Refer to the QuickLIT website for the most up-to-date version of this document.TE-6800 Series Temperature Sensors Product Bulletin1The TE-68xx-xN00S Series provides temperature sensing in room wall mount applications. It allows local setpoint temperature adjustment and temporary occupancy override. A warmer/cooler dial is included on certain models for minor temperature adjustments from the setpoint. An occupancy override button allows the user to request a time-of-day scheduling override when the space is occupied outside of the normal occupied hours schedule. All sensors have DIP switches that enable or disable unit functions.Depending on the model chosen, the wires connecting the sensor to the controller can be terminated using a screw terminal block or modular jack connection, offering wiring flexibility. All models include a Zone Bus access port for connecting accessories to access the 6-pin modular jack. This feature allows a technician tocommission or service the controller via the sensor.Figure 1: TE-6800 Series Temperature SensorsTable 1: Features and BenefitsFeaturesBenefitsController Configuration SwitchAllows users to adjust room comfort and to choose occupancy features that match the application and controller.Occupancy Light-Emitting Diode (LED) IndicatorDisplays the current operating mode of the controller (VMA1200 and VMA1400 Series controllers only).Manual Override Pushbutton (PB)Overrides time-of-day scheduling when the space is occupied outside of normal occupied hours schedule.TE-6800 Series Temperature SensorsProduct BulletinTE-68xx-xN00SCode No. LIT-12011542Issued April, 2018Supersedes September 3, 2009 TE-6800 Series Temperature Sensors Product Bulletin2Product OverviewA manual override PB allows the occupant to control the space temperature. This feature allows the end user to signal the controller that the space is occupied after hours or on weekends.An LED is standard for all models. When used with a VMA1200 or VMA1400 Series controller, the green LED can display the current operating mode of that controller: On = Occupied, Off = Unoccupied, and Flashing = Standby.The controller compatibility DIP switch programs the TE-6800 to:•disable the PB and LED indicator•enable PB with LED indicator•enable PB without LED indicatorThe DIP switch matches the PB and LED indication with features recognized by more recent JohnsonControls® controllers. Specifically, the DIP switch allows for matching controller features to disable the occupancy LED and/or PB.The TE-6800 is available with a modular jack or terminal block wiring connections, and either a 1000-ohm nickel or platinum temperature sensing element. The unit can be used with Application Specific Controllers (ASCs) or for universal applications.The TE-6800 Temperature Sensor uses a warmer/cooler single setpoint adjustment dial. The setpoint dial is adjusted clockwise to heat and counterclockwise to cool.Ordering InformationTo order a TE-6800 Series Temperature Sensor, contact the nearest JohnsonControls representative. Specify the desired sensor product code number from Table2 and accessories from Table3, depending on the model. IMPORTANT:The TE-6800 Series Temperature Sensors are intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the TE-6800sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the TE-6800sensor.Table 2: TE-6800 Series Temperature Sensor Product Code NumbersProduct Code NumberTemperature Sensing ElementWarmer/Cooler Temperature Setpoint Adjustment OverrideTemperature DisplayConnectionEnclosure Dimension, mmTE-68NT-0N00SNi1000NoNoTerminal Block80 x 80TE-68NT-1N00SNi1000YesNoTerminal Block80 x 80TE-68NP-0N00SNi1000NoNoModular Jack80 x 80TE-68NP-1N00SNi1000YesNoModular Jack80 x 80TE-68PP-0N00SPt1000NoNoModular Jack80 x 80TE-68PP-1N00SPt1000YesNoModular Jack80 x 80TE-68PT-0N00SPt1000NoNoTerminal Block80 x 80TE-68PT-1N00SPt1000YesNoTerminal Block80 x 80Table 3: Optional AccessoriesProduct Code NumberDescriptionACC-INSL-01Wallbox Mounting Pad (10/bag)ACC-INSL-11Surface Mounting Pad (10/bag)NS-WALLPLATE-0Adapts a TE-6800 Sensor (80 x 80 mm) to a standard 80x 120 mm wallboxT-4000-119Hex-head Adjustment Tool (30/bag)TE-6800 Series Temperature Sensors Product Bulletin3Repair InformationDo not field repair the TE-6800 Series Temperature Sensors. As with any electrical device, keep the air vents clean and free from dust or obstruction. If the TE-6800 temperature sensor fails to operate within its specifications, replace the unit. For a replacement sensor, contact the nearest Johnson Controls representative.Technical Specifications 1.These foam pads help prevent drafts from entering the unit through the wall, and make installation easier when mounting onan uneven surface.IMPORTANT:Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.TE-6800 Series Temperature Sensors (Part 1 of 2)Nickel Sensor Temperature Sensor1000 ohm thin-film nickelTemperature CoefficientApproximately 3 ohms per F° (5.4 ohms per C°)Reference Resistance1000 ohms at 70°F (21°C)Accuracy±0.34F° at 70°F (±0.18C° at 21°C)Platinum Sensor Temperature Sensor1000 ohm thin-film platinumTemperature CoefficientApproximately 2 ohms per F° (3.9 ohms per C°)Reference Resistance1000 ohms at 32°F (0°C)Accuracy±0.35F° at 70°F (±0.19C° at 21°C)Setpoint RangeWarmer/CoolerResistance1500 OhmsSensor Response Time10 minutes at 10 feet per minuteField ConnectionsModular Jack8-position modular jack connectorTerminal BlockScrew type terminals for 18 to 24 AWG wireZone Bus Access6-pin connector with front bottom access for a laptop with HVAC PRO software and CVTPRO converterManual OverrideIntegral momentary push button (DIP switch selectable)LED LightGreen LED light indicates two modes of operation (VMA1200 and VMA1400 Series controllers only)Ambient Operating Conditions32 to 131°F (0 to 55°C)10 to 95% RH, noncondensing; 86°F (30°C) maximum dew pointAmbient Storage Conditions -40 to 140°F (-40 to 60°C)5 to 95% RH, noncondensing; 86°F (30°C) maximum dew pointMaterialsWhite thermoplasticAccessoryNS-WALLPLATE-0Adapts a TE-6800 Sensor (80 x 80 mm) to a standard 80 x 120 mm wallboxDimensions (Hx W x D)3-1/4 x 3-1/4 x 1-7/16 in. (80 x 80 x 36 mm)Published in U.S.A.www.johnsoncontrols.comTE-6800 Series Temperature Sensors Product Bulletin4Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.All other marks herein are the marks of their respective owners. © 2018 Johnson Controls.Building Technologies & Solutions507 E. Michigan Street, Milwaukee, WI 53202The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.Shipping Weight1 lb (0.5 kg)ComplianceUnited StatesUL Listed, File E107041,CCN PAZX, Under UL 916, Energy Management EquipmentCanadaUL Listed, File E107041,CCN PAZX7, Under CAN/CSA C22.2 No. 205, Signal EquipmentEuropeCE Mark – Johnson Controls, Inc. declares that the TE-6800 Series Temperature Sensors are in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/ECAustralia and New ZealandC-Tick Mark, Australia/NZ Emissions CompliantUnited States Emissions ComplianceThis equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.Canadian Emissions ComplianceThis Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.TE-6800 Series Temperature Sensors (Part 2 of 2)Next >