DS-BASRTB00-AB3 Data Sheet – BASrouter The BASrouter is a compact BACnet multi-network router which provides versatile stand-alone routing between BACnet/IP, BACnet Ethernet (ISO 8802-3), and BACnet MS/TP networks. The BACnet router is web page configurable and it is powered by 24 VAC/VDC. The BASrouter has a number of troubleshooting/diagnostic capabilities. The BACnet MS/TP “Status” webpage contains a graphical table of all of the MS/TP devices on the network and their status. Also provided are network statistics, in addition to a BACnet/IP “Routing” webpage with a discoverable routing table which is useful when setting up or troubleshooting a BACnet network. BASrouter — BACnet ® Multi-Network Router (3.0 Version) Versatile Routing Between … • BACnet/IP and BACnet MS/TP • BACnet Ethernet and BACnet MS/TP • BACnet/IP and BACnet Ethernet • BACnet/IP and BACnet Ethernet and BACnet MS/TP • Two BACnet/IP Networks (between two UDP ports) IP Network Support • Web server for commissioning and troubleshooting • DHCP option to automatically acquire IP address • BACnet/IP Broadcast Management Device (BBMD) • Foreign Device Registration (FDR) Flexible Communications • 10/100 Mbps Ethernet with auto-negotiation and Auto-MDIX • Optically isolated MS/TP port • MS/TP baud rates range from 9.6–76.8 kbps Convenient Installation • 24 VAC/VDC (± 10%), 47–63Hz input voltage • Din-rail mounted Network diagnostics • Webpage with graphical network map of all 128 MS/TP master devices and their status • MS/TP error count • BACnet network traffic statistics • Discover and View current BACnet routing table BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BACnet International.DS-BASRTB00-AB3 Data Sheet – BASrouter 2 BASrouter — BACnet ® Multi-Network Router The BAS Router is housed in a metal case that mounts on 35-mm DIN-rail and is powered from a 24 VAC/VDC (± 10%) source. There is one MS/TP port and one 10/100 Mbps Ethernet port. The MS/TP port offers an optically-isolated transceiver. It has a removable 3-pin terminal block for the EIA-485 connection. The Ethernet port offers a shielded RJ-45 connector. Auto-negotiation and Auto-MDIX allow this port to automatically match connections to the attached equipment. Therefore, either straight-through or crossover CAT5/6 cable can be used for hook-up. A resident web server allows for commissioning, and troubleshooting using a standard web browser. A reset switch is provided on the router to return the unit to the factory default IP address of 192.168.92.68 (/24). Three LEDs are provided: The power LED glows green when proper power is provided. A bicolour Ethernet LED glows green for 100 Mbps, and yellow for 10 Mbps, and indicates activity by flashing. MS/TP LED flashes green when valid MS/TP traffic is received. When flashing continuously and without long interruptions, the MS/TP receive LED is a good indicator that the MS/TP network is operational. Internal MS/TP bias and termination jumpers allow flexible bias and termination options. They can be removed for mid-span installations. Power Input 24 VAC/VDC 4 VA half-wave regulated design allows power sharing with other half-wave devices. Ethernet 10/100 Mbps Ethernet with auto-negotiation and Auto-MDIX. Protocols supported include HTTP, IP, UDP, TCP, BACnet Ethernet, and BACnet/IP. MS/TP 3-wire isolated EIA-485 connection with support for 2-wire non-isolated devices Power LED Power OK indicator MS/TP LED Monitors MS/TP activity Reset IP Switch returns BAS Router to default IP address and default password settings. Ethernet LED Monitors Ethernet activityDS-BASRTB00-AB3 Data Sheet – BASrouter 3 Web Page Configuration The Status screen is always operational as long as the BASrouter is powered. It consists of MS/TP Device Status table, Network Errors count, and Statistics on BACnet networks to which the BASrouter is connected. The Status page will automatically refresh every 5 seconds with the updated status on networks and devices — so you can observe the network state changes and gain insight into the condition of the BACnet network (as seen by the BASrouter). These statistics are retained over time, unless the BASrouter is powered off or rebooted from the main web page using the “Save Changes” button, then all Status page parameters are reset. The “Reset Statistics” button on Status page will reset Network Errors count, and Statistics, but retain the MSTP Device Status table history. For more information on the Status page refer to the BASrouter User Manual. Status Screen 3.0.3 BASRTB Status BASRTB Configuration BASRT-BDS-BASRTB00-AB3 Data Sheet – BASrouter 4 Routing Table Multiple networks, possibly employing different physical layer technologies, may be interconnected by BACnet routers to form a BACnet internetwork. The Routing table