www.belimo.us VAV-Compact MP • 2020-03 • Subject to Change Product informationVAV-Compact MP A pressure sensor, digital VAV controller and damper actuator all in one, providing a compact solution with a communications capability for pressure-independent VAV and CAV systems in the comfort zone • Control (0)2…10 V or via MP-Bus • MP-Bus: Control device with MP interface, Gateway: BACnet / LON / Modbus / KNX • Conversion of sensor signals • Service socket for operating devices • NFC interface for smartphone App Product Features Application The VAV-Compact has PI control characteristics and is used for pressure-independent control of VAV units in the comfort zone. Pressure measurement The integrated D3 differential pressure sensor is also suitable for very small volumetric flows. The maintenance-free sensor technology enables versatile applications in the comfort zone: in residential construction, offices, hospitals, hotels, cruise ships, etc.. Actuator VAV unit manufacturers offer different actuator variants (rotary or linear actuator) for different VAV units structures. Control function Volumetric flow (VAV-CAV) or Open-Loop (for integration in an external VAV control loop). VAV – variable volumetric flow Demand-dependent setting of volumetric flows V min max on a modulating reference variable (0/2…10 V / MP-Bus), e.g. room temperature / CO2 levels, DDC or Bus system, for energy- saving air conditioning in individual rooms or zones. CAV – constant volumetric flow Step mode (via switching contact) for constant volume applications CLOSED / V min / V max / OPEN. DCV – Demand Controlled Ventilation Can be used in conjunction with third party controller or BMS in demand controlled ventilation applications. Bus operation Belimo MP devices (VAV / damper and valve actuators) can be connected to a MP master device via the MP-Bus: –MP partner solution: DDC controller with integrated MP-Bus protocol –Gateway for the integration in BACnet and Modbus applications In Bus operation an additional sensor (0…10 V / passive) such as temperature or a switch for the higher-level system can be integrated. See separate MP-Bus documentation at www.belimo.us. Operating and service devices Smartphone Assistant App: Contactless operating via the integrated NFC interface*. Service tool ZTH, PC-Tool service socket: locally pluggable or via MP-Bus. Electrical connection The connection is made with the integrated connection cable. Type overview MP versions TypeTorquePower consumptionRatingWeight LMV-D3-MP45 in-lb [5 Nm]2 W3.5 VAApprox. 1.1 lb [500 g] NMV-D3-MP90 in-lb [10 Nm]3 W5 VAApprox. 1.5 lb [700 g] LHV-D3-MP34 lbf [150 N]2.5 W4.5 VAApprox. 1.2 lb [550 g] OEM version In addition to the standard Belimo version, there are OEM VAV-Compact versions available for VAV unit manufacturers' variants. These versions are customized and labelled specifically for OEM on the sensors, damper spindles and fastening systems used. See documentation of the VAV unit manufacturer. Designation, e.g.: LMV-D3-MP ABC (ABC = Customer designation) Other versions The VAV-Compact is also available with a built-in interface for direct integration in BACnet and Modbus. MFT version also available. See www.belimo.us for more information and documentation. LMV-D3-MP Belimo Assistant App LHV-D3-MP NMV-D3-MP * Android devices only. Zip-BT-NFC required for iPhone devices.VAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions VAV-Compact MP • 2020-03 • Subject to Change www.belimo.us Electrical installation Notes – Supply via safety isolating transformer! – In conventionally controlled systems it is recommended that the connections 1 to 5 (PP) are led to accessible terminals (e.g. floor distributor) in order to allow remote access for diagnostics and service work. ! No.DesignationWire colorFunction – black AC/DC 24 V supply red YwhiteReference signal / override / sensor orange – Actual value signal – MP bus connection Safety notes ! •The device must not be used outside the specified field of application, especially not in aircraft or in any other airborne means of transport. • Outdoor applications: possible only in the absence of direct effects on the actuator from (sea) water, snow, ice, sunlight and aggressive gases and when it is guaranteed that the ambient conditions do not deviate at any time from the limit values specified in the datasheet. • Only authorized specialists may carry out installation. All applicable legal or institutional installation regulations must be complied with during installation. • The device may only be opened at the manufacturer's site. It does not contain any parts that can be replaced or repaired by the user. • Cables must not be removed from the device. • When calculating the torque required, the specifications supplied by the damper manufacturers (cross-section, construction, place of installation), and the ventilation conditions must be observed. • The device contains electrical and electronic components and is not allowed to be disposed of as household refuse. All locally valid regulations and requirements must be observed. See separate documentation for description of functions and applicationsVAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions www.belimo.us VAV-Compact MP • 2020-03 • Subject to Change Technical Data Electrical data Nominal voltageAC/DC 24 V, 50/60 Hz Operating rangeAC 19.2 ... 28.8V / DC 21.6 ... 28.8V Performance dataSee Overview of types (page 1) Connecting3 ft [1 m] 18 GA plenum rated cable, [4 x 0.75 mm], preassembled Volumetric flow controllers Control functionVAV/CAV and Open-Loop V nom 1) Application specific nominal volumetric flow setting, dependent upon VAV box parameters. Used for calibration. ∆p @ V nom 1) Change in pressure at nominal volumetric flow setting, dependent upon VAV box parameters. Used for calibration. V max 20 … 100 % of V nom , adjustable Max flow required in application V min 0 … 100 % of V nom, adjustable (< V max) Analogue control - VAV Mode (Y)0 … 10 V / 2 … 10 V / (Y and U5 individually) adjustable, input resistance 100k (0/4…20 mA with 500 resistance) Actual value signal (U)0 ... 10 V / 2 ... 10 V, max. 0.5 mA Volumetric flow / damper position / ∆p, selectable Stepped control - CAVOperating stages CLOSED / V min / V max / OPEN Bus modeCommunicationBelimo MP bus AddressingMP1 … 8 (analog control: PP) Bus masterDDC with MP interface (see Belimo MP Partners List www.belimo.eu) Control The setpoint specification in % between the set V min / V max values Sensor integrationPassive sensor (PT1000, 10K2, ..) or active sensor (0…10 V) Switching contact (0 / 1) (switching capacity 16 mA @ 24 V) Operation and servicing Assistant App (Smartphone)Contactless connection via the integrated NFC interface Service tool ZTH, PC-ToolLocal plug / Remote via PP/MP connection or MP master LED Supply , status and communication display Push-buttonAddressing, angle of rotation adaptation and test function Actuator Rotary/linear versionBrushless, non-blocking actuator with power-save mode Direction of rotationleft / right or up / down, adjustable Angle of rotation95° or 4 [100] /8 [200] /12 [300] in [mm] stroke, adjustable mechanical or electronic limiting Gear disengagementPush-button self-resetting without functional impairment Position indication Mechanical or accessible (Tool, Bus-Master) Spindle holderSpindle clamp for round and square shafts form fit, OEM versions Volumetric flow measurement Differential pressure sensorBelimo D3 sensor, dynamic measurement principle Measurement range, operating range-0.08…2 in WC [-20…500 Pa], 0…2 in WC [0…500 Pa] Overload capability± 12 in WC [±3000 Pa] Altitude compensationAdaptation to system altitude (adjustable between 0...9800 ft. [0…3000 m] above sea level) Installation positionAny, no reset necessary Materials in contact with mediumGlass, epoxy resin, PA, TPE Measuring air conditionsComfort zone 32...122°F [0…50°C ]/ 5…95% rH, non-condensing SafetyProtection class IEC/EN III Safety extra-low voltage Degree of protection IEC / EN IP54 EMC CE according to 2014/30/EU Certification IEC/ENIEC/EN 60730-1 and IEC/EN 60730-2-14 Rated current voltage Supply / control 0.8 kV Control pollution degree Ambient temperature -22...+122°F [-30...50°C] Non-operating temperature -40...