800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN2Technical DataServicechilled, hot water, 60% glycol,steam to 50 psiFlow characteristicmodified equal percentage, unidirectionalControllable flow range82°Sizes2” to 30”Type of end fittingfor use with ASME/class 125/150 flangeMaterialsBodyDiscSeatShaftGland sealBushingscarbon steel full lug316 stainless steelRPTF17-4 PH stainlessPTFEglass backed PTFEMedia temperature range-20°F to 400°F [-30°C to 204°C]Body pressure ratingANSI Class 150 Close-off pressure285 psiRangeability100:1 (for 30 deg to 70 deg range)Maximum velocity32 FPSLeakagebubble tight• Bubble tight shut-off to ANSI Class 150 Standards• Long stem design allows for 2” insulation minimum• Valve Face-to-face dimensions comply with API 609 & MSS-SP-68• Designed to be installed between ASME/ANSI B16.5 Flanges• Completely assembled and tested, ready for installationApplicationThese valves are designed to meet the needs of HVAC and Commercial applications requiring positive shut-off for liquids at higher pressures andtemperatures. Typical applications include chiller isolation, cooling towerisolation, change-over systems, large air handler coil control, bypass andprocess control applications. The large C values provide for an economicalcontrol valve solution for larger fl ow applications.Dead End ServiceFollow all described pre-installation and installation procedures. Valves are capable of bubble tight, dead end closure with either the upstream ordownstream fl ange removed.ValveNominal SizeTypeSuitable ActuatorsCv 90°Cv 60°IN2-waySpringNon-Spring10252”F650-150SHP AF SeriesM SeriesY Series146802½”F665-150SHP 2281253F680-150SHP 4512484F6100-150SHP 143925”F6125-150SHP 11036076F6150-150SHP 20611358F6200-150SHP 351719310F6250-150SHP 4837266012”F6300-150SHP 685735924”F6350-150SHP 9287486516”F6400-150SHP 11500327018”F6450-150SHP 14420759020”F6500-150SHP 220501155024”F6600-150SHP 343881801230”F6750-150SHP MODON/OFFValveSize10°20°30°40°50°60°70°80°90°F650-150SHP2”1021.506.101263956779102F665-150SHP½1462.208.8023755811042146F680-150SHP3”2283.4014325787125171221228F6100-150SHP4”4516.802763114171248338437451F6125-150SHP5”7141143100180271393536693714F6150-150SHP6”1103176615427841960782710701103F6200-150SHP8”206431122895207841135154820022064F6250-150SHP10”35175321149288613361934263834113517F6300-150SHP12”483773290677121918382660362846924837F6350-150SHP14”6857103411960172826063771514366516857F6400-150SHP16”92871395571300234035295108696590089287F6450-150SHP18”11400171684159628734332627085501105811400F6500-150SHP20”144202168652019363454807931108151398714420F6600-150SHP24”22050331132330875557837912128165382138922050F6750-150SHP30”343884911965458582531244518012245633275034388F6 Series 2-Way, ANSI Class 150 Butterfly ValveReinforced Tefl on Seat, 316 Stainless Disc50904 - 02/12 - Subject to change. © Belimo Aircontrols (USA), Inc.800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEAN27Maximum Dimensions (Inches)ValveSizeCv 90°ABCD(Max)BHCNo. of HolesLug BoltActuatorClose-Off (PSI)F650-150SHP2101.759.009.0019.504.755/8-11 UNC2*AF150pring ReturnF665-150SHP2½”1461.889.009.0020.005.505/8-11 UNC150F680-150SHP3”2281.929.009.0020.506.005/8-11 UNC150F6100-150SHP4”4512.139.009.0021.007.505/8-11 UNC150F650-150SHP1021.759.009.0019.504.755/8-11 UNCGK285lectronic Fail-SafeF665-150SHP2½”1461.889.009.0020.005.505/8-11 UNC285F680-150SHP32281.929.009.0020.506.005/8-11 UNC285F6100-150SHP4”4512.139.009.0021.007.505/8-11 UNC150F6100-150SHP4”4512.139.009.0021.007.505/8-11 UNC2*GK285F650-150SHP21021.759.009.0019.504.755/8-11 UNCGM285on-Spring ReturnF665-150SHP½”1461.889.009.0020.005.505/8-11 UNC285F680-150SHP3”2281.929.009.0020.506.005/8-11 UNC285F6100-150SHP44512.139.009.0021.007.505/8-11 UNC150F6100-150SHP4”4512.139.009.0021.007.505/8-11 UNC2*GM285F650-150SHP21021.758.008.0022.254.755/8-11 UNCSY2…285F665-150SHP2½”1461.888.008.0022.755.505/8-11 UNC285F680-150SHP3”2281.928.008.0023.006.005/8-11 UNC285F6100-150SHP4”4512.138.008.0023.757.505/8-11 UNC285F6125-150SHP5”7142.258.008.0024.258.503/4-10 UNC285F6150-150SHP6”11032.298.008.0024.759.503/4-10 UNC285F6200-150SHP820642.5012.0012.0032.0011.753/4-10 UNCSY3…150SY4…285F6250-150SHP10”35172.8112.0012.0033.0014.25127/8-9 UNCSY4…285F6300-150SHP12”48373.2312.0012.0035.0017.00127/8-9 UNCSY4…150SY5…285F6350-150SHP14”68573.6214.0014.0036.0018.75121-8 UNCSY5…150SY7…285150F6400-150SHP16”92874.0014.0014.0037.5021.25161-8 UNCSY8…285F6450-150SHP1811404.5014.0014.0042.2522.7511 1/8-8 UNCSY7…150SY8…285F6500-150SHP20”144205.0014.0014.0049.5025.00201 1/8-8 UNCSY8…150SY10…285F6600-150SHP24”220506.0614.0014.0056.2529.50201 1/4-8 UNCSY10…150F6750-150SHP30”343886.7514.0014.0066.5836.00281 1/4-8 UNCSY12…125F6 Series 2-Way, ANSI Class 150 Butterfl y ValveReinforced Tefl on Seat, 316 Stainless DiscDimension “A” does not include flange gaskets. (2 required per valve)Application Notes1. Valves are rated at 285 psi differential pressure in the closed position@ 100°F media temperature.2. Valves are furnished with lugs tapped for use between ANSI Class 125/150 flanges conforming to ANSI B16.5 Standards.3. 