European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue August 2016 © 2016 Johnson Controls, Inc. Catalogue Section 4 Order No. PD-P215PR-F Introduction The Series P215PR/RM direct-mount and remote- mount pressure-actuated condenser fan speed controllers are designed for speed variation of single-phase motors. Head pressure control of a refrigeration system, through speed variation of the fan on an air-cooled condenser, results in optimum performance throughout the year. Once the output drops below 30%, the fan is cut off. The Series P215PR/RM controllers are designed for non-corrosive refrigerant systems. See Table 1 for a list of features and benefits. A pressure-actuated control provides the most direct and fastest response to pressure variations in the refrigerant system. The controller varies the supply voltage to the motor from 30% to at least 95% over the proportional band using the phase-cutting principle. This principle provides speed variation of a permanent split capacitor or shaded pole motors that do not draw more than 4 A (RMS) full-load current. The motor manufacturer should have approved the product for this speed control principle. We recommend confirming with the electric motor manufacturer that the motor can be used with a controller, using the phase-cutting principle for speed variation. You can also provide a copy of this product data sheet to the motor manufacturer or supplier for review. Figure 1: P215PR Direct-Mount Pressure- Actuated Condenser Fan Speed Controller Figure 2: P215RM Remote-Mount Pressure- Actuated Condenser Fan Speed Controller Table 1: Features and Benefits Feature Benefit Fan Speed Variation Condenser Pressure Control Creates optimum condenser pressure control all year round and reduces noise during colder periods (such as nights). Pressure Input Allows direct and fast response to pressure variations. Direct Mount Option Allows for easy installation. Remote Mount Option Creates flexibility in mounting location. Setpoint Screw Location on Top of Device Allows for easy setpoint adjustment after installation. Built-in Suppression Filter Meets electro-magnetic compatibility requirements. IP65 Enclosure Allows for controller mounting outdoors. Compact Design Fits into small units and has a small turnaround circle. Attractive Styling Upgrades your equipment. Quick Connector Plug Included Allows for easy wiring and quick replacement. Style 5 Remote Mount Enables direct connection with flexible refrigeration hose. Pressure Range 5-42 bar Allows compatibility with all HFC types from R134a to R410a. Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors 2 P215PR/RM Series Pressure Controllers IMPORTANT: Use this Series P215PR/RM Pressure-Actuated Condenser Fan Speed Controller only as an operating control. Where failure or malfunction of the P215PR/RM could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the P215PR/RM Controller. Installation The controller must be mounted in an upright position on the refrigerant line, preferably at the condenser outlet side, to reduce pressure pulsation as much as possible. Mount the controller within a 45° angle on both sides of the top of the high pressure line to avoid accumulation of oil inside the controller bellows and maintain the class IP65 rating. See Figure 3. If you are using a pump-down system, the controller connection must be made at the high-pressure side of the system and upstream from the solenoid valve to avoid low pressure during pump-down. The controller (IP65) can be mounted outdoors. See Figure 4. When mounted inside a cabinet, holes for air circulation must be provided. Figure 3: Mounting Position Range Figure 4: Cable Positioning Wiring The built-in EMC filter is designed for a maximum distance of 2 meters between the controller and the motor. Non-shielded cable must be used. The gasket must be placed between the quick connector plug and the controller terminals. The cable jacket must extend through the grommet. The rubber O-ring must be placed on the screw. Tighten screw securely. The screw fastens the connector plug to the controller terminals. The gasket, grommet, and rubber O-ring keep the IP65 protection class for the controller (see Figure 5). Figure 5: Wiring Details ! WARNING: Risk of Electric Shock. Disconnect or isolate all power supplies before making electrical connections. More than one disconnect or isolation may be required to completely de-energize equipment. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death. ! CAUTION: Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. Electro-Magnetic Capability The controller includes a built-in suppression filter and meets required (EC) directives. However, when two or more Electro-Magnetic-Compatibility (EMC) compliant components are combined, the entire system may not be compliant. It is the end user’s responsibility to make the entire system compliant. Multiple motors can be wired in parallel, provided that the total current does not exceed the maximum limit. Measuring Use a True RMS meter for measuring amperes or volt values. P215PR/RM Series Pressure Controllers 3 Adjustments The setpoint is defined at 90% output value. The fixed cut-off value is 30% of the supplied voltage. Both the load and the supply voltage can affect the controller characteristic. Figure 6: VDC Output Relative to Pressure Input The proportional band is fixed and defined as the pressure difference between the points where the output values are 30% and 90% of the supply voltage. See Figure 6. The values indicated are shown at 50 Hz power supply. At 60 Hz power supply, the cut-off and proportional band values decrease by 15%. A built-in (fixed) hysteresis is included in the controller. This hysteresis is not indicated in the control characteristic, but is included in the proportional band. Setpoint The pressure setpoint at which your equipment operates can be adjusted by using the setpoint adjusting screw. See Figure 7. Figure 7: Setpoint Adjustment Screw The setpoint is factory set at the values shown in the following table. Control RangeFactory SetpointRange 5 to 15 bar 9 bar Range 10 to 25 bar 19 bar Range 22 to 42 bar 26 bar Repair Information If a Series P215PR/RM Condenser Fan Speed Controller fails to operate within its specifications, replace the unit. For a replacement Series P215PR/RM, contact the nearest Johnson Controls® representative. Provide the model number of the control when ordering a replacement. This number is found on the data plate. See Table 2 on page 4 for the Product Selection Chart. Range (bar) 5 to 15 10 to 2522 to 42Proportional Band 3.0 ± 0.7 4.5 ± 1 5.5 ± 1.5 4 P215PR/RM Series Pressure Controllers Table 2: Product Selection Chart Product Code Number Range (bar)* Element Style Setting (bar) Prop. Band (bar) Minimum Shipping Quantity Additional Features P215PR-9200 10 to 25 47 19 4.5 1 P215PR-9202 22 to 42 47 26 5.5 1 P215PR-9203 5 to 15 47 9 3.0 1 P215PR-9800 10 to 25 28 19 4.5 1 P215PR-9230 10 to 25 47 19 4.5 25 Bulk Pack P215PR-9232 22 to 42 47 26 5.5 25 Bulk Pack P215PR-9233 5 to 15 47 9 3.0 25 Bulk Pack P215PR-9250 10 to 25 47 19 4.5 15 Bulk Pack, 2 m cable connector includedP215RM-9700 10 to 25 5 19 4.5 1 P215RM-9702 22 to 42 5 26 5.5 1 P215RM-9703 5 to 15 5 9 3.0 1 *1 bar = 100 kPa 14.5 psi Pressure Connections and Dimensions There are three types of pressure connections available. See Figure 8. 196166117141062675109301530Ø4.5 Figure 8: Pressure Connection Types: Style 47 (Left), Style 28 (Middle), Style 5 (Right), Dimensions, mm P215PR/RM Series Pressure Controllers 5 Technical Specifications P215PR/RM Pressure Actuated Controllers Product P215PR/RM Pressure-Actuated Condenser Fan Speed Controllers Pressure Range 5 to 15 bar10 to 25 bar 22 to 42 bar Maximum Overrun Pressure 5 to 15 bar = 25 bar10 to 25 bar = 40 bar 22 to 42 bar = 48 barPressure Connection Style 5 (7/16-20 UNF male for 1/4 in. flared tubing connection) Style 47 (7/16-20 UNF female including valve depressor) Style 28 (with 100 mm tube,6 mm ODM)Control Action Direct Maximum Output Voltage 95% of Supply Voltage Maximum Current 4 A RMS (at maximum voltage output) Operating Ambient Temperature -40° to 55°C Minimum Current 200 mA Residual Current Motor 25 mA Power Factor (cos) Motor 0.6 Main Supply Voltage 230 VAC + 8% / -15% Main Supply Frequency 50/60 Hz Cut-off Point 30% of Supply Voltage Proportional Band (Range) at 50 Hz* *Approximately 15% less at 60 Hz 5 to 15 bar = 3.0 ± 0.7 bar 10 to 25 bar = 4.5 ± 1 bar 22 to 42 bar = 5.5 ± 1.5 bar Storage Ambient Humidity 10 to 98% Relative Humidity (RH) Storage Ambient Temperature -40 to 85°C Enclosure IP65 Material Top/Bottom Polycarbonate (glass filled) Heat Sink Aluminium Pressure Connection Brass Bellows Phosphor Bronze Shipping Weight 0.3 kg (Individual Pack) Wiring Connections Screw Terminals 1-1/2mm2 maximumQuick Connector Plug PG9 (6to 7mm cable)Compliance CE Mark –Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive and Low Voltage Directive. RoHS Directive; WEEE Directive. The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.United States Emissions Compliance This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. - Consult the dealer or an experienced radio/TV technician for help. Canadian Emissions Compliance This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. 6 P215PR/RM Series Pressure Controllers European Single Point of Contact: NA/SA Single Point of Contact: APAC Single Point of Contact: JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA Johnson Controls International, Inc. Headquarters: Milwaukee, WI, USA European Headquarters: Westendhof 8, 45143 Essen, Germany European Factories: Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany) Branch Offices: Principal European Cities. This document is subject to change Printed in Europe Next >