MP909E and H Pneumatic Damper Actuators Copyright © 1996 Honeywell Inc. • All Rights Reserved 77-9030-1 SPECIFICATION DATA GENERAL The MP909E and H Pneumatic Damper Actuators control dampers, variable volume terminal units, and mixing boxes. The MP909H is an MP909E with a positive positioner. FEATURES •Low friction shaft bearing •Close tolerance on operating range and stroke •Versatile mounting and connecting hardware •Cost efficient mounting to Honeywell dampers •Nonoverlapping spring ranges for sequencing •Corrosion resistant materials •Reliable—long life •Models available for use with UL classified leakage rated (smoke) dampers2 MP909E AND H PNEUMATIC DAMPER ACTUATORS 77-9030-1 SPECIFICATIONS Models: oMP909E Actuator without positioner oMP909H Actuator with positioner Maximum Safe Air Pressure: MP909E: 29 psi (200 kPa) MP909H: 25 psi (172 kPa), limited by positioner Operating Range: MP909E: See following table MP909H: Span of 3, 5, or 10 psi (21, 34, or 69 kPa), nonadjustable. Provided with 10 psi feedback spring; 5 psi feedback spring included; 3 psi feedback spring available Net Force Exerted: Net Force in Pounds (N) Exerted at Various Pressures Model Operating Range psi (kPa)Stroke in. (mm)0 psi (0 kPa)18 psi (124 kPa)20 psi (140 kPa) 3-13 (21-90) 5-10 (34-69) 4.0 (100)19.8 (88) 33 (147) 33 (147) 53 (236) 46.2 (206) 66 (294) MP909E2.5-6.5 (17-45) 5-10 (34-69) 9-13 (62-90) 3.1 (80)16.5 (73) 33 (147) 59.4 (264) 76 (338) 53 (236) 33 (147) 89 (396) 66 (294) 46.2 (206) MP909HAll spans 1 4.0 (100)33 (147)53 (236)66 (294) 1 MP909H has 5-10 psi (34-69 kPa) operating spring range. Air Connections: MP909E: Combination 5/32-in. (4 mm) and 1/4-in. (6 mm) push-on barb MP909H: Positioner: 5/32-in. (4 mm) push-on barb (pilot), 1/4-in. 6 mm) push-on barb (main and branch) Actuator: combination 5/32-in (44 mm) and 1/4-in. (6 mm) push-on barb UL listed actuators: Special high temperature plastic tubing pigtails that allow connection to 1/4-in. (6 mm) O.D. copper tubing Diaphragm: Neoprene, rolling type Effective area 6.6 in 2 (40 cm 2 ) Body Material and Finish: Corrosion resistant aluminum alloy Air Consumption: MP909E: Zero MP909H: 0.021 scfm (9.9 ml/sec) Startpoint Pressure (MP909H): Adjustable 1.5 to 13 psi (10.3 to 90 kPa) Ambient Temperature Range: MP909E: -28 to 160F (-33 to 70C) MP909H: -20 to 160F (-29 to 70C), limited by positioner Mounting: Trunnion and right angle bracketMP909E AND H PNEUMATIC DAMPER ACTUATORS 3 77-9030-1 Dimensions: Damper A and B DimensionsUL Listed: Models Available: MP909E: 5 to 10 psi (34 to 69 kPa) UL Restrictions: UL listing applies only when used with UL classified Honeywell SD series leakage rated dampers Mainline Pressure Limits: 15 psi (103 kPa) minimum; 25 psi (172 kPa) maximum Damper Limitations: D640SD, D641SD: See 77-5129 D644SD, D645SD: See 77-5140 Accessories: oFeedback spring kit for 3 psi span (MP909H): 14004509- 001 (10 springs per kit) oPositioner Kit to convert MP909E 5 to 10 psi to MP909H (includes 3, 5, and 10 psi feedback spring): 14004137-001 EXAMPLE: Damper Model: D641 Duct Dimension: 62 inches (A dimension) x 20 inches (B dimension)Actuator: MP909E Operating Range: 5 to 10 psi (34 to 69 kPa) Type of Operation: Modulating Service Main Air Pressure: 13 psi (90 kPa) The 62-inch A dimension requires two damper sections (48 inches maximum per section). Multiplying the B dimension (20 inches) by two equals 40 inches of total B dimension. The Maximum Damper Load Rating Table shows that one MP909E can operate up to 33 inches of damper. Two MP909Es are required in this example. 17 (430) MP909E 19-3/4 (500) MP909H TRUNNION BRACKET 13-3/4 (350) MP909H 5 (127) 9-1/4 (235) MP909E ANGLE BRACKET MP909E N.C. 7 (180) MP909H N.C. 9-1/2 (240) MP909H N.C. 9-1/2 (240) N.O. 6-1/2 (165) 4-1/2 (114) EDGE OF DAMPER 6-7/8 (175) WIDE MP909H 6-1/4 (159) C8281 "B" DIMENSION "A" DIMENSION "B" DIMENSION VERTICAL BLADE "A" DIMENSION C7856MP909E AND H PNEUMATIC DAMPER ACTUATORS Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc. Room 3213-3225 Sun Hung Kai Centre No. 30 Harbour Road Wanchai Hong Kong Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 2C9 Honeywell Latin American Division Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016 Helping You Control Your World 77-9030-1 Rev. 5-96 Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers Damper Load Rating (See Following Table): Damper load ratings for Honeywell Moduflow Dampers (non-UL Listed models) are calculated by multiplying the B dimension of each section by the number of sections required. Approvals: MP918B (all models): UL Recognized Component, Category EMKU2, File No. R18118, Mainline –25 psi maximum Modulating Service2-Position Service Damper ModelActuator Model Operating Range psi (kPa) Main Air Pressure 13 psi (80 kPa) for B Dimension in. (mm) Main Air Pressure 18 psi (124 kPa) for B Dimension in. (mm) Main Air Pressure 18 psi (124 kPa) for B Dimension in. (mm) D640MP909E3-13 (21-90)—33 (835)36 (910) D6415-10 (34-69) 3 33 (835)33 (835)60 (1520) 2.5-6.5 (17-45)27 (685) 1 27 (685) 1 27 (685) 1 9-13 (62-90)—29 (735)49 (1240) MP909H 4 N.A.40 (1010)67 (1700)67 (1700) D642MP909E3-13 (21-90)—27 (685)29 (735) D6435-10 (34-69) 3 27 (685)27 (685)49 (1240) D6442.5-6.5 (17-45)22 (555) 2 22 (555) 2 22 (555) 2 D6459-13 (62-90)—27 (685)40 (1010) MP909H 4 N.A.33 (835)60 (1520)60 (1520) 1 With normally closed linkage having 81-degree rotation. For 90-degree rotation, use 20 inches (505 mm). 2 With normally closed linkage having 81-degree rotation. For 90-degree rotation, use 17 inches (430 mm). 3 Applies to 4-in. stroke models only. 4 Rating also applies to MP909E 5 to 10 psi (34-69 kPa) slaves used with MP909H. By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.Next >