Series CDTV Duct Mount Carbon Dioxide / Volatile Organic Compound TransmitterSpecifications - Installation and Operating InstructionsBulletin AQ-CDTV-DThe Series CDTV Carbon Dioxide / Volatile Organic Compound (VOC) Transmitter reduces energy cost in buildings by lowering the amount of conditioned air based on the occupancy of the space. By detecting both CO2 and VOC, the transmitter can also detect fumes that may need to be exhausted during lower occupancy periods. Combining both measurements in one transmitter reduces both labor and material costs by only having to install one CDTV-VOC unit, instead of separate CO2 and VOC transmitters. Carbon dioxide measurements are taken using our proven Single-Beam Dual-Wavelength Non-Dispersive Infrared (NDIR) sensor. Our sensor allows users to get accurate measurements without waiting for the settling / correction periods of other logic based sensors. Transmitters can be used in buildings and applications that have 24 hour occupancy and can be calibrated on site to match environmental conditions for improved accuracy.The VOC measurement is a single value derived from the presence of substances including alcohols, aldehydes, aliphatic hydrocarbons, amines, aromatic hydrocarbons, CO, CH4, LPG, ketones, and organic acids. Although a standard unit of measure is not currently defined, the VOC measurement unit “ppm CO2 equivalent” used by the device is commonly used in the industry. The VOC measurement does not actually measure CO2, but instead senses and indicates an air quality value that approximately correlates perceived comfort levels to similar concentrations of CO2 in the environment. Single-beam dual-wavelength sensor advantages:• Automatically corrects for aging effects in occupied and unoccupied buildings • Perfect for hospitals and manufacturing plants that are occupied 24 hours per day• Measures actual unfiltered light intensity directly • Eliminates error from incorrect assumptions of gas concentration in theoretical logic assumption methodsSPECIFICATIONSRange: CO2: 0 to 2000 or 0 to 5000 ppm (depending on model); VOC: 0 to 2000 ppm CO2 equivalent.Accuracy: CO2: ±40 ppm +3% of reading.Temperature Dependence: ±8 ppm / °C at 1100 ppm.Non-Linearity: CO2: 16 ppm.Pressure Dependence: CO2: 0.13% of reading per mm of Hg.Response Time: CO2: 2 minutes for 99% step change; VOC: 5 minutes.Temperature Limits: 32 to 122°F (0 to 50°C).Power Requirements: 16 to 35 VDC / 19 to 28 VAC.Power Consumption: Average: 2 watts; Peak: 3.75 watts.Sensor: CO2: Single-beam, dual-wavelength NDIR; VOC: MEMS (metal oxide semiconductor).Output: Current: 0 to 20 mA, 4 to 20 mA, 0 to 10 mA, or 2 to 10 mA (depending on selection jumper, max 500 Ω); Voltage: 0 to 10 VDC, 2 to 10 VDC, 0 to 5 VDC, or 1 to 5 VDC (depending on selection jumper, min 500 Ω); Relay: SPST NO 2A @ 30 VDC.Weight: 5.6 oz (158.8 g).Agency Approvals: CE.INSTALLATIONMake sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.LEED® is a registered trademark of the U.S. Green Building Council.Disconnect power supply before installation to prevent electrical shock and equipment damage.WARNINGUpon powering the transmitter, the firmware version will flash on the display. A warm up period of 30 minutes is required for the transmitter to adjust to the current CO2 concentration.NOTICESelf calibration feature of the transmitter requires exposure to normal outdoor equivalent carbon dioxide level once every thirty days.NOTICEUse electrostatic discharge precautions (e.g., use of wrist straps) during installation and wiring to prevent equipment damage.CAUTIONAvoid locations where severe shock or vibration, excessive moisture or corrosive fumes are present.CAUTIONDo not exceed