FocusPRO ® 6000 Series TH6110, TH6220, TH6320, TH6110D, TH6220D, TH6320U Installation Instructions Programmable Digital Thermostat Read before installing M29433 Wallplate installation Remove the wallplate from the thermostat, then follow directions below for mounting. 1. Remove battery holder. 2. Pull here to remove wallplate from new thermostat. 3. Pull wires through wire hole. 4. Position wallplate on wall, level and mark hole positions with pencil. 5. Drill holes at marked positions as shown below, then tap in supplied wall anchors. 6. Place wallplate over anchors, insert and tighten mounting screws. 7. Insert reference card. Drill 7/32" holes for plaster. Drill 3/16" holes for drywall. Wire holeMounting screws MCR294342 MCR29436 Power options Wiring terminal designations Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted. Keep wires in this shaded area Connect C for primary AC power (optional if batteries are installed). Insert batteries for primary or backup power. Remove factory- installed jumper only for two-transformer systems. Conventional Terminals: Rc 24VAC power from cooling transformer R 24VAC power from heating transformer W Heat relay (stage 1) W2 Heat relay (stage 2) Y Compressor contactor (stage 1) Y2 Compressor contactor (stage 2) G Fan relay C 24VAC common. For 2 transformer systems, use common wire from cooling transformer. Heat Pump Terminals: Rc 24VAC power from cooling transformer R 24VAC power from heating transformer O/B Changeover valve Y Compressor contactor Y2 Compressor contactor (stage 2) -TH6320U only G Fan relay Aux/E Auxiliary/Emergency heat relay L Sends output when set to Em. Heat C 24VAC common TH6110D RcYWGRC TH6220D RcYWGW2Y2RC TH6320U RcYWGW2Y2RC MCR29437A TH6110D RcYGRC RcYGLRC TH6220D RcYGAux E Y2LRC TH6320U MCR29438A Aux E3 Wiring conventional systems Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted. 1H/1C System (1 transformer) Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common [3] W Heat relay G Fan relay Heat-only System Rc Power [1] R [R+Rc joined by jumper] C 24VAC common [3] W Heat relay Heat-only System (Series 20) [5] Rc [R+Rc joined by jumper] R Series 20 valve terminal “R” [1] Y Series 20 valve terminal “W” C 24VAC common [3] W Series 20 valve terminal “B” Heat-only System (normally open zone valve) [5] Rc [R+Rc joined by jumper] R Power [1] Y Normally open zone valve C 24VAC common [3] 1H/1C System (2 transformers) Rc Power (cooling transformer) [1, 2] R Power (heating transformer) [1, 2] Y Compressor contactor C 24VAC common [3, 4] W Heat relay G Fan relay Heat-only System with Fan Rc Power [1] R [R+Rc joined by jumper] C 24VAC common [3] W Heat relay G Fan relay Cool-only System Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common [3] G Fan relay 2H/2C System (1 transformer) [6] Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor (stage 1) C 24VAC common [3] W Heat relay (stage 1) G Fan relay W2 Heat relay (stage 2) Y2 Compressor contactor (stage 2) 2H/2C System (2 transformers) [6] Rc Power (cooling transformer) [1, 2] R Power (heating transformer) [1, 2] Y Compressor contactor (stage 1) C 24VAC common [3, 4] W Heat relay (stage 1) G Fan relay W2 Heat relay (stage 2) Y2 Compressor contactor (stage 2) RcYWGRC RcWRC RcYWRC RcYRC RcYWGRC RcWGRC RcYGRC RcYWGW2Y2RC RcYWGW2Y2RC NOTES Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required. [1] Power supply. Provide disconnect means and overload protection as required. [2] Remove jumper for 2-transformer systems. [3] Optional 24VAC common connection. [4] Common connection must come from cooling trans- former. [5] In Installer Setup, set system type to Heat Only. [6] In Installer Setup, set system type to 2Heat/2Cool Conventional. [7] In Installer Setup, set changeover valve to O or B. [8] In Installer Setup, set system type to 2Heat/1Cool Heat Pump. [9] In Installer Setup, set system type to 2Heat/2Cool Heat Pump. [10] In Installer Setup, set system type to 3Heat/2Cool Heat Pump. [11] L terminal sends a continuous output when thermostat is set to Em. Heat. Connect to zoning panels to switch the panel to Emergency Heat.4 MCR29453 Thermostat mounting 1. Push excess wire back into the wall opening. 2. Plug wall opening with non-flammable insulation. 