web page provides a routing table which contains information about the network topology of the surrounding BACnet internetwork such as Destination Network, Network Type, Connecting Network, and Network Status. This table will be blank upon powering the BASrouter. Click the “Discover Routing Table” button to discover other routers on the BACnet network which will send a “Who-Is-Router-To- Network” message and fill the table with the discovered BACnet routers. BASRTB Routing StatusDS-BASRTB00-AB3 Data Sheet – BASrouter 5 BAS Router Parameters Main Settings Device Parameters Default Value Description Device Name BASRT-B xxxxxx The unique default value ends with the last 6 characters of the unit’s Ethernet MAC address. You can edit it to be up to 20 characters. Device Instance 0 The router device instance is a 22-bit decimal value (0–4,194,303). Each BACnet device has a unique device instance. BACnet Ethernet Parameter Default Value Description BACnet Ethernet Network 0 16-bit decimal value (1–65534). Each BACnet network, regardless of technology, must have a unique network number. By retaining the default value of 0, BACnet Ethernet routing is disabled. BACnet/IP Parameters Default Value Description BACnet/IP UDP Port BAC0 16-bit hex value (0–FFFF) is set to BAC0 as the default value and should be used. All BACnet/IP devices on the same BACnet network must have the same UDP port assignment. For other assignments choose ports in the range from BAC1 to BACF while verifying that these ports are available. BACnet/IP Network 1 16-bit decimal value (1–65534). Each BACnet network, regardless of technology, must have a unique network number. It is recommended that all subnets of the same BACnet/IP network be given the same BACnet network number as well. IP Address 192.168.92.68 IP address in dotted decimal format. Select a valid address in the range from 0.0.0.1 through 255.255.255.254. IP Subnet 24 Decimal value (0–30) in the “slash” notation is the number of bits with a “1” in the mask. The default value of 24 corresponds to 255.255.255.0 in the dotted decimal format. All devices on the same subnet which communicate via BACnet/IP should use the same subnet mask. IP Gateway 192.168.92.1 IP Gateway address in dotted decimal format. Select a valid address in the range from 0.0.0.1 through 255.255.255.254. MS/TP Parameters Default Value Description MS/TP MAC Address 0 Decimal value (0–127) represents the MAC address of the router’s MS/TP port. Lower MAC address numbers are preferred. MS/TP Network 2001 16-bit decimal value (1–65535). Each BACnet network, regardless of technology, must have a unique network number. Max Masters 127 This 8-bit decimal value (1–127) represents the highest master MAC address in the MS/TP network. If the highest value MAC address is unknown or if additional devices are to be added in the future above the current highest MAC address, use the default setting of 127. Max Info Frames 100 This is the maximum number of messages (1–100) that can be routed onto the MS/TP network by the router per token pass. Values above 20 are typical. MS/TP Baud Rate 38400 The baud rate of the MS/TP network can be 9600, 19200, 38400 or 76800 bps. All MS/TP devices on the same MS/TP network must use the same baud rate. Auto-bauding devices will set their baud rates to that of the BAS Router. MS/TP Tolerance Lenient Affects the degree to which interoperability with devices is successful. Lenient option causes less efficient traffic but optimises interoperability.DS-BASRTB00-AB3 Data Sheet – BASrouter 6 BAS Router Parameters Advanced Settings — BBMD BBMD Parameters Default Value Description BBMD Enable Unchecked Check to enable BACnet/IP Broadcast Management Device (BBMD). BBMD UDP Port Primary Normally the primary port is selected. The secondary port is used in very special applications. Accept FDR Checked Uncheck to disable foreign devices from registering with this router. Secondary BACnet/IP UDP Port 0000 Enter secondary UDP port as a 16-bit hex value (0-FFFF) when operating with two BACnet/IP BACnet networks. In this case use BAC1 if it is available. Secondary BACnet/IP Net 0 Assign a unique network number from all other BACnet networks. Public IP Address 0.0.0.0 Enter the public IP address in dotted decimal format of the IP router in the system. BAS Router Additional Tables and Screens Table or Screen Name Description Broadcast Distribution Table (BDT) This table must contain the entries of any other BBMDs located on the network. The IP address and subnet mask of the BBMDs must be listed. Foreign Device Table (FDT) This table is automatically lists all the foreign devices that have registered with this router. Information includes IP address, port number, time-to-live, and remaining time on its lease. Status Screen Displays a log of events (automatically refreshed each second) to facilitate troubleshooting. Use this information when discussing any routing issues with Contemporary Controls’ technical support. Security Screen Authentication menu. Allows the user to change user name and password. Depressing the Reset IP button restores user name and password to default settings.DS-BASRTB00-AB3 Data Sheet – BASrouter 7 BACnet Protocol Implementation Conformance (PIC) Statement 15 February 2018PI-BASRTB00-AA1 BASrouter BACnetMulti-Network Router BACnet Protocol Implementation Conformance Statement(Annex A) Date:15 February 2018 Vendor Name:Contemporary Controls Product Name:BASrouter Product Model Number:BASRT-B Applications Software Version:3.0.3Firmware Revision:3.0.3BACnet Protocol Revision:13 Product Description: The BASrouter from Contemporary Controls provides BACnet routing between BACnet/IP, MS/TP and ISO 8802-3 networks. It also supports BACnet Broadcast Management Device (BBMD) and Foreign Device Registration (FDR). By supporting two BACnet/IP UDP ports it can also assist BACnet messages in traversingNAT routers. BACnet Standardized Device Profile (Annex L): BACnet Router (B-RTR) BACnet Broadcast Management Device (B-BBMD) List all BACnet Interoperability Building Block Supported (Annex K) : DS-RP-B Data Sharing —ReadProperty –B DM-DOB-B Device Management —Dynamic Object Binding–B NM-RC-B Network Management —Router Configuration –B DS-RPM-B Data Sharing –ReadPropertyMultiple –B DM-DDB-B Device Management —Dynamic Device Binding –B NM-BBMDC-B Network Management —BBMD Configuration –B Segmentation Capability: Segmentation is not supported. Standard Object Types Supported: Object Type SupportedCan Be Created DynamicallyCan Be Deleted Dynamically DeviceNoNo No optional properties are supported. NOTE:The above object is directed supported on the router. The router will pass to the appropriate network all BACnet communications not directed to the router. Data Link Layer Options: BACnet IP, (Annex J)BACnet Broadcast Management Device (BBMD) BACnet IP, (Annex J), Network Address Translation (NAT Traversal) ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s): MS/TP master (Clause 9), baud rate(s):9600; 19,200; 38,400; 76,800 MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): Point-To-Point, modem, (Clause 10), baud rate(s): LonTalk, (Clause 11, medium: Device Address Binding: Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) YesNo Networking Options: Router, Clause 6 —routing between BACnet/IP,ISO 8802-3, and MS/TP Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously. ISO 10646 UTF-8 If this product is a communication gateway, describe the types of non-BACnet equipment/network(s) that the gateway supports: No gateway support.DS-BASRTB00-AB3 Data Sheet – BASrouter 8 Wiring Diagrams Since the BAS Router incorporates a half-wave rectifier circuit, it can share the same 24 VAC power with other half-wave rectified devices. It can also be powered from a 24 VDC source. A redundant power connection exists for back-up power schemes. The BAS Router incorporates a 3-wire optically-isolated EIA-485 interface for the MS/TP connection, allowing better circuit protection and noise immunity. To connect to other 3-wire devices simply make a one-to-one connection to the other devices. But when connecting to 2-wire non-isolated devices, the signal common (SC) on the BAS Router must share the reference used by the 2-wire devices. This is accomplished by tying the SC pin to COM on the BAS Router and by grounding the low-side of each power supply on all connected devices. In this way all EIA-485 transceivers share the same earth reference. Notice that the SC pin is signal common and not a shield pin. MS/TP PinFunction +Signal High –Signal Low SCSignal Common Ethernet PinFunction 1Signal 1 2Signal 2 3Signal 3 4N/C 5N/C 6Signal 4 7N/C 8N/C Connector Pin AssignmentsMechanical DrawingDS-BASRTB00-AB3 Data Sheet – BASrouter September, 2018 www.ccontrols.com Specifications Ordering Information ModelRoHSDescription BASRT-BBASrouter BACnet/IP to MS/TP to Ethernet DIN-Rail Mount Power Requirements 24 VDC ±10% 2 W or 24 VAC ±10% 4 VA 47–63 Hz Operating Temperature 0°C to 60°C Storage Temperature −40°C to 85°C Relative Humidity 10–95%, non-condensing Protection IP30 Ethernet Communications IEEE 802.3 10/100 Mbps data rate 10BASE-T, 100BASE-TX physical layer 100 m (max) CAT5 cable length MS/TP Communications ANSI/ASHRAE 135 (ISO 16484-5) 9600, 19200, 38400, 76800 bps data rate EIA-485 physical layer 1200 m (max) cable length LEDs Power Green = power OK Ethernet Green = 100 Mbps Yellow = 10 Mbps Flash = activity MS/TP Flashing Green = receive activity Regulatory Compliance CE Mark; CFR 47, Part 15 Class A; RoHS UL 508, C22.2 No. 142-M1987Next >