2-way assemblies are furnished assembled, calibrated and tested, ready forinstallation.4. Dimension “D” allows for actuator(s) removal without the need to remove thevalve from the pipe.5. Weather shields are available, dimensional data furnished upon request.6. Flange gaskets (2 required, not provided with valve) MUST be used betweenvalve and ANSI flange.7. Flange bolts are not included with the valve. These are furnished by others.DimensionsDBCABHC102SHP series valves have a preferred flow direction.PreferredFlowrate50904 - 02/12 - Subject to change. © Belimo Aircontrols (USA), Inc.800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA58 06/10 - Subject to change. © Belimo Aircontrols (USA), Inc.GKX24-MFT-X1 Actuators, Multi-Function TechnologyDimensions with 2-Way ValveDBCABHCDimensions (Inches)Non-Fail Safe (psi)ValveSizeABCD(Max)BHCGKF680HD3”1.699.009.0021.036.00200F6100HDU4”1.929.009.0021.537.5050F6125HDU5”2.089.009.0022.538.5050F650-150SHP2”1.759.009.0020.034.75285F665-150SHP2½”1.889.009.0020.535.50285F680-150SHP3”1.929.009.0021.036.00285F6100-150SHP4”2.139.009.0021.537.50150F650-300SHP2”1.759.009.0020.035.00285F665-300SHP2½”1.889.009.0020.535.88285F680-300SHP3”1.929.009.0021.036.63285F6100-300SHP4” 2.139.009.0021.537.88150AM_GM_LineRevisedTechnical DataGKX24-MFT-X1Power supply24VAC ±20% 50/60Hz 24VDC ±10%Power consumption12W (3W)Transformer sizing21VA (class 2 power source)Electrical connection18 GA plenum rated cable ½" conduit connector protected NEMA 2 (IP54) 3 ft [1m] 10 ft [3m] 16 ft [5m]Overload protectionelectronic throughout 0 to 95 rotationOperation range Y2 to 10 VDC, 4 to 20mA (default) variable (VDC,PWM, floating point, on/off)Input impedance100kW (0.1 mA), 500W1500W (PWM, floating point, on/off)Feedback output U2 to 10VDC, 0.5mA max, VDC variableAngle of rotationmax. 95°, adjustable with mechanical stop electronically variableDirection of rotationreversible with switch Fail-safe positionadjustable with dial or tool 0 to 100% in 10% incrementsPosition indicationreflective visual indicator (snap-on)Manual overrideexternal push buttonRunning time normal operation fail-safe 95 seconds (default), variable 90 to 150 seconds 35 secondsHumidity5 to 95% RH non-condensing (EN 60730-1)Ambient temperature-22°F to +122°F [-30°C to +50°C]Storage temperature-40°F to +176°F [-40°C to +80°C]HousingNEMA2, IP54, UL enclosure type 2Housing materialUL94-5VAAgency listcULus acc. to UL 60730-1A/-2-14 CAN/CSA E60730-1:02 CE acc. to 2004/108/EEC and 2006/95/ECNoise level< 45dB(A) Servicingmaintenance freeQuality standardISO 9001Dimensions with 3-Way ValveDimensions (Inches)Non-Fail Safe (psi)ValveSizeABCD(Max)BHCGKF780HDU3”5.507.207.2016.786.00200F750-150SHP2”4.506.256.2517.034.75150F765-150SHP2½”5.006.886.8817.535.50150F780-150SHP3”5.507.427.4218.036.00150Single_Butterfly100DABC800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA59 06/10 - Subject to change. © Belimo Aircontrols (USA), Inc.GKX24-MFT-X1 Actuators, Multi-Function TechnologyWARNING Live Electrical Components!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.W399_ButterflyVDC/4-20 mAW399_ButterflyPWMW399_ButterflyOn/Off controlW399_ButterflyFloating Point controlWiring Diagrams1Provide overload protection and disconnect as required.3Actuators may also be powered by 24 VDC.4Position feedback cannot be used with Triac sink controller. The actuator internal common reference is not compatible.5Control signal may be pulsed from either the Hot (source) or the Common (sink) 24 VAC line.8Contact closures A & B also can be triacs. A & B should both be closed for triac source and open for triac sink.9For triac sink the common connection from the actuator must be connected to the hot connection of the controller.Meets UL requirements without the need of an electrical ground connection.The ZG-R01 500 W resistor may be used.NOTE: Wiring diagrams shown are for single actuator mounted solutionsNext >