+176°F [-40...80°C] Ambient humidity range95% r.h., non-condensing MaintenanceMaintenance-free. Depending on the application, the differential pressure sensor (measuring cross, disc, ..) of the VAV unit is checked occasionally and cleaned if required. UL listingcULus according to UL 60730-1A/-2-14, UL 2043 1) Set during calibration. Dependent upon VAV box parameters. FCC: see US-relevant notes on page 12VAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions VAV-Compact MP • 2020-03 • Subject to Change www.belimo.us CAV – step mode CLOSED / V min / V max / OPEN Tool / Actual value signal CAV control VAV-Compact can be adapted to the desired CAV function pattern for constant volumetric flow applications with PC-Tool by using the "CAV function": – Damper CLOSED – V min – V max – damper OPEN (standard) Wiring diagrams abcde 1235 YU + ~ – T ** PC-Tool "CAV Function" setting: 2 ... 10 V, Shut-off level 0.1 V CAV Function CLOSED – V min – V max – OPEN (standard) Signal Switching terminal 3 33333 Mode 2 ... 10 VCLOSEDV min CLOSED *V max OPEN * Mode 0 ... 10 VV min V min CLOSED *V max OPEN * PC-Tool "CAV Function" setting: CLOSED – V min – V max . Shut-off level CLOSED: 0.1 V VAV – variable operation V min V max Wiring diagrams Example 1: VAV, analogue reference signal Example 2: VAV with shut-off (CLOSED), 2...10 V mode 1235 + ~ – T UY ZUL 1235 UY ABL T T 1235 + ~ – T UY ZUL 1235 UY ABL T a b Reference signal V min ... V max 2…10 V Tool / Actual value signal Tool / Actual value signal Option Master/Slave Circuit Reference signal Slave Reference signal V min ... V max 0…10 V / 2…10 V Tool / Actual value signal Tool / Actual value signal Option Master/Slave Circuit Reference signal Slave a Damper CLOSED b VAV mode Description: Damper CLOSED via 0...10 V reference signal (Mode 2...10 V) Setting parameters: Mode 2…10 V, Shut off level 0.1 V or 0.5 V If the required switching threshold of 0.1 V cannot be attained, the value can be switched to 0.5 V with PC-Tool. Function: Standard 0.1 V: Shut-off level 0.5 V: Damper CLOSED <0.1 V <0.5 V V min >0.1...2 V >0.5 V...2 V V min ... V max 2...10 V 2...10 V In CAV applications shut-off level must not be set to 0.5 V, otherwise the open connection 3 is interpreted as damper CLOSED. Notes • Note that the contacts are mutually interlocking. • DC supply: * c and e are not available with DC 24 V. • Setting parameters in CAV applications: Mode 2…10 V, Shut-off level 0.1 V In CAV applications shut-off level must not be set to 0.5 V, otherwise the open connection 3 is interpreted as damper CLOSED.VAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions www.belimo.us VAV-Compact MP • 2020-03 • Subject to Change Connection on the MP-BusPower topology 1235 MP + ~ – T UY A) A) Additional actuators and sensors (max. 8) topology (star, ring, tree or mixed forms are permitted). Supply and communication in one and the same 3-wire cable • no shielding or twisting necessary • no terminating resistors required Connection of active sensorsConnection of external switching contact 1235 MP + ~ – T UY A) A) Additional actuators and sensors (max. 8) • Supply AC / DC 24 V • Output signal DC 0...10 V (max. DC 0...32 V) • Resolution 30 mV 1235 MP + ~ – T UY A) p A) Additional actuators and sensors (max. 8) • Switching current 16 mA @ 24 V • Start point of the operating range must be parameterized on the MP actuator as ≥ 0.5 V Connection of passive sensors 1235 MP + ~ – T UY A) (max. 8) Local override control If no sensor is integrated, then connection 3 (Y) is available for the protective circuit of a local override control. Options: CLOSED – V max – OPEN Note: Functions only with AC 24 V supply! 1235 MP ~ T UY abcd Damper CLOSED V Max Damper OPEN Bus mode MP-Bus operation – VAV / CAV function See www.belimo.us / Bus and System Integration for detailed information on MP-Bus and installation (max. signal cable lengths, etc.) Sensor TypeOperating Temperature Range Belimo Part (e.g.) NTC (10K2)-60...+300°F [-50...+150°C] 01CT-5Lx 01DT-5Lx Ni1000-60...+320°F [-50...+160°C] 01CT-5Ex 01DT-5Ex PT1000-60...+320°F [-50...+160°C] 01CT-5Bx 01DT-5BxVAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions VAV-Compact MP • 2020-03 • Subject to Change www.belimo.us Control functions - VAV / CAV VAV-operating volumetric flow – Setting and controlDamper CLOSED via 0...10 V reference signal (Mode 2...10 V) 0% nom 100% 20% 0% 0 V10 V 2 V10 V 0%100% < max V V Reference signal 0…10 V Reference signal 2…10 V MP-Bus reference signal V V 2 V min 0.1 V min Reference signal 2…10 V Description: Setting parameters: Mode 2…10 V, Shut-off level 0.1 V or 0.5 V If the required switching threshold of 0.1 V cannot be attained, the value can be switched to 0.5 V with PC-Tool. FunctionStandard 0.1 VShut-off level 0.5 V Damper CLOSED<0.1 V<0.5 V V min >0.1...2 V>0.5 V...2 V V min ... V max 2...10 V2...10 V In CAV applications shut-off level must not be set to 0.5 V, otherwise the open connection 3 is interpreted as damper CLOSED. VAV-operating volumetric flow - ExampleCAV operating volumetric flow – setting 0% nom max 100% 20% 0% 0 V10 V 2 V min 10 V 0%100% < max V V V V 515 CFM 50 CFM 450 CFM max: V min: V Reference signal 0…10 V Reference signal 2…10 V MP-Bus reference signal V V Open-Loop (separate external VAV-Control) Control damper YVolumetric flow sensor value 100% 0% 0/210 V 0100%20406080 nom 10 V 0 V 0100%20406080 100% 0% Reference signal Y MP-Bus reference signal Volumetric flow min 100% 0% 10 V 0/2 V U [V] nom max 100% < max 20% 0% mi n ma x V V V V V V V V CAV stages Damper CLOSED Damper OPEN V nom - Volumetric flow rate used for calibration V max - Max desired volumetric flow rate V min- Minimum desired volumetric flow rateVAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions www.belimo.us VAV-Compact MP • 2020-03 • Subject to Change Setting and Tool function DesignationAdjustment values, limits, explanationsUnitsTools 5) Remarks Assistant App6) ZTH USPC-Tool System specific data Position16 characters e.g.: Office 4 6.OG ZLTextr/wr/w Designation16 Characters: Unit designation, etc.Textrrr/w AddressPP / MP1…8r/w 1)r/w r/wPP: 0…10 / 2…10 V MP1…8: MP mode V max20…100% [ V nom] /h / l/s / cfmr/wr/wr/w >/= V min V mid V min… V max /h / l/s / cfmr/wr/wr/w V min0…100% [ V nom] /h / l/s / cfmr/wr/wr/w </= V max System altitude0…3000 0...9800 Meter Feet r/wr/wAdaptation ∆p-Sensor to system altitude (above sea level) Controller settings Controller functionVolumetric flow / open loopr/w Mode0…10 / 2…10 Voltr/w 1)r/w 1)r/w CAV function CLOSED/ V min/ V max; Shut-off level CLOSED 0.1 V CLOSED/ V min/ V max; Shut-off level CLOSED 0.5 V r/wFor an explanation see 2) Positioning signal YStart value: 0.630; Stop value: 2.632 Voltrrr/w Feedback UVolume / damper position / ∆pr/wDefinition feedback signal Feedback UStart value: 0.08.0; Stop value: 2.010 Voltr/w Response when switched on (Power-On) 4) No action / Adaption / Synchronizationr/w Synchronization behaviorY=0 % Y=100 % r/wSynchronization to damper position 0 or 100 % Bus fail positionLast set point / Damper CLOSED V min / V max / Damper OPEN r/w Unit specific settings*) V nom 0...35,000 cfm / 0…60,000 m/h/h / l/s / cfmr/(w*)Unit specific adjustment value ∆p@ V nom 0.15...2 in WC [38 … 500 Pa]in WC [Pa]rr/(w*)Unit specific adjustment value NFC interface read / read&writerr/(w*) Label print function-wIncl. customer logo Other settings Direction of rotation (for Y = 100%) cw/ccwor / r/w 1) r/w 1) r/w Range of rotationAdapted 3) / programmed 30…95 r/w Torque100 / 75 / 50 / 25r/w% of nominal torque Renovating Existing systems (Retrofit of old VAV units with leaking damper *) Parameters are only accessible by VAV manufacturers and Retrofit Partners) Supress damper leakYes/Nor/(w*)Supresses volume display with the damper closed Operating data Setpoint / actual value Damper position /h / l/s / cfm Pa / % Trend display with print function and data storage on HD SimulationDamper CLOSED / OPEN V min / V max / motor stop Running timesOperating time, running time Ratio r Alarm messagesSetting range enlarged, mech. overload, Stop&Go ratio too high r/w Series numberDevice ID. incl. date of manufacture TypeType designationrrr Version display Firmware, Config table IDr Configuration data Print, create PDFYes Save to file Yes Log data / bookActivity log Yesincl. complete setting data Explanations 1) Access only on operating level 2 2) Shut-off level 0.1 / 0.5V - Application: VAV mode, in Mode 2…10 V, Damper CLOSED via 0…10 V control signal. If the required switching threshold of 0.1 V cannot be attained, the threshold can be switched to 0.5 V. Note on CAV application: the shut-off level must not be set to 0.5 V. If the line 3 (Y) is open, damper will be CLOSED instead, min will be activated. 