ratings of this device. Permanent damage not covered by warranty may result.CAUTION1/8˝[3.17]4-25/32˝[121.44]4-9/32˝[108.74]2-13/16˝[71.44]Ø3-5/16˝[84.14]11-49/64˝[298.85]Ø1-15/64˝[31.35]®DWYER INSTRUMENTS, INC.P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.Phone: 219/879-8000Fax: 219/872-9057www.dwyer-inst.come-mail: info@dwyermail.comMOUNTING1. Cut hole into duct large enough to insert probe.2. Attach housing ears to duct using the two self-tapping screws provided.3. Knock out an opening in the housing and attach an electrical fitting to route electrical wiring. PG11 & PG16 knockouts are molded into the housing.WIRINGUse maximum 18 AWG wire for wiring to terminals. Refer to Figure 4 for wiring information.Selection of Current and Voltage OutputsPrior to wiring, verify that the current/voltage configuration switches (positions 1 and 2) are set to the desired output type. Refer to Figure 1 to locate the configuration switches. See Figure 2 for diagram of the current/voltage selection switches. For voltage output selection, the output can be 0 to 10 VDC, 0 to 5 VDC, 2 to 10 VDC or 1 to 5 VDC. See Figure 3 for the type of voltage output selection switches (positions 3 & 4).Figure 2: Current/Voltage OutputSelection Jumper (PJ1 and PJ2)Figure 3: Output range selection jumperFigure 1: Diagram of circuit boardDOWN PUSHBUTTONCONFIGURATIONSWITCHESTERMINALBLOCKREMOTE DISPLAYCONNECTORUP PUSH BUTTONENTER PUSH BUTTONCO2 CONCENTRATIONOUTPUT SELECTIONVOC OUTPUT SELECTIONVOLTAGECURRENTVOLTAGECURRENT0-10 V0-20 mA2-10 V4-20 mA0-5 V0-10 mA1-5 V2-10 mACurrent / Voltage OutputsThe transmitter may be wired for current or voltage output for both carbon dioxide and VOC. The transmitter can be powered with either 16 or 35 VDC or 19 to 28 VAC. Wire the transmitter according to Figure 4.Thermistor and RTD OutputsThermistor and RTD passive outputs are located on terminals 7 and 8 and do not require any power. Passive temperature outputs are not polarity sensitive. Remote DisplayRemote display Model A-449 can be used to display the VOC or carbon dioxide. The mini USB plug of the remote display plugs into the receptor on the side of the housing. After a short warm up time, the display will begin to show the VOC or carbon dioxide measurements.ACCESSING MENU PARAMETERSStep 1: To enter the menu structure, press and simultaneously for 5 seconds (display will show RON parameter).Step 2: Press or to cycle between menu items.Step 3: Press to edit the value for the displayed menu item (SET will appear on display).Step 4: Press or to adjust the value of the menu item.Step 5: Press to save the changes (SET will disappear).Step 6: Repeat Steps 2 through 5 for each of the parameters.Step 7: To exit the menu at any time, press and hold and simultaneously for 5 seconds or wait 10 seconds without pushing any buttons.During the initial 5 minute warm-up phase, the VOC reading will be 0 ppm or an indeterminate value. After warming up, the device is operational and note the VOC output level will be approximately 450 PPM. If the device outputs 0 ppm after the warm-up, there is either an operational error or a disconnected sensor error and customer service should be contacted.Note: Reference menu descriptions for changing factory settings.PASSIVETEMPERATURESENSORRELAYCONTACTPOWERSUPPLYVOCRECEIVERCO2RECEIVERFigure 4: Active output wiring diagramOptional relay can be used as either a dry contact or low voltage switched circuit up to 2 A at 30 VDC.NOTICEMenu DescriptionsROC Define which output relay will be configured. CO2 default VOC Max CO2 / VOCRON Relay set point Sets the CO2 or VOC concentration which the optional relay is energized. Low limit: 0 PPM Factory setting: 1000 PPM High limit: 2000 