Technical Data2215Power Supply24 VAC, ±20%, 50/60 Hz, 24 VDC, -10% / +20%Power Consumption Running6.5 WPower Consumption Holding3 WTransformer Sizing9 VA (class 2 power source)Electrical Connection18 GA applicance rated cable with 1/2” conduit connector protected NEMA 2 (IP54) 3ft [1m] 10ft [3m] and 16ft [5m]Overload Protectionelectronic throughout 0° to 95° rotationOperating Range Y2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor), variable (VDC, PWM, floating point, on/off)Feedback Output U2 to 10 VDC, 0.5 mA max, VDC variableAngle of Rotation95°, adjustable with mechanical end stop, 35° to 95°Nominal TorqueMin. 90 in-lbs [10 Nm]Direction of Rotation (Motor)reversible with built-in switchDirection of Rotation (Fail-Safe)reversible with CW/CCW mountingPosition Indicationvisual indicator, 0° to 95° (0° is full spring return position)Manual Override5 mm hex crank (3/16” Allen), suppliedRunning Time (Motor)default 150 sec, variable 40...150 sec, constant, independent of loadRunning Time (Fail-Safe)<20 sec @ -4°F to 122°F [-20°C to 50°C], <60 sec @ -22°F [-30°C]Override Controlmin. position = 0% , mid. Position = 50% , max. position = 100% (Default)Ambient Humiditymax. 95% RH non-condensingAmbient Temperature Range-22°F to 122°F [-30°C to 50°C]Storage Temperature Range-40°F to 176°F [-40°C to 80°C]HousingNEMA 2, IP54, UL Enclosure Type 2Housing Materialzinc coated metal and plastic casingAgency Listings†cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/ECNoise Level (Motor)<50 dB (A) Noise Level (Fail-Safe)<62 dB (A) Servicingmaintenance freeQuality StandardISO 9001Weight4.4 lb [2 kg]Degree of Protection IEC/ENIP54*Variable when configured with MFT options.†Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3NFX24-MFT-X1Modulating, Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 03/26/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsINSTALLATION NOTESAActuators with appliance cables are numbered.Provide overload protection and disconnect as required.Actuators may also be powered by 24 VDC.Only connect common to negative (-) leg of control circuits.A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not compatible.Actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed.IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blk (1)Red (2)Pnk (4)Wht (3)Org (5)LineVoltsPositionFeedback VDC(+)(–)1318CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer2On/Off LineVolts(–)(+)Position Feedback VDC11810Blk (1)Red (2)Pnk (4)Wht (3)Org (5)CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer (AC Only)2Floating Point (–)(+)LineVoltsΩ500 Ω1/4 wattControl Signal VDC / mA135187Blk (1)Red (2)Pnk (4)Wht (3)Org (5)CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer2VDC/mA Control LineVolts (–) (+) PositionFeedback VDC1188Blk (1)Red (2)Pnk (4)Wht (3)Org (5)CommonHot +Y2 Input Y1 InputU Output 24 VAC Transformer (AC Only)2PWM ControlNFX24-MFT-X1Modulating, Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 03/26/2018 - Subject to change. © Belimo Aircontrols (USA), Inc. Functions0%50%100%Control mode acc. to Y1MinMidMaxNormalabcOrg (5) 24 VAC Transformer (AC Only) U Output15Blk (1) CommonRed (2) + Hot Pnk (4) Wht (3) (–)(+)LineVoltsBCAVDC / mAControl Signal Y2 Input Y1 Input127182Override ControlNFX24-MFT-X1Modulating, Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 03/26/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >