Technical Data140311Servicechilled or hot water and steamApplicable Valve Size2” [51], 2-1/2” [64], 3” [80], 4” [101], 5” [127], 6” [152]Stem316 stainless steelFrame, plate, basealuminum, steel (fits Warren Type 20,22,23,30, and 32) and Belimo G6/G7CollarsteelCouplingGF Nylon suppliedHousing MaterialAluminum die cast and plastic casingStem AdaptorsteelStroke2” [50 mm]Mounting Position360°Media Temperature Range (Water)20°F to 250°F [-7°C to 120°C]Media Temperature Range (Steam)32°F to 338°F [0°C to 170°C]Weight5.7 lb [2.6 kg]For close-off pressure reference Select Pro or Retrofit Technical Documentation.ApplicationThe WGVL retrofit kit is designed to easily attach AVK, EV and RV series actuators to select Warren globe valves. Its casted base and lower lock nut allow the WGVL to be mounted on 2-1/2” to 6” two-way or three-way valves in both normally open and normally closed configurations.OperationThe WGVL linkage with actuator will provide 50 mm of linear travel to accommodate a wide range of valve sizes.Default/ConfigurationThe default set up for a WGVL linkage will be factory installed along with an AVK or EV, RV series actuator. Included in the kit will be all the necessary hardware to facilitate mounting to the Warren valve.Suitable Actuators Non-SpringElectronic Fail-SafeWGVLEVB(X), RVB(X)AVKB(X)Dimensions (Inches [mm])BCDAEVB, EVX, RVB, RVXABCD10.2” [259]5.50” [139.7]9.20” [234]12.22” [310.4]WGVL Warren Globe Valve LinkageFor Use with AVK and EV and RV Series Actuators800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 08/12/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Dimensions (Inches [mm])BCDAAVKB, AVKXABCD10.4”’ [264]5.50” [139.7]10.3”’ [262]10.9” [276]WGVL Warren Globe Valve LinkageFor Use with AVK and EV and RV Series Actuators800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 08/12/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Technical Data102692Power Supply24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10%Power Consumption Running5 W Power Consumption Holding2 W Transformer Sizing9.5 VA (class 2 power source)Electrical Connection3 ft, 18 GA plenum rated cable with 1/2” conduit connector protected NEMA 2 (IP54)Overload Protectionelectronic throughout full strokeElectrical Protectionactuators are double insulatedOperating Range Y2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor), variable (VDC, PWM, floating point, on/off)Input Impedance100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, floating point and On/OffFeedback Output U2 to 10 VDCStroke1.25” [32 mm]Linear Force450 lbf [2000 N force] Direction of Rotation (Motor)reversible with switchDirection of Rotation (Fail-Safe)reversible with switchPosition Indicationstroke indicator on bracketManual Override5 mm hex crank (3/16” Allen), suppliedRunning Time (Motor)90 sec (default), Optional (90 or 150 sec)Running Time (Fail-Safe)35 secBridge Time2 sec delay before fail-safe activatesPre-charging Time5 to 20 secondsHumidity5 to 95% RH non-condensingAmbient Temperature Range-22°F to +122°F [-30°C to +50°C]Storage Temperature Range-40°F to +176°F [-40°C TO +80°C]HousingNEMA 2, IP54, UL enclosure type 2Housing MaterialAluminum die cast and plastic casingAgency Listings†cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/ECNoise Level (Motor)<60 dB (A) Noise Level (Fail-Safe)<60 dB (A) Servicingmaintenance freeQuality StandardISO 9001Weight6.4 lb [2.9 kg]† Use flexible metal conduit. Push the listed conduit fitting device over the actuator’s cable to butt against the enclosure. Screw in conduit connector. Jacket the actuators input wiring with listed flexible conduit. Properly terminate the conduit in a suitable junction box. Rated impulse Voltage 800V. Type of action 1. Control pollution degree 3.AVKB24-MFTModulating, Fail-Safe Operation, Linear, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 08/12/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsINSTALLATION NOTESActuators may be connected in parallel. Power consumption and input impedance must be observed.Actuators may also be powered by 24 VDC.A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.For triac sink the common connection from the actuator must be connected to the hot connection of the controller. Contact closures A & B also can be triacs. A & B should both be closed for the triac source and open for triac sink.For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not compatible.IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).Actuators with plenum cable do not have numbers; use color codes instead.Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blk (1) - CommonRed (2) Hot Wht (3) Y1 InputOrg (5) U Output LineVolts24 VAC Transformer2 to 10 VDCFeedback Signal(+)(–)318On/Off LineVolts (–) (+)24 VAC TransformerBlk (1) – CommonRed (2) + HotWht (3) Y1 InputOrg (5) U OutputABABDirection of rotation switchABFeedback Signal 2 to 10 VDC2101818188912Floating Point Blk (1) - CommonRed (2) + HotWht (3) Y1 InputOrg (5) U Output(–)(+)LineVolts24 VAC TransformerControl SignalVDC/mA31875001/4 WVDC / 4 to 20 mA Functions0%50%100%Control mode acc. to YMinMidMaxNormalabc500Blk (1) - CommonRed (2) + HotOrg (5) U OutputWht (3) Y1 Input(–)(+)LineVolts24 VAC Transformer (AC Only)BCA1/4 WVDC/mAControl Signal187Override Control Min, Mid, Max PositionsAVKB24-MFTModulating, Fail-Safe Operation, Linear, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 08/12/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >