Technical Data 281355 Fluidchilled or hot water, up to 60% glycol Flow characteristicequal percentage Controllable flow range75° Valve Size [mm]0.5” [15] Pipe connectionNPT female ends Housingforged brass Ballstainless steel Stemstainless steel SeatPTFE O-ringEPDM Characterized discincorporated into the ball DiaphragmEPDM Body Pressure Rating360 psi Maximum Allowable Operating Temperature 212°F [100°C] * Close-off pressure ∆ps200 psi Valve Accuracy±5% Weight6.61 lb [3.0 kg] GPM4.3 Fluid Temp Range (water)36...212°F [2...100°C] Leakage rate0% Servicingmaintenance-free * If temperature exceeds 212°F operating range due to a boiler control failure the valve will safely contain the hot water but manufacturers product warranty becomes invalid. Valve and actuator replacement is at the expense of others. Application The PIQCV zone valves with its pressure independent technology are suited for large commercial buildings where higher close-off and dynamic balancing is required. Common applications include unit ventilators, fan coil units, VAV reheat coils, fin tube casing, radiant panels and duct coils. The valve fits in space restricted areas and can be assembled without the use of tools. Suitable Actuators Non-SpringElectronic fail-safe Z2050QPT-FCQBCQKB(X) Dimensions (Inches [mm]) EF D B A C CQK ABCDEF 4.9” [125]4.2” [107]4.8” [122]3.5” [89]2.4” [62]1.3” [33] Safety Notes WARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov Z2050QPT-F Technical Data Sheet 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 05/31/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.Dimensions (Inches [mm]) E F D B A C CQ ABCDEF 4.9” [125]4.2” [107]4.5” [114]3.4” [87]2.4” [62]1.3” [33] Z2050QPT-F Technical Data Sheet 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 05/31/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.Technical Data 333704 Power Supply24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power consumption in operation0.4 W Power consumption in rest position 0.3 W Transformer sizing1 VA (class 2 power source) Electrical Connection18 GA plenum cable, 3 ft [1 m], with 1/2” conduit connector Overload Protectionelectronic thoughout 0...90° rotation Operating Range2...10 V, 4...20 mA w/ ZG-R01 (500 Ω , 1/4 W resistor) Angle of rotation90°, adjustable with mechanical stop Position indicationpointer Running Time (Motor)75 s Ambient humiditymax. 95% r.H., non-condensing Ambient temperature35...104°F [1.7...40°C] Storage temperature-40...176°F [-40...80°C] Degree of ProtectionIP40, NEMA 2 Housing materialUL94-5VA Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU Noise level, motor35 dB(A) Servicingmaintenance-free Quality StandardISO 9001 Weight0.44 lb [0.20 kg] † Use flexible metal conduit. Push the listed conduit fitting device over the actuator’s cable to butt against the enclosure. Screw in conduit connector. Jacket the actuators input wiring with listed flexible conduit. Properly terminate the conduit in a suitable junction box. Rated impulse Voltage 800V. Type of action 1. Control pollution degree 3. Application Non-Fail Safe proportional ZoneTight actuator. Valve selection should be done in accordance with the flow parameters and system specifications. The actuator is mounted directly to the valve without the need for tools or additional linkage. The actuator operates in response to a 2...10 V or 4...20mA control signal. Safety Notes WARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov CQX24-SR Technical Data Sheet 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 05/31/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring Diagrams INSTALLATION NOTES Actuators may be connected in parallel. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC. Only connect common to negative (-) leg of control circuits. A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC. Actuators with plenum cable do not have numbers; use color codes instead. Meets cULus requirements without the need of an electrical ground connection. ! WARNING! LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. (–) (+) Line Volts 500 1/4 watt Control Signal VDC / mA 7 Blk (1) Red (2) Wht (3) Org (5) Common + Hot Y Input U Output Feedback Signal (+) 23185 24 VAC Transformer CQX24-SR Technical Data Sheet 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 05/31/2020 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >