LIT-12013113 1 LIT-12013113 Issue Date January 2020 Product Bulletin NS8000 Series Vertical Wallbox-Mounted or Surface-Mounted NS Series Network Sensors The NS Series Network Sensors function directly with Metasys® system Field Equipment Controllers (FECs), Metasys Network and Control Engines (NCEs), Advanced Application Field Equipment Controller (FACs), Metasys VAV Box Equipment Controllers (CVM), General Purpose Application Controllers (CGM), Input/Output Modules (IOMs), VAV Modular Assembly (VMA16) Controllers, and Facility Explorer™ FX-PC Series Programmable Controllers (FX-PCGs, FX-PCVs, and FX-PCXs). The sensors are also compatible with Verasys® and Johnson Controls® Smart Equipment. The NS Series Network Sensors monitor zone temperature, relative humidity (RH), carbon dioxide (CO 2 ), motion, and local temperature setpoint adjustments. The sensor transmits this data to a controller on the Sensor/Actuator (SA) bus. Some NS Series Network Sensors models include an onboard passive infrared (PIR) occupancy sensor that detects motion to determine if a space is occupied. This feature maximizes up to 30% energy savings in high-energy usage environments such as schools, dormitories, offices, hospitals, and hotels by adjusting the temperature of the space based on the occupancy status. In addition, the PIR occupancy sensor facilitates trending of floor space usage in these environments. Display models of the NS Series Network Sensors are available with a backlit LCD fixed segment display or a full color graphical LCD interface. These models allow the user to view zone temperature, RH, CO 2 , and adjust the zone temperature setpoint and fan speed. Graphical models provide a summary of sensor values at the base of the display. Fixed segment models have the capability to set the default display to temperature, RH, or temperature setpoint. The user can also choose between degrees Fahrenheit (F) and degrees Celsius (C). To prevent tampering with the sensor, display models also include a screen lockout feature. The graphical display allows the user to choose between a light or dark color theme and to set the sleep mode to dim or turn off. Some models also have a Warmer/Cooler interface to adjust the zone temperature. Instead of a display, these models have two cap touch buttons with seven LED lights that represent the current setpoint. The display models include the following fan speeds: automatic, off, low, medium, or high. Interaction with the sensor sets the occupancy override function to signal to the controller that the zone is occupied and to override the scheduled mode. The LCD full color graphical models use the graphical user interface to set a unique BACnet® address for applications that require multiple sensors. Other models have DIP switches to set a unique address for applications that require multiple sensors. All models ship standard with modular phone jacks and screw terminals to terminate the wiring connecting the sensors to the controller. Note: To connect the NS Series Network Sensor to the same SA bus segment, use only one of the two connection methods, either the modular phone jack or the screw terminals. Each network sensor includes a SA bus access port, allowing for accessories to connect to the SA bus. Through this connector, the user can use accessories to service or commission the connected controller or gain access to any other controller on the same field controller (FC) bus. Note: Device programming for the NS8000 sensor connected to the controller does not include balancing functionality and features. The NS Series Network Sensors can be surface mounted or vertical wallbox mounted to meet the requirements of the specific application. All display models are optimized for the California Energy Code (Title 24). To suit specific architectural and interior design needs, the models come with either black or white enclosures. Overview 466 72.0 74.5 40 CO2 °FLIT-12013113 2 NS8000 Series Features and benefits Ordering information Table 1 through Table 6 list the various NS Series Network Sensors available. FeaturesBenefits BACnet MS/TP protocol