3. Align the 4 tabs on the wallplate with corresponding slots on the back of the thermostat. 4. Push gently until the thermostat snaps in place. 1H/1C Heat Pump System Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common [3] O/B Changeover valve [7] G Fan relay 2H/1C Heat Pump System (TH6220D only) [8] Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common [3] O/B Changeover valve [7] G Fan relay Aux/E Auxiliary/Emergency heat relay L Sends output when set to Em. Heat [11] 2H/1C Heat Pump System (TH6320U only) [8] Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor C 24VAC common [3] O/B Changeover valve [7] G Fan relay Aux/E Auxiliary/Emergency heat relay L Sends output when set to Em. Heat [11] 2H/2C Heat Pump System (TH6320U only) [9] Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor (stage 1) C 24VAC common [3] O/B Changeover valve [7] G Fan relay Y2 Compressor contactor (stage 2) L Sends output when set to Em. Heat [11] 3H/2C Heat Pump System (TH6320U only) [10] Rc Power [1] R [R+Rc joined by jumper] Y Compressor contactor (stage 1) C 24VAC common [3] O/B Changeover valve [7] G Fan relay Aux/E Auxiliary/Emergency heat relay Y2 Compressor contactor (stage 2) L Sends output when set to Em. Heat [11] See Notes on page 3. RcYG Aux E LRC RcYGAux E LRC RcYGY2LRC RcYGAux E LRCY2 Wiring heat pump systems Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted. RcYGRC5 1 0 DoneNext MCR29454 Follow the procedure below to configure the thermostat to match the installed heating/cooling system, and customize feature operation as desired. 1. To begin, press and hold the s and FAN buttons until the display changes. 2. Press s or t to change settings. 3. Press NEXT to advance to next function. 4. Press DONE to exit and save settings. Installer setup Setup function Settings & options (factory default in bold) Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted. 1 System type 0 1 heat/1 cool conventional 1 1 heat/1 cool heat pump (no aux. heat) 2 Heat only — 2-wire systems, 3-wire zone valves (Series 20), and normally open zone valves 3 Heat only with fan 4 Cool only 5 2 heat/1 cool heat pump (with aux. heat) 6 2 heat/2 cool conventional 7 2 heat/1 cool conventional 8 1 heat/2 cool conventional 9 2 heat/2 cool heat pump (no aux. heat) - TH6320U only 10 3 heat/2 cool heat pump (with aux. heat) - TH6320U only 2 Changeover valve (O/B terminal) 0 Changeover valve (O/B terminal energized in cool- ing) 1 Changeover valve (O/B terminal energized in heating) 3 Fan control (heating) 0 Gas or oil furnace — equipment controls fan in heating 1 Electric furnace — thermostat controls fan in heating 5 Stage 1 heat cycle rate (CPH: cycles/hour)* 5 For gas or oil furnaces of less than 90% efficiency 1 For steam or gravity systems 3 For hot water systems & furnaces of over 90% efficiency 9 For electric furnaces 6 Stage 2 heat cycle rate/Auxiliary heat cycle rate (CPH)* 5 For gas or oil furnaces of less than 90% efficiency 1 For steam or gravity systems 3 For hot water systems & furnaces of over 90% efficiency 9 For electric furnaces Function number Setting *[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]6 7 Auxiliary heat cycle rate (CPH)* Only TH6320U for 3H/2C Heat Pumps 5 For gas or oil furnaces of less than 90% efficiency 1 For steam or gravity systems 3 For hot water systems & furnaces of over 90% efficiency 9 For electric furnaces 9 Stage 1 compressor cycle rate (CPH) 3 Recommended for most compressors [Other cycle rate options: 1, 2, 4, 5 or 6 CPH] 10 Stage 2 compressor cycle rate (CPH) 3 Recommended for most compressors [Other cycle rate options: 1, 2, 4, 5 or 6 CPH] 12 Manual/Auto changeover 0 Manual changeover (Heat/Cool/Off) 1 Auto changeover (Heat/Cool/Auto/Off) 2 Auto changeover only (Auto) 13 Adaptive Intelligent Recovery™ 1 On**See page 8 0 Off 14 Temperature display 0 Fahrenheit 1 Celsius 15 Compressor protection 5 Five-minute compressor off time [Other options: 0, 1, 2, 3 or 4-minute off time] 16 Schedule format 0 5/2 (programmable weekdays and weekends) 1 5/1/1 (weekdays, Saturday & Sunday programmable) 27 Heat temperature range stops 90 Max. heat temperature setting is 90 °F (32 °C) [Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)] 28 Cool temperature range stops 50 Min. cool temperature