PPM (CO2 or VOC), 5000 PPM (only CO2)ROF Relay off set point Sets the CO2 or VOC concentration which the optional relay is de-energized. Setting value lower than RON provides direct action for detecting high concentrations of CO2. Setting value higher than RON provides indirect action for detecting low concentrations of CO2. or on the LCD display will be lit to indicate when the relay is energized. Low limit: 0 PPM Factory setting: 950 PPM High limit: 2000 PPM (CO2 or VOC), 5000 PPM (only CO2)DSP Display configuration Determines the LCD display configuration during normal operation. The LCD display can indicate the CO2 concentration or VOC concentration. C CO2 concentration only V VOC onlyUNI Units selection Temperature and barometric pressure values can be displayed in US engineering units or SI engineering units. The factory default is to display US engineering units. US units Hg for barometric pressure SI units hPa for barometric pressureCOL CO2 low output range Sets the CO2 concentration for the lowest output (0 V, 1 V, 2 V, 0 mA, 2 mA, 4 mA). Low limit: 0 PPM Factory setting: 0 PPM High limit: 2000 PPM (CO2 or VOC), 5000 PPM (only CO2)COH CO2 high output range Sets the CO2 concentration for the highest output (10 mA or 5 V, 20 mA or 10 V). When COH is set above COL, the transmitter is direct acting and the output will increase with an increase in CO2 level. When COH is below COL, the transmitter is reverse acting and the output will increase with a decrease in CO2 level. Low limit: 0 PPM Factory setting: 2000 PPM (CO2 or VOC), 5000 PPM (only CO2) High limit: 2000 PPM (CO2 or VOC), 5000 PPM (only CO2)VOL VOC low output range Sets the VOC for the lowest output (0 V, 1 V, 2 V, 0 mA, 2 mA, 4 mA). To configure output for 450 PPM equal 0V, set VOL to 450 PPM. Even if power is lost the VOL setpoint will remain in memory. Low limit: 0 PPM Factory setting: 0 PPM High limit: 2000 PPM CO2 equivalent VOH VOC high output range Sets the VOC level for the highest output (10 mA or 5 V, 20 mA or 10 V). When VOH is set above VOL, the transmitter is direct acting and the output will increase with an increase in VOC level. When VOH is below VOL, the transmitter is reverse acting and the output will increase with a decrease in VOC level. Low limit: 450 PPM Factory setting: 2000 PPM CO2 equivalent High limit: 2000 PPM CO2 equivalentBAR Barometric pressure Sets the typical barometric pressure for the location where the transmitter is mounted. The factory setting is for standard pressure at sea level. Adjusting the barometric pressure gives a more accurate measurement, especially at higher elevations. Refer to the elevation charts in Figure 9 for typical barometric pressures at a given elevation. Low limit: 20.0 in Hg / 600 hPa Factory setting: 29.9 in Hg / 1013 hPa High limit: 32.0 in Hg / 1100 hPaCAL Calibration Calibrates in carbon dioxide sensor to a known gas valve. Read calibration instructions before using this feature. Hold for 5 seconds.Printed in U.S.A. 3419FR# 444204-00 Rev. 3©Copyright 2019 Dwyer Instruments, Inc.DWYER INSTRUMENTS, INC.P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.Phone: 219/879-8000Fax: 219/872-9057www.dwyer-inst.come-mail: info@dwyermail.comCALIBRATING CO2 SENSORStep 1: Slide probe into sealed calibration tube. Step 2: Tighten screws to lock probe in place.Step 3: Attach gas to the calibration tube.Step 4: Follow the steps in the accessing parameter section to access the calibration parameter (CAL).Step 5: Press the button.Step 6: Flow zero reference gas at 0.3 SLPM for 5 minutes.Step 7: Press and hold the button for 3 seconds.Step 8: Flow the full scale reference gas at 0.3 SLPM for 5 minutes.Step 9: Press and hold the button