Technical Data313783Servicechilled, hot water, up to 60% glycolFlow Characteristicmodified equal percentageControllable Flow Range90° rotationSize [mm]8” [200]End FittingFor use with ANSI Class 125/150 flangesBodyductile iron ASTM A536Body Finishpolyester powder coatedSeatEPDMShaft420 stainless steelBushingssteel, PTFE (typical)Disc304 stainless steelBody Pressure Rating [psi]232Number of Bolt Holes8Lug Threads3/4-10 UNCMedia Temperature Range (Water)-22°F to 250°F [-30°C to 120°C]Close-Off Pressure50 psiRangeability10:1Maximum Velocity12 FPSCv3136 Weight36.4 lbs [16.5 kg]Leakage0%Servicingmaintenance freeWhen installing in Victaulic piping systems, use Victaulic 41 series flange nipples. 741 flanges not recommended without the use of adapter rings. L-Series Butterfly valves are designed to be installed between ANSI 125/150 flat-faced, raised face, slip-on or weld neck flanges. Do NOT use flange gaskets on L-Series Butterfly valves.Flow Pattern0102010305040608070902030406050708010090100% OF MAXIMUM FLOW% OF VALVE OPENINGApplicationValve is designed for use in ANSI flanged piping systems to meet the needs of bi-directional high flow HVAC hydronic applications with 0% leakage. Typical applications include cooling tower bypass, primary flow change-over systems, and large air handler coil control.Jobsite NoteValve assembly should be stored in a weather protected area prior to installation. Reference the butterfly valve installation instruction for additional information.Flow/CvCv 10°Cv 20°Cv 30°Cv 40°Cv 50°Cv 60°Cv 70°Cv 80°Cv 90°2 89 188 408 727 1202 1903 2854 3136 Suitable Actuators Non-SpringF6200LUPRB(X)Dimensions (Inches [mm])ABCDEDFPRB, PRXABCDEF11.95” [303.5]2.36” [59.9]23.91” [607.3]17.37” [441.2]6.51” [165.4]F6200LU, 8”, 2-Way Butterfly Valve (Undercut)Resilient Seat, 304 Stainless Steel Disc800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 06/12/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Technical Data307561Power Supply24...240 VAC, -20% / +10%, 50/60 Hz, 24...125 VDC, -20% / +10%Power Consumption Running20 W @ 24 V, 18 W @ 120 V, 20 W @ 230 VPower Consumption Holding3.5 W @ 24 V, 4 W @ 120 V, 6 W @ 230 VTransformer Sizing20 VA @ 24 VAC/DC (class 2 power source), 23 VA @ 120 VAC/DC, 52 VA @ 230 VACElectrical Connectionterminal blockOverload Protectionelectronic thoughout 0° to 90° rotationOperating Range Y2 to 10 VDC, 4 to 20 mA variable (VDC, floating point, on/off)Input Impedance100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA, 1500 Ω for On/OffFeedback Output U2 to 10 VDC, 0.5 mA max, VDC variableAngle of Rotation90°Torque motorMin. 1400 in-lbs [160 Nm]Direction of Rotation (Motor)reversible with appPosition Indicationintegral pointer and bottom mounted reflective indicatorsManual Override7 mm hex crank, suppliedRunning Time (Motor)35 secAmbient Humidity5 to 100% RH (UL Type 4)Ambient Temperature Range-22°F to 122°F [-30°C to 50°C]Storage Temperature Range-40°F to 176°F [-40°C to 80°C]HousingNEMA 4X, IP66/67, UL Enclosure Type 4Housing MaterialAluminum die cast and plastic casingAgency Listings†cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EC and 2006/95/ECNoise Level (Motor)68 dB (A) Servicingmaintenance freeQuality StandardISO 9001Weight12.8 lbs [5.8kg]Auxiliary switch2 x SPDT, 3A resistive (0.5A inductive) @ 250 VAC, one set at 10°, one adjustable 0° to 90°CommunicationBACnet MS/TPPassive Sensor Inputs2 (PT1000) (NI1000) (NTC)ApplicationPR Series valve actuators are designed with an integrated linkage and visual position indicators. For outdoor applications, the installed valve must be mounted with the actuator at or above horizontal. For indoor applications the actuator can be in any location including directly under the valve.OperationThe PR series actuator provides 90° of rotation and a visual indicator shows the position of the valve. The PR Series actuator uses a low power consumption brushless DC motor and is electronically protected against overload. A universal power supply is furnished to connect supply voltage in the range of 24-240 VAC and 24-125 VDC. Included is a smart heater with thermostat to eliminate condensation. Two auxiliary switches are provided; one set at 10° open and the other is field adjustable. Running time is field adjustable from 30-120 seconds by using the Near Field Communication (NFC) app and a smart phone.†Use 60°C/75°C copper wire size range 12-28 AWG, stranded or solid. Use flexible metal conduit. Push the listed conduit fitting device over the actuator’s cable to butt against the enclosure. Screw in conduit connector. Jacket the actuators input wiring with listed flexible conduit. Properly terminate the conduit in a suitable junction box. Rated impulse Voltage 4000V. Type of action 1. Control pollution degree 3.PRXUP-MFT-T-250Modulating, Non-Spring Return, 24-240 V, NEMA 4X with BACnet800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/29/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Wiring DiagramsMeets cULus requirements without the need of an electrical ground connection.UPUniversal Power Supply (UP) models can be supplied with 24 VAC up to 240 VAC, or 24 VDC up to 240 VDC.Disconnect power.Provide overload protection and disconnect as required.Two built-in auxiliary switches (2x SPDT), for end position indication, interlock control, fan startup, etc.Only connect common to negative (-) leg of control circuits.46Actuators may be controlled in parallel. Current draw and input impedance must be observed.!WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. N L Y1Y2 Common + Hot Input CCW (open)Input CW (close)24 to 240 VAC or 24 to 125 VDC1UP461!On/Off N L Y1Y2 1UP46!Common + Hot Input CCW (open)Input CW (close)24 to 240 VAC or 24 to 125 VDCFloating Point N L Y1Y2 N5UP4624 to 240 VACor 24 to 125 VDC-+ Y3U5Com -24 VDC Out (max 5mA) Y3 0 - 10 VDC, 4-20 mAU5/MP 0 - 10 VDC1Modulating N L Y1Y2 N24 to 240 VACor24 to 125 VDCComD +D -ComBacnet D + D -BACnetPRXUP-MFT-T-250Modulating, Non-Spring Return, 24-240 V, NEMA 4X with BACnet800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/29/2017 - Subject to change. © Belimo Aircontrols (USA), Inc. T1 ComT1T2 ComT2Temperature Sensors 0˚ to 90˚ default 85˚41Auxiliary SwitchesPRXUP-MFT-T-250Modulating, Non-Spring Return, 24-240 V, NEMA 4X with BACnet800-543-9038 USA866-805-7089 CANADA203-791-8396 LATIN AMERICA / CARIBBEANDate created, 11/29/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.Next >