Technical Data2196Power Supply24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%Power Consumption Running4.5 WPower Consumption Holding1.5 WTransformer Sizing7 VA (class 2 power source)Electrical Connection3ft [1m], 18 GA plenum rated cable with 1/2” conduit connector (10ft [3m] and 15ft [5m] avail.)Overload Protectionelectronic throughout 0° to 95° rotationOperating Range Y2 to 10 VDC, 4 to 20 mA w/ ZG-R01 (500 Ω, 1/4 W resistor), variable (VDC, floating point, on/off)Input Impedance100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for PWM, floating point and On/OffFeedback Output U2 to 10 VDC, 0.5 mA max, VDC variableAngle of RotationMax. 95°, adjustable with mechanical stopNominal TorqueMin. 360 in-lbs [40 Nm]Direction of Rotation (Motor)reversible with built-in switchPosition Indicationreflective visual indicator (snap on)Manual Overrideexternal push buttonRunning Time (Motor)default 150 sec, variable 90...150 secAmbient Humidity5 to 95% RH non-condensingAmbient Temperature Range-22°F to 122°F [-30°C to 50°C]Storage Temperature Range-40°F to 176°F [-40°C to 80°C]HousingNEMA 2, IP54Agency Listings†cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/ECNoise Level (Motor)<45 dB (A) Servicingmaintenance freeQuality StandardISO 9001Weight4.9 lb [2.2 kg]Degree of Protection IEC/ENIP54†Rated Impulse Voltage 800V, Type action 1, Control Pollution Degree 3.GMX24-MFT-X1Modulating, Non-Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 03/27/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsINSTALLATION NOTESAActuators with appliance cables are numbered.Provide overload protection and disconnect as required.Actuators may also be powered by 24 VDC.Only connect common to negative (-) leg of control circuits.A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC.Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line.For triac sink the Common connection from the actuator must be connected to the Hot connection of the controller. Position feedback cannot be used with a triac sink controller; the actuator internal common reference is not compatible.IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number 40155).46Actuators may be controlled in parallel. Current draw and input impedance must be observed.47Master-Slave wiring required for piggy-back applications. Feedback from Master to control input(s) of Slave(s).Meets cULus requirements without the need of an electrical ground connection.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blk (1)Red (2)Pnk (4) Wht (3)Org (5) LineVolts24 VAC TransformerPositionFeedback VDC(+)(–)Common+ Hot Y2 Input Y1 InputU Output A134647On/Off 24 VAC Transformer (AC Only)Blk (1) Common Red (2) + Hot Wht (3) Y1 InputOrg (5) U Output Pnk (4) Y2 Input LineVolts(–)(+)Position Feedback VDC1104647Floating Point Blk (1) CommonRed (2) + HotPnk (4) Y2 InputWht (3) Y1 InputOrg (5) U Output(–)(+)LineVolts24 VAC Transformer500 1/4 wattControl Signal VDC / mAA13546477VDC/mA Control Blk (1) CommonRed (2) + HotWht (3) Y1 InputPnk (4) Y2 InputOrg (5) U OutputLineVolts24 VAC Transformer (AC only) (–) (+)PositionFeedback VDCA184647PWM ControlGMX24-MFT-X1Modulating, Non-Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 03/27/2018 - Subject to change. © Belimo Aircontrols (USA), Inc. Functions0%50%100%Control mode acc. to Y1MinMidMaxNormalabcOrg (5) 24 VAC Transformer (AC Only) U Output15Blk (1) CommonRed (2) + Hot Pnk (4) Wht (3) (–)(+)LineVoltsBCAVDC / mAControl Signal Y2 Input Y1 Input127182Override Control Blk (1) CommonRed (2) + HotWht (3) Y1 InputOrg (5) U OutputMaster24 VAC TransformerLine VoltsControl Signal (–)(+)Blk (1) CommonRed (2) + HotWht (3) Y1 InputOrg (5) U Output1546477Slave1Master - SlaveGMX24-MFT-X1Modulating, Non-Spring Return, 24 V, Multi-Function Technology®800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 03/27/2018 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >