The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc. www.johnsoncontrols.com 1 CSD Series Current Devices Code No. LIT-1900454 Issued April 5, 2013 Description The Current Switch Device (CSD) Series of digital output current switches are non-intrusive devices designed to detect current flowing through a cable or wire. A cost-effective solution for monitoring on and off status or proof of operation, these units are ideal for monitoring very small current loads on motors driving fans and blowers, pumps, heating coils, and lighting. The CSD models with command relays not only monitor the current flowing through the cable but also facilitate the start and stopping of the motor. These units also provide a universal solid-state output and do not require a power supply. Completely self-powered, these units draw their power from current induced from the cable or line being monitored. CSD Series Current Devices are available in the following types: •solid core, setpoint fixed •solid core, setpoint adjustable •solid core with command relay, setpoint adjustable •split core, setpoint fixed •split core, setpoint adjustable •split core with command relay, setpoint fixed •split core with command relay, setpoint adjustable •12 VAC/VDC and 24 VAC/VDC accessory command relays Refer to the CSD Series Current Devices Product Bulletin (LIT-12011292) for important product application information. Features •dual function — monitors current and motor start and stop •100% solid-state output — has no moving parts to fail •polarity insensitive output — provides easier wiring •snap-in mounting bracket — simplifies installation •small size — fits in tight enclosures Fixed Setpoint Models CSD-SF0C0-1 (solid core) •Setpoint fixed at 0.25 A •Current range — 0.25 to 200 A CSD-CF0A0-1 (split core) •Setpoint fixed at 0.15 A •Current range — 0.15 to 200 A CSD-CF0J0-1 (split core) •Setpoint fixed at 1.5 A •Current range — 1.5 to 200 A CSD-CF0J1-1 (split core with 24 V command relay) •Relay Single Pole, Single Throw (SPST), Normally Open (N.O.), 10 A at 260 VAC, 5 A at 30 VDC •Actuation coil — 20–30 VAC/DC, 40–85 mA maximum •Setpoint fixed at 1.5 A •Current range — 1.5 to 200 A Adjustable Setpoint Models CSD-SA1E0-1 (solid core) •Multi-turn potentiometer — adjust setpoint for application •Adjustable setpoint — wide range from 1.0 to 135 A •Two status Light-Emitting Diodes (LEDs) — provide visual indication of off and on status CSD-SA1E1-1 (solid core with 24 V command relay) •Multi-turn potentiometer — adjust setpoint for application •Adjustable setpoint — wide range from 1.00 to 135 A •Relay SPST, N.O., 10 A at 260 VAC, 5 A at 30 VDC •Actuation coil — 20–30 VAC/DC, 40–85 mA maximum •Two Status LEDs — provide visual indication of off and on status CSD-CA1G0-1 (split core) •Multi-turn potentiometers — adjust setpoint for application •Two status LEDs — provide visual indication of off and on status •Adjustable setpoint — wide range from 1.25 to 135 A CSD-CA1G1-1 (split core with 24 V command relay) •Multi-turn potentiometers — adjust setpoint for application •Adjustable setpoint — wide range from 1.25 to 135 A •Relay SPST, N.O., 10 A at 260 VAC, 5 A at 30 VDC •Actuation coil — 20–30 VAC/VDC, 40–85 mA maximum •Two status LEDs — provide visual indication of off and on status CSD-SA1E2-1 (solid core with 12 V command relay •Multi-turn potentiometers — adjust setpoint for application •Adjustable setpoint — wide range from 1.00 to 135 A •Relay SPST, N.O., 10 A at 260 VAC, 5 A at 30 VDC •Actuation coil — 10–14 VAC/VDC, 25–45 mA maximum •Two status LEDs — provide visual indication of off and on status Repair Information If the CSD Series Current Device fails to operate within its specifications, replace the unit. For a replacement CSD Series Current Device, contact the nearest JohnsonControls® representative. CSD Series Current DeviceThe performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc. www.johnsoncontrols.com 2 CSD Series Current Devices (Continued) Selection Chart Accessories (Order Separately) Technical Specifications Code NumberCore TypeSetpoint Threshold LED DisplayLow Setpoint (Amperes) Output Relay CSD-SF0C0-1SolidFixedNo0.25 No CSD-SA1E0-1SolidAdjustableYes1.00 No CSD-SA1E1-1SolidAdjustableYes1.00 24 V SPST, N.O. 10 A at 260 VAC, 5 A at 30 VDC CSD-SA1E2-1SolidAdjustableYes1.00 12 V SPST, N.O. 10 A at 260 VAC, 5 A at 30 VDC CSD-CF0A0-1Clamp/SplitFixedNo0.15 No CSD-CF0J0-1Clamp/SplitFixedNo1.5 No CSD-CA1G0-1Clamp/SplitAdjustableYes1.25 No CSD-CF0J1-1Clamp/SplitFixedNo1.5 24 V SPST, N.O. 10 A at 260 VAC, 5 A at 30 VDC CSD-CA1G1-1Clamp/SplitAdjustableYes1.25 24 V SPST, N.O. 10 A at 260 VAC, 5 A at 30 VDC Code NumberDescription CR-01200-0 1 1.Refer to the Command Relay Installation Instructions (Part No.24-10345-50) for more information regarding the command relays. 12 VAC/VDC SPST, N.O. Relay CR-02400-0 1 24 VAC/VDC SPST, N.O. Relay CSD Series Current Devices - Solid Core Models CSD-SF0C0-1CSD-SA1E0-1CSD-SA1E1-1CDS-SA1E2-1 Amperage Range0.25–200 A1.00–135 A1.00–135 A1.00–135 A Switch SetpointFixed AdjustableAdjustableAdjustable Output RelayNoNo24 V SPST, N.O. 10 A at 260 VAC, 5 A at 30 VDC 12 V SPST, N.O. 10 A at 260 VAC, 5 A at 30 VDC Actuation CoilNoNo20–30 VAC/VDC, 40–85 mA Maximum 10–14 VAC/VDC, 25–45 mA Maximum Switch LED IndicationNoYesYesYes Relay LED IndicationNoNoYesYes Trip Setpoint Value0.25 A1.00 A1.00–135 A Current Switching ModeUnder Current SensingOver/Under Current SensingOver/Under Current Sensing Sensor Supply VoltageInduced from power conductor cable. Wire Size2.1–0.6 mm (12–22 AWG) Diameter Status OutputSwitch normally open. Switch Load Capacity1 A at 30 VAC/42 VDC Maximum Isolation Voltage600 VAC rms Temperature Range-15 to 60°C (5 to 140°F) Frequency Range50/60 Hz Humidity Range0–95% Noncondensing Screw Torque0.5 N·m (4 lb·in.) Dimensions65 x 47 x 25 mm (2-9/16 x 1-7/8 x 1 in.)65 x 65 x 40 mm (2-9/16 x 2-9/16 x 1-19/32 in.) Aperture (Sensing Hole) Size18 mm Diameter (0.71 in. Diameter) ComplianceUnited StatesUL Listed, File E310692, CCN NRNT, Under UL 508, Industrial Control Equipment CanadaUL Listed, File E310692, CCN NRNT7, Under CAN/CSA C22.2 No. 14-M91 Industrial Control Equipment EuropeCE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC. Shipping Weight0.16 kg (0.35 lb)The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc. www.johnsoncontrols.com 3 CSD Series Current Devices (Continued) CSD Series Current Devices - Split Core Models CSD-CF0A0-1/ CSD-CF0J0-1 CSD-CA1G0-1CSD-CF0J1-1CSD-CA1G1-1 Amperage Range0.15–200 A/ 1.5–200 A 1.25–135 A1.5–200 A1.25–135 A Switch SetpointFixedAdjustableFixedAdjustable Output RelayNoNo24 V SPST, N.O. 10 A at 260 VAC, 5 A at 30VDC 24 V SPST, N.O. 10 A at 260 VAC, 5 A at 30VDC Actuation CoilNoNo20–30 VAC/VDC, 40–85 mA Maximum 20–30 VAC/VDC, 40–85 mA Maximum Switch LED IndicationNoYesNoYes Relay LED Indication NoNoYesYes Trip Setpoint Value0.15 A/1.5 A1.25–135 A1.5 A1.25–135 A Current Switching ModeUnder Current SensingOver/Under Current SensingUnder Current SensingOver/Under Current Sensing Sensor Supply VoltageInduced from power conductor cable. Wire Size2.1–0.6 mm (12–22 AWG) Diameter Recommended Status OutputSwitch normally open. Switch Load Capacity1 A at 30 VAC/42 VDC Maximum Isolation Voltage600 VAC rms Temperature Range-15 to 60°C (5 to 140°F) Frequency Range50/60 Hz Humidity Range0–95% Noncondensing Screw Torque0.5 N·m (4 lb·in.) Dimension69 x 65 x 27 mm (2-23/32 x 2-9/16 x 1-1/16 in.)69 x 65 x 44 mm (2-23/32 x 2-9/16 x 1-3/4 in.) Aperture (Sensing Hole) Size18 x 20 mm Diameter (0.72 x 0.78 in. Diameter) ComplianceUnited StatesUL Listed, File E310692, CCN NRNT, Under UL 508, Industrial Control Equipment CanadaUL Listed, File E310692, CCN NRNT7, Under CAN/CSA C22.2 No. 14-M91 Industrial Control Equipment EuropeCE Mark – Johnson Controls, Inc., declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC and the Low Voltage Directive 2006/95/EC. Shipping Weight0.16 kg (0.35 lb)Next >