setting is 50 °F (10 °C) [Other options: 51 °F to 99 °F (10.5 °C to 37 °C)] Setup function Settings & options (factory default in bold) Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted. Special function Auto Changeover (Setup Function 12): When set to Auto, the thermostat automatically selects heating or cooling depending on the indoor temperature. The thermostat will automatically adjust heat and cool settings to maintain a 3-degree separation (fixed). Note: If you select Auto Changeover Only, the System Setting on the thermostat will stay locked in the Auto position, preventing the user from changing it to Em Heat, Heat, Cool or Off. Adaptive Intelligent Recovery™ (Setup Function 13): Allows the thermostat to “learn” how long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time. Compressor Protection (Setup Function 15): Forces the compressor to wait a few minutes before restarting, to prevent damage. During the wait time, the message Cool On or Heat On (heat pumps only) will flash on the display. *[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]7 10 0 MCR29455 Installer system test 1. To begin, press and hold the s and t buttons until the display changes. 2. Press s / t to turn system on/off. 3. Press NEXT to advance to next test 4. Press DONE to terminate system test. Temperature Ranges Heat: 40° to 90°F (4.5° to 32°C) Cool: 50° to 99°F (10° to 37°C) Operating Ambient Temperature 32° to 120°F (0° to 48.9°C) Shipping Temperature -20° to 120°F (-28.9° to 48.9°C) Operating Relative Humidity 5% to 90% (non-condensing) Physical Dimensions 3-9/16” H x 5-13/16” W x 1-1/2” D 91 mm H x 147 mm W x 38 mm D Electrical Ratings Terminal Voltage (50/60Hz) Running Current W Heating 20-30 Vac 0.02-1.0 A (Powerpile) 750 mV DC 100 mA DC W2 (Aux/E) Heating 20-30 Vac 0.02-1.0 A Y Cooling 20-30 Vac 0.02-1.0 A Y2 Cooling 20-30 Vac 0.02-1.0 A G Fan 20-30 Vac 0.02-0.5 A O/B Changeover 20-30 Vac 0.02-0.5 A L Output 20-30 Vac 0.02-0.5 A Specifications System test System status Shaded areas below apply only to TH6320U/TH6220D or as otherwise noted. 10 Heating system0 Heat and fan turn off. 1 Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1, 5, 9 or 10 OR Setup Function 3 is set to 1 2 Stage 2 heat turns on 3 Stage 3 heat turns on - TH6320U only 20 Emergency heating system 0 Heat and fan turn off 1 Heat and fan turn on 30 Cooling system0 Compressor and fan turn off 1 Compressor and fan turn on 2 Stage 2 compressor turns on 40 Fan system0 Fan turns off 1 Fan turns on System test number System status69-2695EFS-09 Resideo Inc., 1985 Douglas Drive North Golden Valley, MN 55422 www.resideo.com This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-468-1502 © 2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved. 69-2695EFS—09 M.S. Rev. 04-19 | Printed in United States For assistance with this product, please visit customer.resideo.com. Or call Customer Care toll-free at 1-800-468- 1502. Customer assistance Turn thermostat over to find model number and date code. Pull at bottom to remove thermostat from wallplate. CAUTION: EQUIPMENT DAMAGE HAZARD Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly. CAUTION: ELECTRICAL HAZARD Can cause electrical shock or equipment damage. Disconnect power before beginning installation. CAUTION: MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.Read before installing FocusPRO ® 6000 Série TH6110, TH6220, TH6320, TH6110D, TH6220D, TH6320U Thermostat numérique programmable Notice D’installation M29433 Installation de la plaque murale Séparer la plaque murale du thermostat comme, puis suivre les directives d’installation. 1. Retirer le porte-pile. 2. Tirer ici pour enlever la plaque murale du thermostat neuf. 3. Faire passer les fils par l’ouverture réservée aux fils. 4. Placer la plaque murale sur le mur, mettre de niveau et marquer au crayon l’emplacement des trous. 5. Percer les trous aux endroits marqués à l’aide d’une perceuse, puis insérer les chevilles d’ancrage fournies. 6. Apposer la plaque murale sur les chevilles, insérer puis resserrer les vis de fixation. 7. Insérer la carte de référence. Trou du filVis de montage Utiliser une mèche de 3/16 po si le mur est en placoplâtre Utiliser une mèche de 7/32 po si le mur est en plâtre. MCR29434Next >