The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc.www.johnsoncontrols.com1T-5210Pneumatic Temperature TransmitterDescriptionThe T-5210 Pneumatic Temperature Transmitter measures temperature and converts this measurement to an air pressure signal that is transmitted to a pneumatic receiver, controller, or receiver-indicator. When used with a Dewcel® (purchased locally), the T-5210 operates as a dew point transmitter.Refer to T-5210 Pneumatic Temperature Transmitter Product Bulletin (LIT-7171170) for important product information.Selection Charts T-5210 Pneumatic Temperature TransmitterCode NumberElement StyleOperating RangeT-5210-1001Copper Bulb with 5-1/2 in. (140 mm) Copper Capillary50 to 100°FT-5210-20020 to 100°CT-5210-2003-15 to 35°CT-5210-10020 to 100°FT-5210-100440 to 240°FT-5210-100850 to 150°FT-5210-112360 to 85°FT-5210-200110 to 35°CT-5210-112540 to 65°CT-5210-1113Copper Bulb with 4 ft (1.2 m) Copper Capillary-40 to 160°FT-5210-2004-40 to 60°CT-5210-1144-20 to 80°FT-5210-11140 to 100°FT-5210-2005-15 to 35°CT-5210-115120 to 120°FT-5210-1135200 to 400°FT-5210-10078 ft (2.4 m) Copper Averaging Element with 1 ft (305 mm) Copper Capillary50 to 150°FT-5210-100640 to 240°FT-5210-10090 to 100°FT-5210-112440 to 65°FT-5210-20060 to 50°CT-5210-2007-15 to 35°CT-5210-115020 to 120°FT-5210-100550 to 100°FT-5210-111617 ft (5.2 m) Copper Averaging Element with 1 ft (305 mm) Copper Capillary50 to 150°FT-5210-11180 to 100°FT-5210-2008-15 to 35°CAccessories for T-5210 Pneumatic Temperature TransmitterCode NumberDescriptionT-275-100“B” Bulb Element HolderT-275-101Averaging Element HolderT-800-1603Single-Hub Duct FlangeT-800-1604Double-Hub Duct FlangeT-800-1605Brass Well, 6-1/2 in.T-800-1606Stainless Steel Well, 5-1/4 in.TE-6001-8Temperature Element HolderT-800-1610Bulb Element Adapter Nut, 1/2 in. NPTT-800-1618Brass Well, 9-1/2 in.T-800-1620Stainless Steel Well, 9-1/2 in.T-5210-129Sheet Metal BracketT-5210-138Dewcel® Adapter KitT-5210-602Pneumatic Transmitter Cover Kit, includes one Blank Cover and two Pan-Head Mounting ScrewsSHL10A-603RBulb Weather ShieldR-3710 Series0.007 in. Aqua-colored RestrictorCode No. LIT-1921595Issued February 19, 2013 T-5210 Pneumatic Temperature TransmitterFeatures•provides an exact proportional relationship between the measured temperature and the transmitted signal•includes appropriate brackets for mounting to ductwork, walls, or directly to the hub of a duct flange, or separable well•operates in any position from a rigid, flat, mounting surface•requires a 0.007 in. restricted supplyRepair InformationIf the T-5210 Pneumatic Temperature Transmitter fails to operate within its specifications, replace the unit. For a replacement temperature transmitter, contact the nearest JohnsonControls® representative.Next >