 JP2.1-2:24V JP2.2-3:COM Output 24 VAC / 0.5ATO1TO2CommonExternal C/O Sensor InputNSB Input Fan Fan relays 240 Vac TB1 TB2 TB4 TB5 9 8 7 6 5 4 3 2 1 1 2 1 2 3 4 1 2 3 4 5 6 TB3 1 2 3 High Voltage 240 Vac Cooling and heating ON/OFF valve High Low Medium Power supply 240 VAC Return Line GROUND THE CONTROL MUST BE CONNECTED TO EARTH WITH THE AID OF THE GROUND LUG LOCATED ON THE METAL BASE 1- Neutral 2- Line Terminals TB2 (Fan - Line voltage) 1- Neutral 2- High speed (DO1) 3- Medium speed (DO2) 4- Low speed (DO3) Terminals TB3 (Other contact –Line voltage) 1- Neutral 2- Line voltage Output 1 3- Line voltage Output 2 Terminals TB4 (From Thermostat) 1- Common 2- 24 Vac Output 3- Output 1 (External sensor) 4- Output 2 (Night Set Back) 5- Triac Input 1 (TO1) 6- Triac Input 2 (TO2) 7- Digital Input1 (DO1) (Fan speed High) 8- Digital Input2 (DO2) (Fan speed Medium) 9- Digital Input3 (DO3) (Fan speed Low) Terminals TB5 (Input / Output) 1- Common 2- 24 Vac Output 3- Input 1 (External sensor) 4- Input 2 (Night Set Back) 5- Triac Output 1 (TO1) 6- Triac Output 2 (TO2) Recycling at end of life At end of life, please return the thermostat to your Neptronic ® local distributor for recycling. If you need to find the nearest Neptronic ® authorized distributor, please consult www.neptronic.com. Next >