Master Catalog 125 Temperature Controls Section Product Bulletin A19E Issue Date 0418 © 2018 Johnson Controls 1 Code No. LIT-125075 A19E Series Warm Air Fan and Duct Controls Low or Line Voltage Application These controls are for use on warm air furnaces, ventilating systems, air conditioners, reverse flow heating plants, and to control fan operation. They can be used on the following applications: Fan control to open the blower circuit when temperature is too low to circulate warm air. The fan control turns on the blower after the air has been heated to a suitable temperature. The blower continues to run until the air temperature drops to a predetermined level. Duct temperature control to sense the temperature in the furnace plenum or duct and operate the heating unit. Duct temperature cutout control for ventilating system, air conditioner or reverse flow heating plant, duct or plenum mounting. Must be manually reset after cutout. All Series A19 controls are designed for use only as operating controls. Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls) or systems (alarm, supervisory systems) that protect against, or warn of control failure. Features Dependability . . . snap-acting, dust protected switch and the liquid filled sensing element are field proven. Fig. 1 -- A19 Warm Air Control. Special coil element has high surface to mass ratio for fast response. “Repeat” accuracy is unaffected by barometric pressure and cross ambient temperature problems. “Trip-free” manual reset . . . reset must be pressed and released before operation will resume. Contacts cannot be blocked in the closed position. Fig. 2 -- A19 Control with cover removed showing differential adjusting lever and scale. Specifications 2 A19E Product Bulletin General Description These controls have adjustable differentials. Knob range adjustment and visible scale are standard. The controls have flange mounting that gives a choice of insertion depths. This makes it possible to position the element in the best location for sensing temperature changes. The element support bracket provides a firm support for the element. Models that have lockout have a “trip-free” manual reset. The adjustable differential models have an internal scale plate with multiplier. For example, when the minimum differential is 9F (5C), then X2 is 18F (10C), X3 is 27F (15C) and X4 is 36F (20C) which is the maximum differential. To adjust, move the lever to the differential required. Concealed Cutout Stop The cutout stops are field adjustable. Available stop settings are: 50 to 250F Range -- Stop settings are 250, 205, 195, 180, 165, 155 and 145F (10 to 120C Range -- Stop settings are 121, 96, 91, 82, 74, 68 and 63C). 100 to 350F Range -- Stop settings are 350, 305, 295, 280, 265, 255 and 240F (38 to 177C Range -- Stop settings are 177, 152, 146, 138, 129, 124 and 116C). Ordering Information 1. To order, specify Product Number if available. 2. Where Product Number is not available, specify Type Number and the range. 3. Fixed cutout stop, if required. Specify cutout setting required. Repairs and Replacement Field repairs must not be made. For a replacement control, contact the nearest Johnson Controls wholesaler. UL Guide No. XAPX File E668 Building Technologies & Solutions 507 E. Michigan Street, Milwaukee, WI 53202 ® Johnson Controls and PENN are registered trademarks of Johnson Controls in the United States of America and/or other countries. All other trademarks used herein are the property of their respective owners. © Copyright 2018 by Johnson Controls. All rights reserved. Next >