for 3 seconds.Step 10: Exit the parameter menu.Step 11: Loosen screws to release probe.Step 12: Remove probe from sealed calibration tube.MAINTENANCE/REPAIRUpon final installation of the Series CDTV, no routine maintenance is required. The Series CDTV is not field serviceable and should be returned if repair is needed. Field repair should not be attempted and may void warranty.WARRANTY/RETURNRefer to “Terms and Conditions of Sales” in our catalog and on our website. Contact customer service to return a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.MODEL CHARTSeriesCDTV-2D4A4-RLYExample: CDTV-2D4A4-RLYRange250 to 2000 ppm CO2 range0 to 5000 ppm CO2 rangeConfigurationDNDuctNorth American style wall mountCO2 Output44 to 20 mA / 0 to (5 or 10) VDCTemperature Output0ABCDEFNone10 KΩ NTC thermistor type III10 KΩ NTC thermistor type II3 KΩ NTC thermistorPt100 Ω RTDPt1000 Ω RTD20 KΩ NTC thermistorVOC Output44 to 20 mA / 0 to (5 or 10) VDCOptionsRLYFCCOCLCDRelayFactory calibration certificateCertificate of calibrationLCD display (wall only)US Customary Unitsftin Hg040080012001600200024002800320036004000440048005200560060006400680072007600800084008800920096001000029.9229.5029.1028.6928.2927.9027.5127.1326.7626.3926.0225.6625.3024.9524.6024.2623.9323.6023.2722.9422.6322.3122.0021.7021.4021.40RESISTANCE VS TEMPERATURE TABLETemperatureResistance Curves (in Ohms)°C°FABCDEF-55-50-45-40-35-30-25-20-15-10-505101520253035404550556065707580859095100105110115120125130135140145150-67.0-58.0-49.0-40.0-31.0-22.0-13.0-4.05.014.023.032.041.050.059.068.077.086.095.0104.0113.0122.0131.0140.0149.0158.0167.0176.0185.0194.0203.0212.0221.0230.0239.0248.0257.0266.0275.0284.0293.0302.0607800.00441200.00323600.00239700.00179200.00135200.00102900.0078910.0061020.0047540.0037310.0029490.0023460.0018780.0015130.0012260.0010000.008194.006752.005592.004655.003893.003271.002760.002339.001990.001700.001458.001255.001084.00939.30816.80712.60623.60547.30481.80425.30376.40334.00297.20265.10237.00963849.00670166.00471985.00336479.00242681.00176974.00130421.0097081.0072957.0055329.0042327.0032650.0025392.0019901.0015712.0012493.0010000.008057.006531.005326.004368.003602.002986.002488.002083.001752.001480.001255.001070.00915.50786.60678.60587.60510.60445.30389.60341.90301.00265.80235.30208.90186.10289154.70201049.80141595.50100943.7072804.3053092.2039126.3029124.3021887.1016598.7012698.109795.007617.605970.304713.603747.903000.002417.101959.301597.801310.401080.60895.80746.40624.90525.60444.00376.50321.00274.65235.98203.58176.28153.18133.59116.88102.5790.3079.7470.5962.6755.8378.3280.3182.2984.2786.2588.2290.1992.1694.1296.0998.04100.00101.95103.90105.85107.79109.74111.67113.61115.54117.47119.40121.32123.24125.16127.08128.99130.90132.80134.71136.61138.51140.40142.29144.18146.07147.95149.83151.71153.58155.46157.33783.2803.1822.9842.7862.5882.2901.9921.6941.2960.9980.41000.01019.51039.01058.51077.91097.41116.71136.11155.41174.71194.01213.21232.41251.61270.81289.91309.01328.01347.11366.11385.11404.01422.91441.81460.71479.51498.31517.11535.81554.61573.32394000.001646200.001145800.00806800.00574400.00413400.00300400.00220600.00163500.00122280.0092240.0070160.0053780.0041560.0032340.0025360.0020000.0015892.0012704.0010216.008264.006722.005498.004520.003734.003100.002586.002166.001822.601540.001306.401112.60951.00815.80702.20606.40525.60N/AN/AN/AN/AN/ASI UnitsmhPa0100200300400500600700800900100011001200130014001500160017001800190020002100220023002400250010131002990979968957946935924914904893883873863853844834824815806797787779770761Figure 5: CDTV Model ChartFigure 6: Elevation ChartFigure 7: Resistance vs TemperatureThis symbol indicates waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.Next >