1 QUICK MOUNT VISUAL INSTRUCTION MANUAL PKB and PMB Actuators Near Field Communication (NFC) allows fast programming, commissioning and troubleshooting – even when the actuator is not powered it can be programmed Belimo Assistant App ZIP-BT-NFC (iPhone) 1 2 Option 1 Retrofit Form required Option 2 FCAPM 3 2 3 1 4 x 6 25 Nm 3 10 ... 15° 0 90 ** Note: Signal will be overridden with hand crank engaged in the port located closest to junction box. Position of actuator can be manually adjusted with hand crank. After use, make sure caps are fastened back on securely. 4 2 14 NEMA 4X NEMA 4X 4 2 1 NEMA 4X 4 2 1 3 4 NEMA 4X 9 in-lb2 QUICK MOUNT VISUAL INSTRUCTION MANUAL PKB and PMB Actuators 4 5 № 2 1 2 3 5 ** Note: Only use conduit connector provided by Belimo. Make sure conduit connections are also securely connected. 1 45 in-lb* 2 * Note: Use brass knockout to remove plastic if included with glandset. max. 3 ft-lbs O-ring PG11 Metric Thread 1/2” NPT 34 7 6 5 4 - 6mm 6 - 8mm 8 - 10mm Use supplied conduit fittings. Failure to do so may result in water intrusion and void NEMA 4X rating. Do not remove! Subject to change. © Belimo Aircontrols (USA), Inc.3 WIRING DIAGRAMS Floating Point PKB and PMB Actuators End SwitchesTemp Sensor VDC / 4 to 20 mA BACnet 24 to 240 VAC or 24 to 125 VDC N L Y 1 Y 2 N Com D + D - Com Bacnet D + D - Notes: 0˚ to 90˚ default 85˚ 41! Meets cULus requirements without the need of an electrical ground connection. 5 Only connect common to neg. (-) leg of control circuits. 1 Provide overload protection and disconnect as required. 46 Actuators may be controlled in parallel. Current draw and input impedance must be observed . 4 Two built-in auxiliary switches (2x SPDT), for end position indication, interlock control, fan startup, etc. Universal Power Supply (UP) models can be supplied with 24 VAC up to 240 VAC, or 24 VDC up to 125 VDC. Optional: end switch adjustment On/Off N L Y 1 Y 2 1 UP 46 ! Common + Hot Input CCW (open) Input CW (close) 24 to 240 VAC or 24 to 125 VDC N L Y 1 Y 2 1 UP 46 ! Common + Hot Input CCW (open) Input CW (close) 24 to 240 VAC or 24 to 125 VDC N L Y 1 Y 2 Common + Hot Input CCW (open) Input CW (close) 24 to 240 VAC or 24 to 125 VDC 1 UP 461 ! On/Off N L Y 1 Y 2 N 5 UP 46 24 to 240 VAC or 24 to 125 VDC - + Y 3 U5 Com - 24 VDC Out Y 3 0 - 10 VDC** U5/MP 0 - 10 VDC 1 **Control type, Direction and Fail position changes can be made via Belimo Assistant App, i.e. Floating or 4-20mA. ! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Power Status 5 6 Push-buttons and display B A 1 2 3 o p e n o p e n S2S3 S1 S5S6 S4 S5S6 S4 10° S2S3 S5S6 S4 S5S6 S4 S1S2S3S4S5S6 4 Disconnect power. 1 Gear disengagement Open the manual override cover and insert the hand crank. Manual override is possible. Manual override 2 Turn the hand crank until indicates the desired switching position and then remove the crank. A B 3 Auxiliary switch Open the auxiliary switch adjustment cover and properly seat the hand crank into the actuator. Turn the crank until the arrow points to the vertical line. 4 Terminals Connect continuity tester to S4 + S5 or to S4 + S6. If the auxiliary switch should switch in the opposite direction, rotate the hand crank by 180˚. 5 LED Display Green 6 LED Display Yellow Off: No power supply or malfunction, On: In operation Press button: Triggers test run, followed by standard mode. 6 LED Display Yellow Off: Standard mode, On: Test run active. 6 3 NEMA 4X 12 in-lb 2 1 Power Wire separator 4 № 2 QUICK MOUNT VISUAL INSTRUCTION MANUAL PKB and PMB Actuators WARNING: The wiring technician must be trained and experienced with electronic circuits. Disconnect power supply before attempting any wiring connections or changes. Make all connections in accordance with wiring diagrams and follow all applicable local and national codes. Provide disconnect and overload protection as required. Use copper, twisted pair, conductors only. If using electrical conduit, the attachment to the actuator must be made with flexible conduit.Next >