3) within the mechanical limit. 4) The first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator carries out an adaption, which is when the operating range and position feedback adjust themselves to the mechanical setting range. The actuator then moves into the required position in order to ensure the volumetric flow defined by the positioning signal. 5) See www.belimo.us for function and version history. 6) iPhone devices require use of ZIP-BT-NFCVAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions VAV-Compact MP • 2020-03 • Subject to Change www.belimo.us Display and operation Adaption Power Status 3 1 2 4 Address 5 1Push-button and LED display green Off: On: Press key: No power supply or fault Operation Triggering the angle of rotation adaptation 2Push-button and LED display yellow Off: Flickering: On: Flashing: Press key: Normal operation MP communication active Adaptation or synchronizing process active Addressing request sent to MP master Confirmation of the addressing 3 Gear disengagement key Press key: Release key: Gear disengaged, motor stops, manual override possible Gear engaged, synchronization starts, followed by standard operation 4Service plugFor connecting the parameterization and service tools 5 NFC Logooperated with Belimo Assistant App MP-Bus mode: display panel wiring 1Off and2OnAC supply: connection 1 ( T ) and 2 () reversed 1Off and2OffDC supply: connection 1 ( – ) and 2 ( ) reversed The test is performed once to switch on the 24 V supply. For this test, the MP master must be connected to VAV-Compact. NFC, Smartphone – Assistant App Devices marked with NFC-Logo can be operated contactless via the NFC interface with Assistant App (..MV-D3-MP as of MY 2015). Prerequisites: – NFC-enabled Android smartphone – Belimo Assistant App (Google Play Store) The optimum tuning range is located within the antenna range indicated by the arrows. Align smartphone on the VAV-Compact so that both NFC antennas are superimposed. ZTH / PC-Tool - local service connection The settings and diagnostics of the VAV-Compact can be performed easily and rapidly with the Belimo PC-Tool or with the ZTH-US service tool. When using the PC-Tool, the ZTH US serves as an interface converter. 1325 AC 24 V DC 24 V– + T ~ UY BELIMO PC-Tool USB MP US B i escOK ZTH US RJ12ZK1-GEN ZTH US Download PC-Tool (MFT-P) from www.belimo.usVAV-Compact MP Volumetric flow compact control device for analog and MP-Bus versions www.belimo.us VAV-Compact MP • 2020-03 • Subject to Change ZTH / PC-Tool - remote connection The VAV-Compact can communicate with the service tools via the MP connection (wire 5). The connection can be made in operating mode in the junction box, tool socket of room controllers CR 24 or the control cabinet terminals. In MP-Bus mode, the tool is connected to MP master. When using the PC-Tool, the ZTH US serves as an interface converter. 1325 AC 24 V DC 24 V– + T ~ MP BELIMO PC-Tool USB MP US B i escOK RJ11ZK2-GEN GND UY white = GND green = MP ZTH US blue, do not connect Display and operation GatewaysDescriptionType Gateway MP to BACnet MS/TP, AC/DC 24 V UK24BAC Gateway MP to Modbus RTU, AC/DC 24 VUK24MOD Gateway MP to KNX/EIB, AC/DC 24 V, EIBA certifiedUK24EIB Gateway MP to L ONORKS , AC/DC 24 V, L ONARK certified KK UK24LON VAV-Compact Description VAV-Compact: Version with integrated BACnet and Modbus see www.belimo.us for more information and documentation Electrical accessoriesDescriptionType Connection cable 16 ft [5 m], to ZTH (RJ12) with service plugZK1-GEN Connection cable 16 ft [5 m], to ZTH (RJ11) with free wire ends ZK2-GEN ToolsDescriptionType Service Tool, for MFT/MP/BACnet/Modbus actuators and VAV controllersZTH US Belimo PC-Tool, software for adjustments and diagnostics (Free download at www.belimo.us) Belimo Assistant App, for Android smartphone Accessories ZTH USNext >