The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2011 Johnson Controls, Inc.www.johnsoncontrols.comT-5002Room Temperature TransmitterDescriptionThe T-5002 Series Room Transmitters measure space or mass temperature and transmit a proportional 3 to 15 psig (21 to 105 kPa) pneumatic output signal to an indicator, receiver-controller, or Building Automation System (BAS) for automatic temperature control. The space transmitters measure the temperature of the ambient air; the mass transmitters measure the surface temperature of the walls surrounding the space and transmit the signal to an optional start controller.Refer to T-5002 Room Temperature Transmitter Product Bulletin (LIT-7171070) for important product information.Selection Charts T-5002 Series Room TransmitterCode Number DescriptionT-5002-201Space Temperature, Direct ActingRange 50 to 100°FT-5002-202Range 60 to 85 °FT-5002-300Range 10 to 35°CT-5002-205 11.Includes solid plastic cover (no vents) for mass temperature sensing.Mass TemperatureDirect Acting, Range 20 to 70°FT-5002-203 1Reverse Acting, Range 120 to 70°FNote:For a list of transmitter covers, see T-4000 Covers (For Use With H-4100 and H-5100 Series Humidity Instrument Covers).Accessories and Maintenance Parts for T-5002Code NumberDescriptionT-4002-617Screws#4-40 x 1/4 in. Socket Screws for Mounting Brackets and Covers (Order in Multiples of 100)T-4000-627#4-40 x 1/4 in. Hex Tamper Proof Screws(50 Screws with Driver)Code No. LIT-1921590Issued January 15, 2008 T-5002 Series Room TransmitterFeatures•requires no field adjustment•provided with barbed fittings for direct air line connections with 5/32 in. O.D. tubing•available with optional plug-in terminalRepair InformationIf the T-5002 Series Room Transmitter fails to operate within its specifications, replace the unit. For a replacement room transmitter, contact the nearest JohnsonControls® representative.Next >