communicationProvides compatibility with Metasys system field controllers, Facility Explorer programmable controllers as well as Verasys and Johnson Controls Smart Equipment in a proven communication network. Single and multifunctional sensorsChoose temperature, RH, CO 2 , and occupancy sensing depending on HVAC needs. Large backlit fixed segment LCD display or LCD full-color graphical display available on some models Provides real-time status of the environment with backlighting activated during user interaction. Simple temperature setpoint adjustment or Warmer/ Cooler mode available on display models Configure simple setpoint adjustment or Warmer/Cooler mode. Onboard occupancy sensor available on PIR modelsMaximizes up to 30% energy savings in high-energy usage environments, and facilitates trending of floor space usage. Temporary occupancy included on all display and Warmer/Cooler models Provides a timed override command, which initiates a temporary occupancy state. Field-selectable default display setting on display modelsToggle between temperature, RH or temperature setpoint on the display, and set the desired default for continuous viewing. Fahrenheit/Celsius (°F/°C) selectable on display modelsDisplay temperature in degrees Fahrenheit or degrees Celsius. All display models meet California Energy Code (Title 24)Displays the required State of California Title 24 economizer fault conditions. All display models include a screen lockoutPrevents sensor tampering. Serialized sensors and calibration certificatesObtain factory calibration certificates for all models. IMPORTANT The NS Series Network Sensor is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the network sensor could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the network sensor. Note: Keep the Metasys system software up to date as some NS Series Network Sensor features are not supported in previous releases of Metasys, Facility Explorer, Verasys, or Johnson Controls Smart Equipment system software. Repair information If the NS Series Network Sensor fails to operate within its specifications, replace the unit. For a replacement sensor, contact the nearest Johnson Controls representative. Modern enclosures in black or white design themes are available in the following styles: • LCD fixed segment display and LCD full color graphical display: View zone temperature, RH, CO 2 , occupancy status, and adjust the zone temperature setpoint and fan speed. These models have the capability to set the default display to temperature, RH or temperature setpoint. On these display models, you can also choose between degrees Fahrenheit (F) and degrees Celsius (C). • Warmer/Cooler interface: This interface incorporates cap touch buttons with seven LED lights that represent the current setpoint status. • No display: The NS Series Network Sensors are available in high gloss black or white with or without the Johnson Controls logo. • All sensors are serialized for quality and warranty purposes. Based on the serial number, the user can obtain factory calibration certificates. Note: The LCD full color graphical models are only available in white. See Table 1 through Table 4 for ordering information.LIT-12013113 3 NS8000 Series Table 2: NS Series Network Sensor ordering information: temperature and humidity models (3% RH) Product codeDisplay and interface informationJohnson Controls logo ColorPIR occupancy sensor NSB8BHN240-0Fixed segment displayYesWhiteNo NSB8BHN241-0NoWhiteNo NSB8BHN242-0YesBlackNo NSB8BHN243-0NoBlackNo NSB8MHN240-0YesWhiteYes NSB8MHN241-0NoWhiteYes NSB8MHN242-0YesBlackYes NSB8MHN243-0NoBlackYes NSB8BHN040-0No displayYesWhiteNo NSB8BHN041-0NoWhiteNo NSB8BHN042-0YesBlackNo NSB8BHN043-0NoBlackNo NSB8MHN040-0YesWhiteYes NSB8MHN041-0NoWhiteYes NSB8MHN042-0YesBlackYes NSB8MHN043-0NoBlackYes NSB8BHN140-0Warmer/Cooler interfaceYesWhiteNo NSB8BHN141-0NoWhiteNo NSB8BHN142-0YesBlackNo NSB8BHN143-0NoBlackNo NSB8BHN340-0Graphical user interfaceYesWhiteNo NSB8BHN341-0NoWhiteNo Selection charts Table 1: NS Series Network Sensor ordering information: temperature, humidity, and CO 2 models (3% RH) Product codeDisplay and interface informationJohnson Controls logoColorPIR occupancy sensor NSB8BHC040-0No displayYesWhiteNo NSB8BHC041-0NoWhiteNo NSB8BHC042-0YesBlackNo NSB8BHC043-0NoBlackNo NSB8MHC040-0YesWhiteYes NSB8MHC041-0NoWhiteYes NSB8MHC042-0YesBlackYes NSB8MHC043-0NoBlackYes NSB8BHC240-0Fixed segment displayYesWhiteNo NSB8BHC241-0NoWhiteNo NSB8BHC242-0YesBlackNo NSB8BHC243-0NoBlackNo NSB8MHC240-0YesWhiteYes NSB8MHC241-0NoWhiteYes NSB8MHC242-0YesBlackYes NSB8MHC243-0NoBlackYes NSB8BHC340-0Graphical user interfaceYesWhiteNo NSB8BHC341-0NoWhiteNoLIT-12013113 4 NS8000 Series Product codeDisplay and interface informationJohnson Controls logo ColorPIR occupancy sensor NSB8BTN240-0Fixed segment displayYesWhiteNo NSB8BTN241-0NoWhiteNo NSB8BTN242-0YesBlackNo NSB8BTN243-0NoBlackNo NSB8MTN240-0YesWhiteYes NSB8MTN241-0NoWhiteYes NSB8MTN242-0YesBlackYes NSB8MTN243-0NoBlackYes NSB8BTN040-0No displayYesWhiteNo NSB8BTN041-0NoWhiteNo NSB8BTN042-0YesBlackNo NSB8BTN043-0NoBlackNo NSB8MTN040-0YesWhiteYes NSB8MTN041-0NoWhiteYes NSB8MTN042-0YesBlackYes NSB8MTN043-0NoBlackYes NSB8BTN140-0Warmer/Cooler interfaceYesWhiteNo NSB8BTN141-0NoWhiteNo NSB8BTN142-0YesBlackNo NSB8BTN143-0NoBlackNo NSB8BTN340-0Graphical user interfaceYesWhiteNo NSB8BTN341-0NoWhiteNo Product codeDisplay and interface informationJohnson Controls logo ColorPIR occupancy sensor NSB8BTC040-0No displayYesWhiteNo NSB8BTC041-0NoWhiteNo NSB8BTC042-0YesBlackNo NSB8BTC043-0NoBlackNo NSB8MTC040-0YesWhiteYes NSB8MTC041-0NoWhiteYes NSB8MTC042-0YesBlackYes NSB8MTC043-0NoBlackYes NSB8BTC240-0Fixed segment displayYesWhiteNo NSB8BTC241-0NoWhiteNo NSB8BTC242-0YesBlackNo NSB8BTC243-0NoBlackNo NSB8MTC240-0YesWhiteYes NSB8MTC241-0NoWhiteYes NSB8MTC242-0YesBlackYes NSB8MTC243-0NoBlackYes NSB8BTC340-0Graphical user interfaceYesWhiteNo NSB8BTC341-0NoWhiteNo Table 3: NS Series Network Sensor ordering information: temperature and CO 2 models Table 4: NS Series Network Sensor ordering information: temperature only modelsLIT-12013113 5 NS8000 Series NS Sensors with fault code capability error codes The fault indication comes through the network sensor bus when a network sensor is used in the zone. The display indicates the code number for all the required state of California Title 24 economizer fault conditions. See the following table for fault error codes. Display text California Title 24 economizer fault condition Possible problem E0Air temperature sensor failure/faultProblem with one of the air temperature sensors. Check outdoor air, return air, or supply air sensors. E1Not economizing when it shouldThe economizer is not using outdoor air when it should. E2Economizing when it should notThe economizer is allowing outdoor air inside when the conditions are not suitable for economizer operation. E3Damper not modulatingThe economizer damper is not able to modulate properly. Check damper, linkage to actuator, or the actuator. E4Excess outdoor airThe economizer is allowing excess outdoor air inside. Product codeDisplay and interface informationJohnson Controls logoColor NSB8BPN240-0Fixed segment displayYesWhite NSB8BPN241-0NoWhite NSB8BPN242-0YesBlack NSB8BPN243-0NoBlack Table 6: NS Series Network Sensor ordering information: temperature and humidity models (2% RH) Table 7: Fault code capability error codes Product codeJohnson Controls logoColor NSB8BNC040-0YesWhite NSB8BNC041-0NoWhite NSB8BNC042-0YesBlack NSB8BNC043-0NoBlack Table 5: NS Series Network Sensor ordering information: CO 2 only models without displayLIT-12013113 6 NS8000 Series Technical specifications Supply voltage9.8 VDC to 16.5 VDC; 15 VDC nominal (from SA bus) Current consumptionBase current draw (graphical models) Screen off18 mA maximum (non-transmitting) Screen on45 mA maximum Base current draw (other models)3 mA maximum (non-transmitting) CO 2 modelsLCD graphical13 mA maximum additional current (non-transmitting) Other models15 mA maximum additional current (non-transmitting) Fixed segment display models - backlight on 10 mA additional current Warmer/Cooler models - LEDs on8 mA additional current Note: SA bus applications are limited to a power load of 210 mA. The best practice when configuring an SA bus is to limit the total available operating power consumption to 120 mA or less. This power level allows you to connect a BTCVT Wireless Commissioning Converter temporarily or a DIS1710 Local Controller Display to the bus for commissioning, adjusting, and monitoring. TerminationsModular jack and screw terminal block Network sensor addressing LCD full color graphical modelsConfigurable through graphical user interface Other modelsDIP switch set from 199 to 206; factory set at 199 Wire sizeModular jack models24 AWG or 26 AWG (0.5 mm or 0.4 mm diameter); three twisted pair (six conductors) Screw terminal block models18 AWG to 22 AWG (1 mm to 0.6 mm diameter); 22 AWG (0.6 mm diameter) Communication rateAuto-detect: 9.6 kbps, 19.2 kbps, 38.4 kbps, or 76.8 kbps Temperature measurement range32°F/0°C to 104°F/40°C Temperature sensor typeDigital temperature sensor Humidity sensor typeThin film capacitive sensor Ambient conditionsOperating32°F to 122°F (0°C to 50°C); 10% to 90% RH, noncondensing; 85°F (29°C) maximum dew point StorageDisplay models-40°F to 122°F (-40°C to 50°C); 5% to 95% RH, noncondensing Non-display models-40°F to 185°F (-40°C to 70°C); 5% to 95% RH, noncondensing Temperature resolution±0.5°F/±0.5°C Temperature accuracyNS Series Network Zone Sensor±1°F/±0.6°C Temperature element only±0.36°F/±0.2°C at 70°F/21°C Humidity element accuracyNSB8BPN24x-0 models±2% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C) ±4% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F (10°C to 35°C) NSB8BHxxxx-0 models±3% RH for 20% to 80% RH at 50°F to 95°F (10°C to 35°C) ±6% RH for 10% to 20% and 80% to 90% RH at 50°F to 95°F (10°C to 35°C) CO 2 measurement range0 ppm - 2000 ppm CO 2 sensor accuracyAccuracy±30 ppm +3% of CO 2 reading at 77°F (25°C) and 978 hPa (1,000 ft/300 m) Temperature dependence±1.4 ppm/°F (± 2.5 ppm/°C) Pressure dependenceRefer to the NS8000 Series Network Sensors Installation Guide (24-11256-00007) for CO 2 altitude compensation. CO 2 sensor operation range32°F to 122°F (0°C to 50°C) Time constant10 minutes nominal at 10 fpm airflow Default temperature setpoint adjustment range50°F/10°C to 86°F/30°C in 0.5° increments CO 2 sensor lifespan10 years under standard operating conditions LCD lifespan for graphical display models Screen timeout set to off>10 years Screen timeout set to dimAt least 6 yearswww.johnsoncontrols.com Building Technologies & Solutions Headquarters: Milwaukee, Wisconsin, USA Branch Officies: Principal Cities World-wide Johnson Controls® is registered trademark of Johnson Controls. All other marks herein are the marks of their respective owners. © Copyright 2020 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited. NS8000 Series Use of the software that is in (or constitutes) this product,or access to the cloud, or hosted services applicable to this product, if any, is subject to applicable terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms. This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty. Patents: http://jcipat.com Software terms Product warranty Patents Contact information Contact your local branch office: www.johnsoncontrols.com/locations Contact Johnson Controls: www.johnsoncontrols.com/contact-us APAC JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 - CHINA Europe JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY NA/SA JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Single point of contact PIR occupancy sensor motion detectionMinimum 94 angular degrees up to a distance of 26 ft (8m); Based on clear line of sight ComplianceUnited StatesUL Listed, File E107041, CCN PAZX, Under UL 60730-1, Energy Management Equipment FCC Compliant to CFR 47, Part 15, Subpart B, Class B CanadacUL Listed, File E107041, CCN PAZX7, Under CAN/CSA E60730-1, Signal Equipment Industry Canada, ICES-003 EuropeCE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive and RoHS Directive. Australia and New ZealandRCM Mark, Australia/NZ Emissions Compliant ChinaRoHS2 Dimensions (height x width x depth)3.4 in. x 5 in. x 1.1 in. (85.3 mm x 127.55 mm x 26.8 mm) Shipping weight0.4 lb/0.18 kgNext >