Technical Data 314660 Fluidchilled or hot water, up to 60% glycol, steam Flow characteristicmodified equal percentage Controllable flow rangestem up - open A – AB Valve Size [mm]0.75” [20] Pipe connectionNPT female ends HousingBronze Stemstainless steel Stem sealEPDM O-ring SeatBronze Valve plugbrass Body Pressure RatingANSI Class 250, up to 400 psi below 150°F ANSI Class250 Maximum Inlet Pressure (Steam)35 psi [241 kPa] Max Differential Pressure (Steam)20 psi [103 kPa] Rangeability Sv100:1 Cv5.5 Weight2.0 lb [0.9 kg] Fluid Temp Range (water)20...280°F [-7...138°C] Leakage rateANSI Class VI Servicingrepack kits available Flow/Mounting Details Application This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include unit ventilators, VAV box re-heat coils and bypass loops. This valve is suitable for use in hydronic systems with variable flow. Bronze and stainless steel trim valves can be used for steam applications, depending on actuator and close-off combinations. Suitable Actuators Non-SpringSpringElectronic fail-safe G220B-JLVB(X)LFLVKB(X) Dimensions (Inches [mm]) B A C D E F LF ABCDEF 7.9” [200]3.4” [86]9.7” [247]8.2” [208]1.2” [30]4.9” [125] Safety Notes WARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov Piping The valves should be mounted in a weather-protected area in a location that is within the ambient limits of the actuator. Allow sufficient room for valve with actuator and for service. The G2 and G3 preferred mounting position of the valve is with the valve stem vertical above the valve body, for maximum life. However, the assemblies can be mounted with the valve stem vertical or horizontal in relation to the pipe. The actuators should never be mounted underneath the valve, as condensation can build up and result in a failure of the actuators. G220B-J Technical Data Sheet 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 10/10/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.Dimensions (Inches [mm]) E F B A C D LV ABCDEF 8.6” [218]3.4” [86]8.9” [226]7.4” [188]1.9” [48] Dimensions (Inches [mm]) E F B A C D LVK ABCDEF 9.7” [246]3.4” [86]9.6” [244]8.1” [206]1.9” [48] G220B-J Technical Data Sheet 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 10/10/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.Technical Data 283160 Power Supply24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power consumption in operation2.5 W Power consumption in rest position 1.5 W Transformer sizing6 VA (class 2 power source) Electrical Connection18 GA plenum cable, 3 ft [1 m], with 1/2” conduit connector, degree of protection NEMA 2 / IP54 Overload Protectionelectronic throughout full stroke Electrical Protectionactuators are double insulated Operating RangeDC 2...10 V (default), 4...20 mA w/ ZG-R01 (500 Ω , 1/4 W resistor), variable (VDC, PWM, on/off, floating point) Operating range Y variableStart point DC 0.5...30 V End point DC 2.5...32 V Input Impedance100 k Ω for DC 2...10 V (0.1 mA), 500 Ω for 4...20 mA, 1500 Ω for PWM, On/Off and Floating point Position FeedbackDC 2...10 V Stroke0.75” [19 mm] Actuating force motor115 lbf [500 N] Direction of rotation motorreversible with switch Direction of motion fail-safereversible with switch Position indicationMechanically, with pointer Manual override4 mm hex crank (shipped w/actuator) Running Time (Motor)90 s constant, independent of load Running time fail-safe<35 s Bridging time2 s delay before fail-safe activates Pre-charging time5...20 s Ambient humiditymax. 95% r.H., non-condensing Ambient temperature-22...122°F [-30...50°C] Storage temperature-40...176°F [-40...80°C] Degree of ProtectionIP54, NEMA 2, UL Enclosure Type 2 Housing materialDie cast aluminium and plastic casing Agency ListingcULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/EC Noise level, motor55 dB(A) Noise level, fail-safe60 dB(A) Maintenancemaintenance-free Quality StandardISO 9001 Weight3.53 lb [1.6 kg] † Use flexible metal conduit. Push the listed conduit fitting device over the actuator’s cable to butt against the enclosure. Screw in conduit connector. Jacket the actuators input wiring with listed flexible conduit. Properly terminate the conduit in a suitable junction box. Rated impulse Voltage 800V. Type of action 1. Control pollution degree 3. †Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3 Safety Notes WARNING: For Belimo products sold in California: these products do or may contain chemicals which are known to the State of California to cause cancer and or birth defects or other reproductive harms. For more information see www.p65warnings.ca.gov. LVKB24-MFT Technical Data Sheet Modulating, Fail-Safe Operation, Linear, 24 V, Multi-Function Technology® 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 09/11/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring Diagrams INSTALLATION NOTES Actuators may be connected in parallel. Power consumption and input impedance must be observed. Actuators may also be powered by 24 VDC. A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10 VDC. Control signal may be pulsed from either the Hot (Source) or Common (Sink) 24 VAC line. For triac sink the common connection from the actuator must be connected to the hot connection of the controller. Contact closures A & B also can be triacs. A & B should both be closed for the triac source and open for triac sink. Actuators with plenum cable do not have numbers; use color codes instead. Meets cULus requirements without the need of an electrical ground connection. ! WARNING! LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Blk (1) - Common Red (2) Hot Wht (3) Y 1 Input Org (5) U Output Line Volts 24 VAC Transformer 2 to 10 VDC Feedback Signal (+) (–) 318 On/Off Line Volts (–) (+) 24 VAC Transformer Blk (1) – Common Red (2) + Hot Wht (3) Y 1 Input Pnk (4) Y 2 Input Org (5) U Output ABAB Direction of rotation switch A B Feedback Signal 2 to 10 VDC 218 8 9 Floating Point Blk (1) - Common Red (2) + Hot Wht (3) Y 1 Input Org (5) U Output (–) (+) Line Volts 24 VAC Transformer Control Signal VDC/mA 318 7 500 1/4 W VDC / 4 to 20 mA Functions 0% 50% 100% Control mode acc. to Y Min Mid Max Normal abc 500 Blk (1) - Common Red (2) + Hot Org (5) U Output Wht (3) Y 1 Input (–) (+) Line Volts 24 VAC Transformer (AC Only) B C A 1/4 W VDC/mA Control Signal 18 7 Override Control Min, Mid, Max Positions LVKB24-MFT Technical Data Sheet Modulating, Fail-Safe Operation, Linear, 24 V, Multi-Function Technology® 800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN Date created, 09/11/2019 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >